C A B L E

A S S E M B L Y

I N S T R U C T I O N

Controller Model: Maple OIT Model:

Allen-Bradley MicroLogix 1000, 1200, 1500 BLU300 Series

Communication Type: RS-232 with 8-pin connector at PLC


The 8-pin connector for the Allen-Bradley MicroLogix 1000, 1200, or 1500 PLC is a special part only available through Allen-Bradley. We recommend that you purchase Maple Systems Cable (P/N 7445-0040) or purchase a cable from Allen-Bradley. This wiring diagram shows how Maple Systems Cable (P/N 7445-0040) is assembled.

4-40 x 1/2 Retainer Screw, 2 places DE9S Connector & DE9 Backshell A Custom 8 Pin Connector

4 Conductor 24 AWG Shielded cable

OIT END NOTES: Shield wire must be terminated to connector metal shell. 1
2

PLC END

Solder shield wire to the DE9S connector metal shell. Install heatshrink tubing over the shield wire to avoid shorting.

OIT
9S RXD 2 TXD 3 Return 5

PLC
2 Shield 1 8P 7 4 2 TXD RXD Signal Ground

1 3 6 4 7

2 5 8

Pin Con guration View A-A (Solder Side)

1025-0040, Rev 00

C A B L E

A S S E M B L Y

I N S T R U C T I O N

Controller Model: Maple OIT Model:

Allen-Bradley 2-port MicroLogix (DF1) BLU300 Series

Communication Type: RS-232 with DE9 connector at PLC


Use the wiring diagram and illustration to assemble a communication cable for use with an Allen-Bradley 2-port MicroLogix Family PLC. Maple Systems products use the DF1 protocol to communicate with this PLC. This cable is for communication directly from port 2 (9-pin) on the 2 port versions of the MicroLogix 1500.

4-40 x 1/2 Retainer Screw, 2 places DE9S Connector & DE9 Backshell

18 AWG Green wire

To Chassis Ground
DE9 Backshell

4 Conductor 24 AWG Shielded cable

PLC END NOTES: 1 Twist together 18 AWG green wire and shield wire. Solder wires and insulate with heatshrink to avoid shorting. Solder shield wire to the DE9S connector metal shell. Install 2 heatshrink tubing over the shield wire to avoid shorting.
1 Green

OIT END

4-40 x 1/2 Retainer Screw, 2 places

Pin 1 DE9S Connector

To Chassis Ground PLC

OIT
9S RXD 2 TXD 3 Return 5 2

Shield

9S 3 TXD 2 RXD 5 Signal Ground

1025-0004, Rev 00

C A B L E

A S S E M B L Y

I N S T R U C T I O N

Controller Model: Maple OIT Model:

Allen-Bradley SLC500 BLU300 Series

Communication Type: RS-232 with DE9 connector at PLC


Use the wiring diagram and illustration to assemble a communication cable for use with an Allen-Bradley SLC500 PLC. Maple Systems products use the DF1 protocol to communicate with this PLC. This cable is for communication directly from the SLC 5/03, 5/04, 5/05 DF1 port or through the 1747-KE Communication Module of the SLC5/01 and SLC 5/02.

4-40 x 1/2 Retainer Screw, 2 places DE9S Connector & DE9 Backshell

18 AWG Green wire

To Chassis Ground
DE9 Backshell

4 Conductor 24 AWG Shielded cable

PLC END NOTES: 1 Twist together 18 AWG green wire and shield wire. Solder wires and insulate with heatshrink to avoid shorting. Solder shield wire to the DE9S connector metal shell. Install 2 heatshrink tubing over the shield wire to avoid shorting.
1 Green

OIT END

4-40 x 1/2 Retainer Screw, 2 places

Pin 1 DE9S Connector

To Chassis Ground PLC

OIT
9S RXD 2 TXD 3 Return 5 2

Shield

9S 3 TXD 2 RXD 5 Signal Ground

1025-0004, Rev 00