Você está na página 1de 15

CR

Centrifugal roof exhausters * Vertical discharge: Roff mounted and Wall mounted * Horizontal discharge

Extractores Centrfugos de Tejado * Descarga Vertical: Montaje en techo y pared * Descarga Horizontal

CR

Centrifugal roof exhausters * Vertical discharge: Roff mounted and Wall mounted * Horizontal discharge Extractores Centrfugos de Tejado * Descarga Vertical: Montaje en techo y pared * Descarga Horizontal

General Information

CR range of products is a family of High Efficiency fans inside the centrifugal fans type; it is specially designed for ceiling mounting in applications of clean air exhaust in commercial sites and industrial facilities. CR line have 3 kinds of applications: CRH Roof mounting for clean air exhaust, horizontal dischrge CRV Roof mounting specially for kitchen exhaust sistems or specific exhaust instalations. CR model offers an operation providing an air flow volume ranging from 818 m3/hr (481 CFM) to 29,300 3 m /hr (17,235 CFM); with a maximum pressure of 38.1 mm wg (1.5 wg). Its design allows guiding of air inside the fan structure, without any kind of turbulence thanks to the internal aerodynamics of the fan components. Also, manufacturing method of this line, with rejected aluminum allows offering an esthetics finish highly accepted in the market of ventilation and highly resistant to environmental corrosive agents. Construction details for these exhaust fans include high rigidity, because of the manufacturing material and internal support design; without any obstruction of the air flow. CR exhaust fans housing is designed to prevent rain from going into the fan and are provided with a protective mesh to impede foreign objects to go through. Backward straight blade propellers, are totally made with special aluminum alloy, properties of this kind of material are the required ones to offer mechanical stress resistance. Dynamically balanced. All the components utilized for the final assembly of the fan are very carefully selected and tested in order to offer a safe and efficient system. Model CRH-D, CRV-D and CRW-D Direct drive model is available in 4 sizes: 10, 12, 15 y 18. Model CRH-T. CRV-T and CRW-T Pulleys and belt drive option is available in 11 sizes: 10,12,15,18,20,22,24,26,28,30 and 33. CRH range in all sizes has been developed and analyzed in Soler & Palau laboratories. Our advanced manufacturing processes, as well as Quality procedures applied in our facilities, assure the quality of all our products and give you the confidence that the product you have obtained meets the highest international quality standards in every stage of its design and production. Applications for this type of exhaust fans are very extensive, mainly those requested by the projects specification sector, where theyre destinated for multinational companies with strict demands for utilization characteristics. They also can be installed in applications such as: hotels, restaurants, factories, commercial sites, warehouses, etc.

CR

Centrifugal roof exhausters * Vertical discharge: Roff mounted and Wall mounted * Horizontal discharge Extractores Centrfugos de Tejado * Descarga Vertical: Montaje en techo y pared * Descarga Horizontal

Informacin General
La gama CR es una familia de ventiladores con alta eficiencia dentro del tipo de ventiladores centrfugos; cuenta con tres versiones para las distintas aplicaciones que se presentan en sistemas de extraccin: CRH montaje en techo para aplicaciones de extraccin de aire limpio, descarga horizontal; CRV montaje en techo, descarga de aire vertical para instalacin en campanas industriales para extraccin localizada en sistemas; CRW diseo y prestaciones similares al CRV, pero para montaje en pared. El modelo CRH nos ofrece prestaciones en caudal desde 818 m /hr (481 CFM) hasta 29,300 m /hr (17,235 3 3 CFM), el modelo CRV desde 1,559 m /hr (917 CFM) hasta 30,254m /hr (17,789 CFM) y el modelo CRW desde 3 3 1,559 m /hr (917 CFM) hasta 15,273 m /hr (8,981 CFM); todos con una presin mxima de 31.7 mm c.a. (1.25 c.a ). Su diseo les permite guiar al aire dentro de la estructura del ventilador, sin ningn tipo de turbulencia debido a la estructura aerodinmica del ventilador. Adems, el mtodo de fabricacin de esta gama, con material en aluminio rechazado ofrece un acabado esttico de alta aceptacin dentro del mercado de la ventilacin adems de resistencia contra agentes corrosivos del medio ambiente. Dentro de los detalles constructivos, estos extractores cuentan con gran rigidez, debido al material de fabricacin y al diseo de sus soportes internos; favoreciendo al flujo de aire. La cubierta de los extractores CR, est diseada para impedir la entrada de lluvia y cuentan con una malla de proteccin para no permitir el paso de objetos extraos. Las turbinas de labes rectos atrasados balanceadas dinmicamente, estn fabricadas con aleaciones especiales de aluminio, las propiedades de este tipo de material brindon alta resistencia a esfuerzos mecnicos.
3 3

Modelos CRH -D, CRV-D y CRW-D El modelo de transmisin directa est disponible en 4 tamaos: 10, 12, 15 y 18. Modelos CRH-T, CRV-T y CRW-T La opcin con transmisin poleas y bandas, est disponible en 11 tamaos: 10, 12, 15, 18, 20, 22, 24, 26, 28, 30 y 33. La gama CRH, CRV y CRW en todos sus tamaos ha sido desarrollada y analizada en los Laboratorios de Soler y Palau. Nuestros avanzados procesos de fabricacin, as como los procedimientos que se aplican dentro de nuestras instalaciones, aseguran la calidad de todos nuestros equipos y dan la confianza de que el producto que ha adquirido cuenta con los ms altos estndares internacionales de calidad en todas las etapas de su diseo y produccin. Las aplicaciones para este tipo de extractores son muy variadas, principalmente aquellas relacionadas con el sector de la especificacin de proyectos, donde se destinan para multinacionales con estrictas caractersticas para su utilizacin. Tambin se utilizan en aplicaciones tales como: restaurantes (aire limpio), hoteles, fbricas, locales comerciales, bodegas, etc.

CR

Centrifugals exhauster Extractores Centrfugos

CRH

Centrifugal roof exhauster horizontal discharge Extractores Centrfugos de Tejado descarga horizontal

CRH-D (10, 12, 15,18) CRH-T (10, 12, 15, 18, 20, 22, 24, 26, 28, 30, 33)

CRV

Centrifugal roof exhauster vertical discharge Extractores Centrfugos de Tejado descargavertical

CRV-D (10, 12, 15,18) CRV-T (10, 12, 15, 18, 20, 22, 24, 26, 28, 30, 33)

CRV

CRW

Centrifugal exhauster wall mounted Extractores Centrfugos de pared

CRW-D (10, 12, 15,18) CRW-T (10, 12, 15, 18, 20)

CRH
Transmission shaft Eje Transmisin

Centrifugal roof exhausters horizontal discharge Extractores Centrfugos de Tejado descarga horizontal

Product exploded view


Transmission pulley Polea Transmisin

Despiece de Producto
Drive pulley Polea Motriz Motor drive - housing Cubierta motor-transmisin

Housing bearings Chumaceras Motor bearings support base Base Soporte motor chumaceras Antivibration blocks Tacones Antivibratorios

Motor Motor Opening for motor cooling Abertura para enfriamiento motor Lower cover Cubierta inferior

Supporting arm Brazo Soporte

Protective mesh Malla de proteccin

Wheel Turbina

Electrical connections tube Tubo para cableado elctrico Inlet / Venturi Embocadura / Venturi

Housing assembly is designed to provide protection against weather and to protect the motor and its internal components, also having easy opening for inspection and maintenance. Three phase motors used are fabricated under NEMA (MG-1,1998) specifications, also meeting IEEE; Std 112 (R-1996) utilized for efficiency determination. Recognized trademark ball bearings, integrated in cast iron floor mounting bearing blocks, selected for long durability at the highest rated RPM. Supporting base motor bearings is fabricated with high resistance galvanized steel.

Base motor assembly to the fan frame is supported by means of antivibration blocks in order to reduce sound level and possible vibration of drive which could be transferred to the structure of the system. Venturi-propeller assembly is designed to provide great efficiency and sound level reduction. Outlet-base is made of high resistance and large gage aluminum, which provides rigidity to the assembly. With welded corners for higher robustness. In models 26-28-30 and 33 venturi inlet is made with highly rust resistant galvanized metal sheet.

CRH

Centrifugal roof exhausters horizontal discharge Extractores Centrfugos de Tejado descarga horizontal

Product exploded view

Despiece de Producto

Forced ventilation during operation for motor cooling, with cooling blades which carry the air inside transmission housing through perforations made on the supporting plate between propeller and transmission base. Protective mesh to avoid entrance of foreign objects. Connection tube to facilitate electrical installation of the unit. Top cover fabricated with high resistance aluminum.

* La cubierta intemperie esta diseada para proteger al motor y partes internas, con facilidad de apertura para su inspeccin y mantenimiento. * Los motores trifsicos empleados son fabricados bajo especificaciones NEMA (MG-1,1998) adems de cumplir con el estndar de la IEEE; Std 112 (R-1996) empleado para la determinacin de la eficiencia. * Los rodamientos a bolas son de reconocida marca, integrados en chumaceras de fundicin de metal para piso, seleccionadas para larga durabilidad a las ms altas RPM de catlogo. La base soporte motor-chumaceras est fabricada en acero galvanizado de alta resistencia. * El ensamble de base motor a la estructura del ventilador se encuentra soportada por medio de tacones antivibratorios para reducir el nivel sonoro y la posible vibracin de la transmisin que se pudiera trasladar a la estructura del conjunto. * El conjunto venturi-turbina est diseado para proporcionar gran eficiencia y reducir el nivel sonoro.

* La base-embocadura se fabrica con aluminio de alta resistencia y grueso calibre que le permite dar rigidez al conjunto. Con esquinas soldadas para mayor robustez. * En los modelos 26-28-30 y 33 la embocadura se fabrica en lmina de metal galvanizado de alta resistencia a la corrosin. * Ventilacin forzada durante la operacin para enfriar el motor con aletas de enfriamiento que a travs de perforaciones realizadas en el plato soporte entre la turbina y la base transmisin dirigen el aire hacia el interior de la cubierta transmisin. * Malla de proteccin para impedir la entrada de objetos extraos. * Tubo de conexin para facilitar la instalacin elctrica de la unidad. * Cubierta superior resistencia. fabricada en aluminio de alta

Nomenclature

Nomenclatura

CRH - D/T - 10
1 2 3 4 5
Model Modelo: 10, 12, 15, 18, 20, 22, 24, 26, 28, 30 y33 D: Direct Directo T: Transmission Transmisin
C: Centrifugal Centrifugo R: Series letter Siglas de la serie H: Horizontal Discharge
Descarga Horizontal

Direct drive CRH-D

Transmisin directa CRH-D


Air flow volume: From 1998 m /hr (1176 CFM) to 3 7681m /hr ( 4521 CFM); with a maximum pressure of 19.5 mm wg (0.75 wg). Caudal: Desde 1998 m /hr (1176 CFM) hasta 3 7681m /hr ( 4521 CFM); con una presin mxima de 19.5 mm c.a. (0.75 c.a).
Wheel dimensions Model Modelo 10 12 15 18 Dimensin de turbina Height of wheel blades Altura de palas en turbina mm 93 126 140 176 in 3 11/16 4 15/16 5 1/2 6 15/16
3 3

Outer diameter of wheel Dimetro exterior turbina mm 265 340 401 476 in 10 7/16 13 3/8 15 13/16 18 3/4

Pulley-belt drive CRH-T

Transmisin poleas y bandas CRH-T


Air flow volume: From 818 m /hr (481 CFM) to 29,300 3 m /hr (17,235 CFM); with a maximum pressure of 31.7 mm wg (1.25 wg ). Caudal: Desde 818 m /hr (481 CFM) hasta 29,300 m /hr (17,235 CFM); con una presin mxima de 31.7 mm c.a. (1.25 c.a ).
3 3 3

Wheel dimensions Model Modelo 10 12 15 18 20 22 24 26 28 30 33

Dimensin de turbina Height of wheel blades Altura de palas en turbina mm 93 126 140 176 180 192 212 225 239 255 282 in 3 11/16 4 15/16 5 1/2 6 15/16 7 1/16 7 9/16 8 3/8 8 7/8 9 7/16 10 1/16 11 1/8

Outer diameter of wheel Dimetro exterior turbina mm 265 340 401 476 484 580 635 690 720 775 855 in 10 7/16 13 3/8 15 13/16 18 3/4 19 1/16 22 13/16 25 27 3/16 28 3/8 30 1/2 33 11/16

Direct drive CRH-D-10

Transmisin directa

Static pressure mmwg - inwg HP R.P.M.


0.00 m3/hr dB(A) 1998 CFM BHP 1176 0.065 1690 0.24 3.17 mm / .125" m3/Hr. dB(A) 1758 57.43 2718 65.59 CFM BHP 1035 0.078 1600 0.25 6.35 mm / .250" m3/Hr. dB(A) 1471 57.21 2569 65.34 CFM BHP 866 0.079 1512 0.26 m3/Hr. dB(A) 1118 56.77 2387 64.96

(PRESIN ESTTICA) mmcda - inwg.


12.70 mm / 0.50" m3/Hr. dB(A) CFM BHP 15.87 mm / .625" m3/Hr. dB(A) CFM BHP 19.05 mm / .750" m3/Hr. dB(A) CFM BHP CFM BHP 658 0.078 1405 0.27 2207 64.83 1299 0.28 2030 65.09 1195 0.28 1821
65.83

9.52 mm / .375"

1/8 MF 115 V 1/3 MF 115 V

1200
57.85 2871

1072
0.28

1725
65.71

CRH-D-12
Static pressure mmwg - inwg
HP R.P.M. 0.00 m3/hr dB(A) 1/4 MF 115 V 2500 1200 59.43 0.128 59.24 0.147 59.05 0.148 59.62 0.164 59.80 0.167 59.98 0.171 CFM BHP 1442 3.17 mm / .125" m3/hr dB(A) 2161 CFM BHP 1272 6.35 mm / .250" m3/hr dB(A) 1840 CFM BHP 1083

(PRESIN ESTTICA) mmcda - inwg.


11.11 mm / .437" m3/hr dB(A) 1150 CFM BHP 676 12.7mm / 0.50" m3/hr dB(A) 673 CFM BHP 396 15.87 mm / .625" m3/Hr. dB(A) CFM BHP CFM BHP 866

9.52 mm / .375" m3/hr dB(A) 1471

CRH-D-15
Static pressure mmwg - inwg
HP R.P.M. 0.00 m3/hr dB(A) 1/4 MF 115 V 3/4 MF 115 V 3352 850 59.62 4732 1200 65.71 0.54 65.59 0.56 65.34 0.57 65.09 0.58 65.59 0.58 66.07 0.58 66.65 0.57 0.17 2785 59.62 4400 0.19 2590 59.05 4062 0.19 2391 59.24 3700 0.19 2178 3281 1931 2815 1657 2246 1322 CFM BHP 1973 3.17 mm / .125" m3/hr dB(A) 2936 CFM BHP 1728 6.35 mm / .250" m3/hr dB(A) 2467 CFM BHP 1452 m3/hr dB(A) 1901

(PRESIN ESTTICA) mmcda - inwg.


12.70 mm / 0.50" m3/hr dB(A) CFM BHP 15.87 mm / .625" m3/hr dB(A) CFM BHP 19.05 mm / .750" m3/hr dB(A) CFM BHP CFM BHP 1119

9.52 mm / .375"

CRH-D-18
Static pressure mmwg - inwg
HP R.P.M. 0.00 m3/hr dB(A) 0.5 MF 115 V 1 TF 208/230 460 V 5440 850 65.95 7681 1200 72.53 1.05 72.30 1.08 72.38 1.11 72.61 1.11 72.68 1.17 72.83 1.20 73.34 1.22 0.34 4521 66.30 7372 0.36 4339 66.65 7034 0.38 4140 66.42 6672 0.40 3927 66.07 6274 0.41 3693 66.18 5793 0.41 3410 5313 3127 CFM BHP 3202 3.17 mm / .125" m3/hr dB(A) 5041 CFM BHP 2967 6.35 mm / .250" m3/hr dB(A) 4589 CFM BHP 2701 m3/hr dB(A) 4013

(PRESIN ESTTICA) mmcda - inwg.


12.70 mm / 0.50" m3/hr dB(A) 3323 CFM BHP 1956 15.87 mm / .625" m3/hr dB(A) 2416 CFM BHP 1422 19.05 mm / .750" m3/hr dB(A) CFM BHP CFM BHP 2362

9.52 mm / .375"

* Performance at standard conditions *Datos obtenidos a condiciones estndar

Performance curves Curvas caractersticas


CRH-D-10 CRH-D-12
inwg mmcda
inwg

CRH-D-15 CRH-D-18
mmcda

0.98 25

1.18

30
CRH-D-18 1200 rpm

0.98

25

0.78 20

CRH-D-10 1725 rpm CRH-D-15 1200 rpm

0.78

20

0.59 15
CRH-D-12 1200 rpm CRH-D-18 850 rpm

0.59

15

0.39 10

CRH-D-10 1200 rpm

CRH-D-15 850 rpm

0.39

10

0.19 5
0.19 5

0 0 0 0 500 294 1000 588 1500 882 2000 1176 2500 1471 3000 1765
3 3500 m/h r

0 0 0

1000 588

2000 1176

3000 1765

4000

5000

6000 3529

7000 4118

8000 4706

3 9000 m/h r

2059 cfm

2353 2941

5294 cfm

Dimensions Dimensiones
A

* Performance at standard conditions *Datos obtenidos a condiciones estndar

C ext.

Model Modelo mm CRH-D-10 CRH-D-12 CRH-D-15 CRH-D-18 681 772 772 926

Dimensions A in 26 13/16 30 3/8 30 3/8 36 7/16 mm 77 87 111 128 B in 3 1/16 3 7/16 4 3/8 5 1/16 mm 530 610 610 710

Dimensiones C in 20 7/8 24 24 27 15/16 mm 40 50 50 50 D in 1 9/16 1 15/16 1 15/16 1 15/16 mm 543 676 699 821 E in 21 3/8 26 5/8 27 1/2 32 5/16

Accessories

Accesorios

Ceiling mounting fixture Accesorio de Montaje para Techo


This fixture is made with galvanized steel sheet. Makes mounting and installation of exhaust fan easier. With specific dimensions for each model and special design for standard flat surfaces; for designs out of standard contact our plant for proper selection of fixture type and model. Este accesorio esta fabricado en lmina galvanizada. Facilita el montaje e instalacin de los extractores centrfugos de tejado. Cuenta con dimensiones especficas en cada modelo y su diseo es especial para superficies lisas; para pedidos fuera del estndar comunicarse a planta para la seleccin del tipo y modelo de accesorio.

Dimensions

Dimensiones
A B
Model Modelo mm CRH-D-10 CRH-D-12 CRH-D-15 CRH-D-18 568 618 618 718 718 934 934 1036 1036 1170 1170 A

Dimensions B in 22 3/8 24 5/16 24 5/16 28 1/4 28 1/4 36 3/4 36 3/4 40 13/16 40 13/16 46 1/16 46 1/16 mm 530 580 580 680 680 884 884 986 986 1120 1120

Dimensiones C in 20 7/8 22 13/16 22 13/16 26 3/4 26 3/4 34 13/16 34 13/16 38 13/16 38 13/16 44 1/8 44 1/8 mm 152 152 152 229 229 229 229 229 229 305 305 in 6 6 6 9 9 9 9 9 9 12 12

1 1/2

CRH-D-20 CRH-D-22 CRH-D-24 CRH-D-26 CRH-D-28 CRH-D-30 CRH-D-33

Accessories
Dampers Compuertas

Accesorios

Accesorie designed to flow control systems, at the inlet of the exhauster. Dampers options: Air pressure dampers With motorized back draft dampers Constructed with aluminum or galvanized steel, with special design in the blades utilized in the air control systems. Accesorio diseado para controlar el paso del aire a travs de la succin del extractor. Opciones de Dampers: Accionados por sobrepresin O con dispositivo motorizado. Fabricados en aluminio o lmina galvanizada con mecanismos de diseo especial para sistemas de manejo de aire. Apertura paralela o encontrada en hojas. The motor control dampers available in airfoil blades or steel blade. Designed with maximun air velocity: 7m/seg. The apropiate seleccion of the air control damper depends the application (clean air, dusty air, grease air, t emperatures, etc.) Las compuertas con accionamiento controlado, pueden ser suministrados con hojas planas o del tipo airfoil. La seleccin del tipo de compuerta corresponder a la aplicacin que se pretenda manejar (aire limpio, aire con polvo o grasa, temperaturas, etc.)

Aleta Plana

Aleta Airflow

Dimensions Dimensiones Model Modelos


Electrical connections tube Cable conexion electrica

Flat blade Aleta plana A mm (Inches) 355 500 500 645 645x710 790 790x915 935 935 1080 1080x1150 14 19 11/16 19 11/16 25 3/8 25 3/8 x 27 15/16 31 1/8 31 1/8 x 36 36 13/16 36 13/16 42 1/2 42 1/2 x 45 1/4 345 510 510 680 680 840 840 840 1005 1005 1170

Airfoil blade Aleta hueca A mm (Inches) 13 9/16 20 1/16 20 1/16 26 3/4 26 3/4 33 1/16 33 1/16 33 1/16 39 9/16 39 9/16 46 1/16

10 12 15 18 20

152 mm(6 in) 229 mm(9 in) 305 mm(12 in)

22 24 26 28
A outlet Apertura-salida de aire

30 33

Installation recommendations

Recomendaciones de instalacin

Below youll find a suggestion for physical installation of exhaust fans, considering equipment operation is exclusively for clean air, because of discharge orientation, since there could be pollution return, furthermore the fan doesn't have the option for collection and/or drain of solved substances in the air to be exhausted. Electrical connection of the motor is made through connection tube. A continuacin encontrar una sugerencia para la instalacin fsica de estos extractores, tomando en cuenta que la operacin de este equipo es exclusivamente para aire limpio, debido a la orientacin de su descarga, ya que puede haber retorno de contaminacin, adems de que el ventilador no cuenta con la opcin de recoleccin y /o dren de substancias disueltas en el aire a extraer. En el tubo de conexin es donde se realiza la salida al exterior, para la conexin elctrica del motor.

Wire for electrical connection Cable de conexin elctrica

152 mm. (6 in) 229 mm. (9 in) 305 mm. (12 in)

Opening air inlet Apertura entrada de aire

Fan outlet should be placed over the ceiling mounting fixture, for horizontal surfaces. If any other kind of mounting fixture is needed, contact our plant to verify manufacturing probabilities. The hole made in the surface should have some tolerance related to the mounting fixture flange size; as shown in the sketch. Ceiling mounting fixture should be fixed directly to the surface. In case there is an outlet or duct termination, this should overlap the fixing flange of the ceiling mounting. La embocadura del ventilador deber colocarse sobre el accesorio de montaje para techo, en superficies horizontales. En caso de ser necesario algn otro tipo de accesorio para montaje consultar a S&P para verificar las posibilidades de fabricacin. El orificio que se haga en la superficie deber tener cierta tolerancia con respecto a la medida de la brida del accesorio de montaje; segn se muestra en el esquema. El accesorio de montaje para techo, deber fijarse directamente a la superficie y en caso de existir alguna salida o terminacin de ducto, sta se deber empalmar con la brida de fijacin.

Installation recommendations

Recomendaciones de instalacin

Joints between exhaust fan and conduction line should be perfectly sealed to avoid benefits loss (less exhaust air flow). La unin entre el extractor y la conduccin, debe estar perfectamente sellada para evitar prdidas de prestaciones (menor caudal de extraccin). Quitar toda obstruccin en la salida del aire. Quitar toda obstruccin en la salida del aire.

Exhaust fan mounting to ceiling should be performed with a special mounting base, in order to maintain the inlet venturi fixed in the installation. Joints between exhaust fan and conduction line should be. Canalizar descarga de condensados.
Wall Muro

La fijacin del extractor al techo, deber hacerse con una base especial para montaje con el fin de que la embocadura quede fija en la instalacin.

Ceiling Losa

Position of this fan, according to its structure, is special for vertical mounting. Exhaust fan weight will apply compression force on the outlet. Fan must not be installed under stress forces. La posicin de este ventilador, de acuerdo a su estructura, es especial para fijacin vertical. El peso del extractor ejercer compresin sobre la embocadura. No debe instalarse bajo tensin. Verificar la correcta rotacin de la turbina. Verificar la correcta rotacin de la turbina.

Fan Troubleshooting Guide Gua para resolver situaciones diferentes al funcionamiento esperado
Undesirable effect Efecto indeseable

Possible cause

Posibles causas
-Instalacin incorrecta con transmisin de vibracin de otros componentes. - Fijacin a base incorrecta. - Turbina daada o desbalanceada. - Incorrecta colocacin de las poleas. - Bandas daadas o mal aplicadas. - Alta velocidad fuera de rango permitido. - Incorrecta direccin de rotacin de la turbina. - Rodamientos en mal estado o sin lubricacin. - Giro incorrecto de la turbina. - Conexin elctrica mal realizada. - Variaciones grandes en el suministro de energa. - Alineacin incorrecta de la turbina. - Deficiencias en la alimentacin de aire al ventilador. - Obstrucciones en la salida o entrada del aire. - Datos reales requeridos diferentes a los datos seleccionados en el ventilador. - Problemas en el voltaje. - Incorrecto giro en la turbina. - Diferentes RPM a las seleccionadas. - Problemas en el ensamble de la transmisin (poleas y bandas). - Problemas en la entrada del aire para la ventilacin del motor. -Condiciones anormales de funcionamiento del motor. - Tensin excesiva en la bandas. - Daos en los rodamientos. - Desalineacin en la flecha de transmisin.

1) Excessive vibration and noise. - Improper belt drive and Exceso de ruido y vibracin. isolation with other components. - Damaged or unbalanced wheel. - Belts too loose; worn or oily belts. - Speed too high. - Incorrect direction of rotation. - Make sure the fan rotates in same direction as the arrows on the motor or belt drive assembly. -Bearings need lubrication or replacement.

2) Low capacity or pressure. Capacidad de operacin del ventilador por debajo de la esperada.

- Incorrect direction of rotation. - Make sure the fan rotates in same direction as the arrows on the motor or belt drive assembly. - Motor improperly wired. - Incorrect voltage. - Improper wheel alignment. - Diferent air volume required to the performance rating selected.

3) Overheated motor. Calentamiento de motor.

- Incorrect voltage. - Incorrect direction of rotation. - Make sure the fan rotates in same direction as the arrows on the motor or belt drive assembly. - Incorrect fan RPM. - Cooling air diverted or blocked. - Improper inlet clearance. - Excessive belt tension. - Improper bearing lubrication. - Improper shaft alignment.

4) Overheated Bearings. Calentamiento de transmisin.

All S&P products details are documented in printed and electronic catalogs, available for all of our distributors to properly select equipment for best application from our product line. Additionally, a group of well prepared technicians will support you with service either by phone or by e-mail at the following address: comercial@soler-palau.com.mx Todos los productos S&P estn detallados con toda su informacin en los catlogos escritos y electrnicos, disponibles para todos nuestros distribuidores para seleccionar adecuadamente los equipos con la mejor aplicacin dentro de nuestra lnea de productos. Adems un grupo de preparados Tcnicos le apoyan en Servicio telefnico y en lnea comercial@soler-palau.com.mx