Você está na página 1de 8

A.a.

1 Universal On/Off Controller with Communication facility Size : 96 x 96 mm Input : Universal (T/C, RTD, 0 10 V, 0 20 mA) Range : 0 to 1000 C Control output : C, NO, NC (Potential-free Contacts 5 A, 230 V AC with fuse protection) Set points : Dual set point Scanning rate : < 200 ms Accuracy : +/- 0.25 % of FS Front Bezel Protection : IP 66 Stray Rejection : CMRR > 120 dB Communication : RS 485 Modbus (ASCII & RTU) Control output : 2 No.s Relay contact Display : 4 Digit LED / LCD Modes of Operation : Auto / Manual Power : 230 V AC Make : Yokogawa / Eurotherm / Honeywell Special features : Display and record of Error status, Remote set point control, PV transmission, output status Note: 1. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere 2. Detailed Specifications along with Traceable test certificates shall be enclo sed in the offer A.a.2 PID Controller with Communication facility I N P U T 1. Signal Type : Universal 2. Measuring accuracy : +/- 0.25% of FS, +/- 1 digit 3. Sampling period : 200 ms 4. Temp. measuring unit : deg.C 5. Input break action : a) Thermocople : Upscale b) DC Voltage : Down scale c) RTD : Up scale 6. Noise rejection : a) CMRR : 120 dB b) SMRR : 40 dB 7. Measured input bias : -100.0 to 100.0% of measuring span 8. Temp. comp. Error : < +/- 1 deg. C O U T P U T 1. Output type : a) Time proportional PID b) Time proportional voltage pulse type PID c) Continuous PID(4-20 mA DC) d) ON/OFF (Relay output) 2. Relay output rating : 250 V AC, 3 A 3. Retransmission output : 4- 20 mA DC 4. Remote Operation : a) Communication interface : RS485 b) Local / Remote mode switching reqd. 5. Other features required : a) Auto tuning b) Fuzzy based over shoot suppression c) Output limiting 0 to 100 % d) Anti wind up feature required Make : Yokogawa / Eurotherm / Honeywell A.a.3 Thermocouples with thermo well Type : K -type, Mineral insulated, Inconel sheathed along with thermo well Accuracy : Class B +/- 0.8 C at 500 C Calibration : As per DIN 43760 Temperature : 1000 C max.

Insulation : Mineral insulated (MgO) Thermo well material : SS 316 L Max. Operating Pressure : 4 bar Termination & head : Screw type on ceramic terminal block in Die-cast Aluminium connection head coated with anti corrosive paint suitable for Chlorine atmosphere . Make : Omega/ Nagman instruments/Tempsen S.No. Thermocouple Length Thermowell Length Gauge Quantity 1 30 cm 30 cm 22 SWG 9 2 1 m 1 m 18 SWG 3 A.a.4 RTD along with Thermowell Type : Mineral insulated Pt - 100 RTD, SS sheathed With thermo well Lead configuration : 3 Wire system Configuration : Duplex Accuracy : Class B +/- 0.8 deg. C at 100 deg. C Calibration : As per DIN 43760 Temperature : 100 deg. C max Length : 300 mm Insulation : Mineral insulated (MgO) Process Connection material : SS 316L Max.operating Pressure : 5 bar Termination : Screw type on Ceramic terminal block in dieCast Aluminium head coated with anti Corrosive paint Make : Omega/ Nagman instruments/Tempsen A.b.1 Pressure transmitter Type : 2 wire, SMART transmitter Measuring Principle : Piezo resistive/ Capacitance type Span : 10 bar (Minimum 1:10 Rangeability) Service : Chlorine Gas (Dry) Process temperature : 60 C Max. Process connection : " NPT Power supply : 24 V DC Output : 4 - 20 mA with HART Performance Accuracy : 0.25 % of calibrated span or better Material of construction a. Sensing diaphragm : SS 316L b. All other parts : SS 316L including nuts, bolts & mounting brackets Indicator : LCD Digital Display with backlight Electrical connection : NPT Housing : Die cast Aluminium with polyurathene Anti corrosive paint suitable for Chlorine Atmosphere Ingress protection class : IP 65 Make : E+H/ Rosemount/ ABB/Yokogawa Note: 1. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere A.c.1 Thermal Mass Flow Controller Line size : 1 Output signal : 0 5 V DC or 4 20 mA with HART

Communication : RS 485 Modbus / ASCII / RTU Meter size : As required Service : Chlorine gas (dry) Maximum flow : 200 kg/hr Rangeability : 1:20 minimum Accuracy : +/- 1 % FS Repeatability : +/- 0.2 % FS Resolution : 0.1 % FS Control range : 2 to 100 % FS Controller Settling time : < 2 second (to within 2 % of set point) Operating pressure : 2 to 3 bar Maximum Pressure : 10 bar Process temperature : Max. 60 C Temperature coefficient : < 0.1 % FS / C Material of Construction : SS 316L (Wetted), Teflon (Seals) - Suitable Humidity : 0 to 95 % RH, non-condensing Output Impedance : < 1 ohm Ingress protection : IP 67 Process connection : Flanged, ANSI B 16.5 RF 150 Make : MKS/Sierra Instruments/Brooks Note: 1. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere A.c.2 Rotameter for Chlorine Gas Service : Chlorine Gas (dry) Flow range with units : 200 kg/hr (Nominal) Temperature (Op.) : 50 C Operating Pressure : 2 to 3 bar Maximum Pressure : 10 bar Accuracy desired : +/- 2 % on F.S.R End connections : Flanged Inlet Connection Orientation : Down Outlet Connection Orientation : Up Mounting : Pipe Line size : 1.25 Body : SS 316 L Flange & End fitting material : SS 316 L Flange : ANSI B 16.5 RF 150 Float material : SS 316 L Tube Material : Toughened Borosilicate Glass Packing/"O" Ring material : Teflon Note: It shall be complete with suitable needle valves and PRVs, made of SS 316L metallic parts Make : TRAC/ Eureka/ Forbes Marshall A.c.3 Rotameter Switch for Nitrogen Gas Service : Nitrogen Flow range with units : Max. flow 100 lpm Temperature (Op.) : 50 C Operating Pressure : 2 to 3 bar Maximum Pressure : 10 bar Accuracy desired : +/- 1% on F.S.R Output : Switch contacts 230 V AC, 3 A Switching differential : 5 lpm End connections : Flanged Inlet Connection Orientation : Down Outlet Connection Orientation : Up Mounting : Pipe Line size : 1.25

Body : SS 316 L Flange & End fitting material : SS 316 L Flange : ANSI B 16.5 RF 150 Float material : SS 316 L Tube Material : Toughened Borosilicate Glass Packing/"O" Ring material : Teflon Note: It shall be complete with suitable needle valves and PRVs, made of SS 316L metallic parts Make : TRAC/ Eureka/ Forbes Marshall A.c.4 & A.c.5 Insertion type water Flow Switch Type : Insertion type, paddle operated, actuator with Magnetic Reed relay Service : Water Flow Rate : 100 lpm (Operational )& 200 LPM Max for WSR - Adjustable : 15 lpm (Operational) & 30 LPM Max for OC - Adjustable Line Size : 1 Material of wetted parts : SS 316L MOC of other Metallic Parts : SS 316L Operating pressure : 8 kg/cm2 Accuracy : +/- 2 % FS Differential : 10 % Temperature : 50 C max. Switch type : DPDT, 24 V DC, 5 A Enclosure : Die cast Aluminium with polyurathene Anti corrosive paint suitable for Chlorine Atmosphere Protection : IP 65 Make : TRAC/ Danfos/ Switzer A.d.1 Nucleonic bed level measuring instrument For OCF Type : Two-wire SMART transmitter Range of the instrument : 1000 mm (Max) Output : 4 20 mA With HART Accuracy desired : +/- 0.25% of calibrated span Medium of the bed : Solid (Porous), 1.0 gm/cc Reactor details a. Height : 2650 mm b. Outer Diameter : 2050 mm c. Effective Inner diameter : 1250 mm d. Top Cover temperature : 400 C (Max.) e. Temp. inside the reactor : 1100 C (Max.) Power supply : 24 V DC Ambient Process condition : 100 C, Chlorine atmosphere Thickness of layers in the Cylindrical Reactor Vessel: a) MS Shell : 10 mm thick, 7.85 gm/cc b) Glass wool : 75 mm thick, 0.128gm/cc c) SS 316 Shell : 10 mm thick, 8 gm/cc d) Silica Brick Insulation : 390 mm thick, 2.5 gm/cc Screening material : Lead Ingress protection class : IP 65 Housing : Die cast Aluminium with polyurathene Anti corrosive painting to withstand Chlorine atmosphere Make : E+H / Rosemount Note: 1. The supplier shall provide all relevant certificates regarding the radiometri c source, source container, detector and transmitter, the local dose rate and the leak tes t.

2. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere Cross section of the OCF reactor vessel indicating various layers of obstructions: A C MS Shell Glass Wool Silica Brick Lining SS 316 Shell Bed Material A.d.1 Nucleonic bed level measuring instrument For WSR Type : Two-wire SMART transmitter Range of the instrument : 1000 mm (Max) Output : 4 20 mA With HART Accuracy desired : +/- 0.25% of calibrated span Medium of the bed : Turnings, blocks, chunks of 0.5 to 2.5 g/cc density Reactor details a) Height : 2500 mm b) Outer Diameter : 687 mm c) Effective Inner diameter : 530 mm d) Temp. inside the reactor : 1100 C (Max.) Power supply : 24 V DC Ambient Process condition : 100 C, Chlorine atmosphere Thickness of layers in the Cylindrical Reactor Vessel: a) SS 316 : 6 mm thick, 8 gm/cc b) Water jacket : 28.5 mm thick, 1 gm/cc c) Inconel : 6mm of thick , 8.3gm/cc Screening material : Lead Ingress protection class : IP 65 Housing : Die cast Aluminium with polyurathene Anti corrosive painting to withstand Chlorine atmosphere Make : E+H / Rosemount Note: 1. The supplier shall provide all relevant certificates regarding the radiometri c source, source container, detector and transmitter, the local dose rate and the leak test. 2. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere Cross section of the WSR indicating various layers of obstructions: Inconel Shell Water Jacket SS 316 Shell Bed Material A.d.2 Nucleonic level switch Type : Continuous Level measurement Range of the instrument : 300 mm (Max) Accuracy desired : +/- 1 % of calibrated span Medium of the bed : Solid Powder, cake. 1gm/cc density Reactor details a. Height : 2415 mm b. Diameter : 2500 mm c. Effective Inner diameter : 2340 mm d. Top Cover temperature : 400 C (Max.) e. Temp. inside the vessel : 500 C (Max.) Power supply : 24 V DC

Ambient Process condition : 70 C, Chlorine atmosphere Thickness of layers in the Cylindrical Condenser: a) SS 316 : 6 mm thick, 7.85 gm/cc b) Air jacket : 75 mm thick c) Inconel : 6mm of thick , 8.3gm/cc d) Chloride : 1gm/cc Screening material : Lead Response time : 2 s Ingress protection class : IP 67 Housing : Die cast Aluminium with polyurathene Anti corrosive painting to withstand Chlorine atmosphere Make : E+H / Rosemount Note: The supplier shall provide all relevant certificates regarding the radiome tric source, radiometric source container, detector and transmitter, the local dose r ate and the leak test. Conformal coating required for all the electronic boards of t he instruments in order to withstand chlorine atmosphere. Cross section of the condenser indicating various layers of obstructions: Inconel Shell SS 316 Shell Chloride Air Jacket A.d.3 Side mounted Float type Level Switch Type : Float type Mounting : Side mounted Application : Conductive slurry/acidic liquid Process temperature : 80- deg. C (max) Response time : 0.5 sec or better Switching : Continuously adjustable Output : Potentially free contacts (rated 3A, 230 V) Ambient temperature : 60 deg. C (max) Make : Switzer/ Danfoss/DK instruments A.e.1 Chlorine Leak Monitoring System Sensor Type : Electrochemical type Measuring gas : Chlorine Measuring range : 0 to 20 ppm (Max.) for measuring at zones : 0 to 200 ppm(max) for measuring at Stack Ambient Conditions : 15 C to 50 C, Atmospheric pressure, 10 % to 95 % RH Lower detection limit : 0.01 ppm for 0 to 20 ppm range : 0.1ppm for 0 to 200 ppm range Linearity tolerance : +/- 5 % of measured value Accuracy : < +/- 0.1 ppm or better. Effect of temperature : < 0.001 ppm/K No. of sensors : 7 No. of Transmitters for sensors : 7 (With display) Communication facility : RS 485, Modbus RTU Ethernet (Optional) Alarms : To identify the intensity of the leak and the location of the leak w.r.t. each zone Wall mounting cabinet : Required along with Power supply, Control Card with Alarm output etc., installed in single Rack Make : Drager/ Honeywell/ equivalent Note: 1. The intensity of the chlorine and the alarm conditions w.r.t. each zone are required to be continuously transmitted to the PLC and recorded. 2. Conformal coating required for all the electronic boards of the instruments and the sensors in order to withstand chlorine atmosphere A.f.1 Shut-off Valve

Type : Diaphragm operated Pneumatic Valve Size : 25 mm Body : SS 316L with Teflon backed EPDM 2-way Medium : Chlorine Gas (dry) Op. Temperature : 50 C Op. Pressure : 2 to 3 bar Maximum pressure : 10 bar End connections : Flange, ANSI B16.5 RF 150, SS 316 L Features required : Single acting Actuator, Normally close, Electro Pneumatic Valve Positioner, Valve travel indicator with Limit Switch and LED, Stoke Limiting Mechanism, Manual override facility Actuator : 30 % Glass Filled Polyamide with Hand wheel a. Pilot Pressure : 4.5 to 8.5 bar Air or Non-Corrosive gas b. Solenoid Valve : 3/2 Built in Namur Solenoid valve that works on 230 V A.C Protection : IP 67 Leakage Class : VI Coating : Entire Assembly to be coated and to be protected from Chlorine Atmosphere Make : BDK / AVCON / ROTEX Note: 1. All the metallic parts of the valve and actuator including nuts, bolts and ot her accessories shall be of SS 316 L 2. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere A.g.1 Thyristorised Heater Controller Current : 600 A Rated Voltage : 415 V AC, 3 Supply Frequency : 50 Hz Operating Temperature : Ambient Power Dissipation : 2 W per amp per phase Humidity : 5 to 95 % RH, non-condensing Electrical Protection : RC Snubber network High-speed fuse protection for thyristor Load type : Transformer Load configuration : 3 wire delta Control type : Three phases of the three phase system Control mode : True power control (V x I) Firing mode : Phase angle control Current limit feature : Required Retransmission output : 0-10 V for load current, load voltage Analog input : 0 10 V, 4 20 mA Communication : RS 485, Modbus RTU Make : Eurotherm or equivalent A.g.2 Power meter Measurement type : True RMS on three phase AC system (128 samples per cycle) Measurement Accuracy 0.075 % of reading + 0.025 % of FS a. Current & Voltage : b. Power : 0.5 % of reading + 0.025 % of FS c. Frequency : 0.01 Hz Data Update rate : 1 s Input Current Characteistics i. CT ratings a. Primary : 5 to 100 kA b. Secondary : 1 to 5 A

ii. Measurement input range : 0 to 10 A iii. Impedance : < 0.1 iv. Load : 0.15 VA IP degree of protection : IP 52 Dimensions : 96 x 96 mm Humidity : 5 to 95 % RH, non-condensing Communication interface : Two-wire RS 485, MODBUS Trend curves : Four, 1 minute, 1 hour, 1 day, 1 month Make : GE / Areva / Schneider / Siemens Note: 1. Conformal coating required for all the electronic boards of the instruments i n order to withstand chlorine atmosphere 2. Detailed Specifications along with Traceable test certificates shall be enclo sed in the offer A.h.1 pH Transmitter Type : 2-wire microprocessor operated Measuring range : 0 14 pH Supply : 16 V DC to 32 V DC Load : 725 ohms max. at 30 V Output : 4 20 mA, load 725 ohm max., Galvanic isolated Accuracy : +/- 0.2% FSD Linearity : 0.1% Local indication : LCD Zero adjustment : +/- 0.2 pH Calibration : 2-point calibration Temperature compensation : Automatic Protection : IP 65 Enclosure : Epoxy coated Aluminium Programming should be available with touch keyboard Make : Endress + Hauser, Yokogawa, Rosemount A.h.2 Combined pH Electrode Type: Combination, without pre-amplifier Construction: Glass, Reference, Thermo-compensator & Solution in a single moulded body. Body material: RYTON PPS Solution Ground: Graphite Wetted Part pH Range: 0 14 Temperature: 10-80 Deg C Pressure: 0 to 0.3 bar Measuring Glass: Semi Dome toughened Reference: Double Junction, Polymerised & Gel filled Ref. Junction: Large, Annular Ceramic fouling resist Thermo-compensator: Pt 100, 2/3 wire Mounting: 3/4 inch NPT Insertion Length: 45mm beyond mounting threads Cable: Single cable with PH, RTD and Solution ground, 15 mtr length Make: Endress + Hauser, Yokogawa,