Digitrip 1150i - IEC Curves IEC-B (Very Inverse)

.7 .8 .9 1

7 8 9 10

50

30

60

.6

20

2 Hours

10000 9000 8000 7000 6000 5000

40

70

.5

Circuit Breaker Time/Current Curves (Phase Current)


Magnum Circuit Breakers Response: Very Inverse & Short Delay Trip This curve is for 50Hz or 60Hz applications.

1 Hour

4000 3000

Available Sensors and Matching Rating Plug


2000

In Amperes 200A 250A 300A 400A

600A 630A 800A 1000A 1200A

1250A 1600A 2000A 2500A 3000A

3200A 4000A 5000A 6000A 6300A

1000 900 800 700 600 500 400 300

Notes: 1. This curve is shown as a multiple of the PICKUP setting (Ir). The TimeDial setting combined with SHORT PU and SHORT TIME setting (shown in heavy lines) depict the IEC-B response. The Instantaneous, shown as a separate response, can be set to OFF. 2. Curve Equation: Trip = TimeDial *[ 13.5 / (I -1)], where I is a multiple of Ir. For current > 1.2xIr tolerance is [15%] or [-15%, +90 ms], whichever is larger. TimeDial curve goes to flat response at 14xIr with a shorter time of TimeDial function or SHORT TIME function prevailing if curves overlap. The ShortTime function and the TimeDial function act independently and the entire TimeDial curves continue to be active even after the curves intersect. Adjustable PICKUP 0.4 to 1.0x In = Ir with 0.05 increments See Note 4 3. With zone interlocking on Short Delay utilized and no restraining signal, the minimum SHORT TIME band [0.10s] applies regardless of the SHORT TIME setting. 4. The actual pick up point (indicated by rapid flashing of Unit Status LED on the product) occurs at 110% of the Ir, current, with a 5% tolerance. The SHORT PU settings have conventional 100% 5% as their pick up point. 5. SHORT PU also has a M1 setting, which may extend out where the SHORT PU will become active. Adjustable Range M1 setting M1=14x In M1=12x In M1=12x In M1=14x In M1=12x In M1=10x In M1=14x In M1=12x In M1=10x In Narrow Frame: 200A through 1250A 1600A 2000A (IEC only) Standard Frame: 100A through 1250A 1600A, 2000A, 2500A 3000A, 3200A Double Wide Frame: 2000A, 2500A 3000A, 3200A, 4000A, 5000A 6000A, 6300A (IEC only)

200

1 Minute

100 90 80 70 60 50 40 30

20

1.5 to 14x Ir 1.5 to 12x Ir 1.5 to 10x Ir 1.5 to 14x Ir 1.5 to 12x Ir 1.5 to 10x Ir 1.5 to 14x Ir 1.5 to 12x Ir 1.5 to 10x Ir

10 9 8 7 6 5 4 3

See Note 5

Adjustable TimeDial Setting 0.10 to 1.00 With 0.05 increments See Note 2

6. The end of the curve is determined by the interrupting rating of the circuit breaker. 7. SHORT TIME: FLAT only Tolerance is +0/ -80 ms of setting except 0.10s setting is 0.06 to 0.13 0.15s setting is 0.10 to 0.17 0.20s setting is 0.15 to 0.22 8. Curve applies from -20C to +55C ambient. Temperatures above +85C cause automatic trip. Breaker must be applied according to Continuous Rating at Different Ambient table.

TIME IN SECONDS

1 .9 .8 .7 .6 .5 .4

1.00 0.90 0.80 0.70 0.60 0.50 0.40 0.30

Adjustable SHORT TIME 0.10s to 0.50s With 0.05 increments See Note 7

0.50 s

.3
0.20

.2
0.15

.1 .09 .08 .07 .06 .05 .04 .03

0.10

Adjustable SHORT PU 1.5x to 10x or 12x or 14x Ir With 0.5 increments See Notes 4, 5

Minimum clearing time See Notes 3, 7

.02

.01

.7 .8 .9 1

7 8 9 10

30

50

Current in Multiples of Pickup ( Ir ) Dwg. No.: 70C1032 June 2006 Printed in the U.S.A.

70 80 90 100

20

40

60

.6

.5