YASKAWA INVERTERS
Global Reliability
VT/CT Selection
2
VT C6-01=1
CT C6-01=0
3 8 10 12 14 18 21 29 57 61 64 67 90 94 97
Inverter Constants
Torque
Load Characteristics
Speed Speed
Torque
Variable torque
Constant torque
180%
Dimensions Software Functions Constants List Constant Descriptions Application Examples Protective Functions Typical Connection Diagram
150%
Carrier High carrier frequency Low carrier frequency (2 kHz) (With a low-carrier-frequency Frequency (15 kHz max.) low-noise control) Stall Prevention Level
120%
150%
1 : Only VT is available for 200V-class 110 kW and 400V-class 220/300 kW inverters. 2 : The factory setting of Varispeed F7 SPEC E or later is CT (constant torque).
If noise from the motor causes a problem after having replaced the Varispeed F7 with that of SPEC E or later, set C6-01 to 1.
High-speed response
Open-loop vector control: Speed response 5Hz Flux vector control: Speed response 40 Hz/motor unit With a PG, our unique high-speed current vector control enables your machine to respond more rapidly to speed-reference changes. The speed remains constant even if the load fluctuates.
Quick Response to Reference Changes
Speed reference step response
960min-1
Motor speed
450min-1 Torque reference 8min-1 100%
Torque reference
Motor current 8A
28A
100
50ms
60Hz
60Hz
28s
12s
Motor speed
12Hz/div
Phase U Output Current 25A/div) Slip Starting current is suppressed.
Motor speed
12Hz/div
OFF
OFF
Relay delay time Braking voltage of braking transistor
OFF
OFF
Relay delay time
0
Output frequency Emergency stop time Selected acceleration time (1 to 4)
Main-circuit low-voltage detection level 0 Output frequency of inverter No. 1 Output frequency of inverter No. 2 Output frequency of inverter No. 3
0
KEB deceleration time
Droop Control This function arbitrarily sets the slip of the motor. This function is effective for material handling machines such as cranes and conveyors.
Droop Control Gain
Droop control gain (b7-01)
Rewinding Operation
T N X M Motor
Configuration Normal Rotation Direction Torque Reference Polarity (TREF) Speed Limit Polarity (SLIM)
Line direction
X M Motor
Line direction
Forward
Torque Torque limit
N
Reverse
Torque Torque limit
Forward
Torque Torque limit
Reverse
Torque
100%
Torque limit TREF N Torque
TREF
SLIM
Generated Torque
(d5-05) 0 Speed
-(d5-05)
TREF
N
TREF
SLIM 0 (d5-05)
Torque limit
TREF(%) C5-01
N(%) =
Speed
TREF(%) C5-01
N(%) =
N(%) =
Set the droop control gain as speed reduction at a 100% *:motor torque, as a percentagethe the maximum output frequency. of
Zero-servo Control No matter if an external force is applied or an offset is set for an analog reference input, this function stops a motor electrically and forcibly when the frequency (speed) reference drops to the zero-speed level.
Feedforward Control An accel/decel torque is applied by the feedforward control device, which enables a quick response. Therefore, it is not necessary to increase the gain forcibly. This function is effective to improve response to accel/decel for a load with high moment of inertia or machine with low rigidity.
Overshoot Control Effects
Overshooting is suppressed when the acceleration completes.
1050
1050
Motor speed
If the frequency (speed) reference decreases to the zero-speed level while the zeroservo command is ON, the motor stops in zero-servo status.
900 750
900 750
0 0
0.5
Time (s)
0 0
0.5
Time (s)
Feedforward control
2 Stationary autotuning
Open-loop vector control, flux vector control
3 Stationary autotuning
Use this mode to perform autotuning for a motor connected to a load such as material handling machine.
If the motor cable length changes or the motor capacity is different from the inverter capacity in the applications using V/f control, perform this autotuing to improve the control accuracy.
IM
IM
IM
Features
the figure below. The digital reference input points are increased to 8 (conventionally 7), and the analog reference input points are increased to 3 (conventionally 2).
Analog reference card (AI-14U and AI-14B) and digital
or source (+24V common). An external +24V power supply is also available for selecting the signal input.
Varispeed F7
Power Supply R S T S1 S2 S3 S4 S5 S6 S7 S8 RP A1 Option Card A2 A3 AC R+ R S+ S IG Digital Operator U V W IM PG Option Pulse Train Output Analog Output
SI-N1
CC-Link
SI-C
Field buses
MP AM FM AC M1 M2 P1 P2 PC
Output Option
6-pulse input without AC reactor (conventional model) Current distortion factor: 88%
12-pulse input with optical transformer with a dual stardelta secondary Current distortion factor: 12% Input Current Waveforms
Note: For 12-pulse input, a transformer with a star-delta secondary is required for the input power supply.
control circuits and the independent cover of the wiring parts promise easy wiring and high reliability.
The one-touch detachable cooling fan
Global standards
Certified by UL/cUL and CE marking
Note : When using CE standard inverters, the special EMC-compatible noise filter is required. Contact your Yaskawa representative.
All constants of each inverter can be managed by a personal computer, which simplifies the adjustment and maintenance.
PC
CPU Pentium 200 MHz min. Main Memory 64 MB min. (96 MB min. recommended) Free Hard For standard setup Resolution OS Super VGA monitor (800 x 600 pixels, small fonts)
Windows 98 Windows NT4.0 Service Pack3 or later (IE4.01 Service Pack2 or later) Windows 2000 Windows ME Windows XP
RS-232C, RS-422, or RS-485 I/F CD-ROM drive (for installation only) Adobe Acrobat Reader (Adobe Systems Incorporated)
Others
Automatic Operation with Preset Pattern Automatic operation according to a preset operation pattern is possible.
Troubleshooting Confirm faults occurred. Display fault trace, causes, and corrective actions.
Features
Disk Space
Features
Constants can be easily up/downloaded using the copy function. Even if an inverter failure occurs, operations can be quickly resumed soon after the replacement of the inverter. An operator with a LCD indicator corresponding to seven languages are available as an option.
Japanese (katakana), English, German, French, Italian, Spanish, and Portuguese.
The standard digital operator with easy to read LED indicators allows remote operation using an extension cable (option). The quick program mode requires only few constant settings. The verify mode enables you to check all modified constants at one time.
Functions
Remote Mode
Lights when selecting input mode from the control circuit terminal. SEQLED lights when selecting run command from control circuit terminal. REFLED lights when selecting frequency reference from control circuit terminals A1 and A2. FWDLED lights at forward run. R E V LED lights at reverse run.
Menu Key
Changes the display of operation and programming mode.
Escape Key
Returns to the status entered before [DATA/ENTER] key was pressed.
DATA/ENTER Key
Selects mode, group, function or constant name. Displays each constant set value while displaying a constant name. By pressing this key again, the set value is written in.
Frequency Setting
RUN LED STOP LED
ON
Blinking
OFF
G
a l
Description
F 0.00
Mode selection
Select LOCAL mode. Forward Jog Run (6 Hz) JOG run procedure (RUNs while depressing JOG key.) Frequency Setting Change reference value.
t f f z
G G G
f1- 01
A.TUNE ON
F 6.00
f1- 01
f
Change the value by depressing,
G G G G G
F00.00 F15.00
G G G G G G G G G G
f1- 01 f1- 02
pvu
Write-in set value. Select output frequency monitor display. Forward Run Forward Run (15 Hz)
u f z u f u u V
f z u
0014.0 f1- 04
DRIVE ON
15.00
RUN LED ON
V
Frequency Changing 15Hz 60Hz Select frequency display. Change reference value.
Start auto-tuning.
fUn12 fUn12
Tuning completed
v f
G G G G G G G G
End
DRIVE blinks.
pvu
Write-in set value. Select output frequency monitor display. Reverse Run Switch to reverse run. Stop Decelerates to a stop.
t
Press the key for several times until DRIVE LED blinks.
F60.00
AfterEnddisplay
f z u d W
Power ON
t f
F 0.00
0.00
G
u u u u u u
DRIVE LED ON
F 0.00
Display Example
Output frequency monitor Output current monitor Output voltage monitor [set by o1-01] U1-== monitor U2-== monitor [fault trace] U3-== monitor [fault history]
G G G G G G
Digital Operator
02
Specifications
200 V ClassSpecifications in blue letters are available for inverters of Spec E or later
Model CIMR-F7A /
Max. Applicable Motor Output1
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2.2 3.7 18 5.7 15 5.5 24 8.8 23 7.5 37 12 31 11 52 17 45 15 68 22 58 18.5 84 27 71
2022 22 94 32 85
kW 0.4 0.75 1.5 A kVA A 3.8 1.2 3.2 4.9 1.6 4.1
Rated Input Current Power Supply Output Characteristics Inverter Capacity Rated Current Max. Voltage Max. Frequency
Rated Input Voltage and Frequency Allowable Voltage Fluctuation Allowable Frequency Fluctuation
3-phase, 200/208/220/230/240 V (Proportional to input voltage) CT (low carrier frequency, constant torque) mode : 300 Hz, VT (high-carrier frequency, variable torque) mode : 400 Hz 3-phase 200/208/220/230/240 V, 50/60 Hz2 10 15 5 Option Not available
9.8 m/s2 at 20Hz or below, up to 5.9 m/s2 at 20Hz to 55Hz
Provided Available3
9.8 m/s2 at 20Hz or below, up to 2.0 m/s2 at 20Hz to 55Hz
1Our standard 4-pole motors are used for max. applicable motor output. Choose the inverter model whose rated current is allowable within the motor rated current range. 2When using the inverter of 200 V class 37 kW or more with a cooling fan of three-phase 230 V 50 Hz or 240 V 50/60 Hz power supply, a transformer for the cooling fan is required. 3A 3-wired transformer is required at 12-pulse input.
400 V ClassSpecifications in blue letters are available for inverters of Spec E or later
Model CIMR-F7A /
Max. Applicable Motor Output1
40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300 2.2 6.4 4.0 5.3 3.7 9.0 5.8 5.5 15 9.5 7.5 20 13 17 11 29 18 24 15 37 24 31 18.5 47 30 39 22 50 34 45 30 66 46 60 37 83 57 75 45 55 75 90 110 132 160 185 220 300
kW 0.4 0.75 1.5 A kVA A 2.2 1.4 1.8 2.5 1.6 2.1 4.4 2.8 3.7
Rated Input Current Power Supply Output Characteristics Inverter Capacity Rated Current Max. Voltage Max. Frequency
Rated Input Voltage and Frequency Allowable Voltage Fluctuation Allowable Frequency Fluctuation
100 120 165 198 238 286 334 407 557 743 69 91 85 110 140 160 200 230 280 390 510
7.6 12.5
3-phase, 380/400/415/440/460/480 V (Proportional to input voltage) CT (low carrier frequency, constant torque) mode : 300 Hz, VT (high carrier frequency, variable torque) mode : 400 Hz 3-phase 380/400/415/440/460/480V, 50/60 Hz 10 15 5 Option Not available
9.8 m/s2 at 20Hz or below, up to 5.9 m/s2 at 20Hz to 55Hz
Provided Available2
9.8 m/s2 at 20Hz or below, up to 2.0 m/s2 at 20Hz to 55Hz
1Our standard 4-pole motors are used for max. applicable motor output. Choose the inverter model whose rated current is allowable within the motor rated current range. 2A 3-wired transformer is required at 12-pulse input.
Enclosures
200 V Class Model CIMR-F7A / 20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 Enclosed Type [NEMA1 (Type1)] Available as standard Open Chassis TypeIEC IP00 Available by removing the upper and lower cover of enclosed type 400 V Class 2022 2030 2037 2045 2055 2075 2090 2110 Not available Available for option Available as standard
Model CIMR-F7A / 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300 Available for option Not available Available as standard Enclosed Type [NEMA1 (Type1)] Open Chassis TypeIEC IP00 Available by removing the upper and lower cover of enclosed type Available as standard
Enclosed type [NEMA1 (Type1)] : Provides a clean and ventilated environment within the enclosure. Front and rear panels are firmly secured (e.g. front, rear, right, left, top, bottom). Open chassis type (IEC IP00) : Designed for mounting in a customer's enclosure. Constructed so that openings do not permit direct or inadvertent access to live parts by personnel.
Model Designation
CIMR F7 A 2 0P4
Inverter F7 series Specifications Japanese standard specifications Voltage 2200 V class 4400 V class Max. Applicable Motor Output 0P40.4 kW to 022 22 kW to 300300 kW
2 0P4 1 E
Voltage Max. Applicable Motor Output Revision Enclosure 0Open chassis typeIEC IP00 1Enclosed type [NEMA 1 (Type 1)]
10
200/400 V ClassSpecifications in blue letters are available for inverters of Spec E or later
Control Method Starting Torque Speed Control Range Speed Control Accuracy Speed Response Torque Limit Frequency Control Range Frequency Accuracy Frequency Setting Resolution Output Frequency Resolution Overload Capacity Frequency Setting Signal Accel/Decel Time Braking Torque
Sine wave PWM [Flux vector, open loop vector, V/f, V/f with PG control (switched by parameter)] 150 at 0.5 Hz (Open loop vector control, CT mode)1, 2, 150 at 0 min-1 (Flux vector control, CT mode)1, 2 1 : 100 (Open loop vector control)1, 1 : 1000 (Flux vector control)1 0.2 3 (Open loop vector control at 25 10 )1, 0.02 (Flux vector control)1 5 Hz (Open loop vector control)1, 40 Hz (Flux vector control)1 Provided for vector control only CT mode : 0.01 to 300 Hz2, VT mode : 0.01 to 400 Hz2 Digital reference: 0.01 , 10 to 40 ; Analog reference: 0.1 , 25 10 Digital Reference: 0.01 Hz ; Analog reference: 0.03 Hz/60 Hz (11 bit) 0.001 Hz CT mode : 150 rated output current for 1 min. (not available when using 200 V 110 kW or 400 V 220 to 300 kW inverters) VT mode : 120 rated output current for 1 min. 10 V to 10 V, 0 to 10V, 4 to 20 mA, pulse train 0.01 to 6000.0 s (Accel/Decel time setting independently, 4 steps available) Approx. 20 (Approx. 125 when using braking resistor)4 Inverters of 200/400 V 18.5 kW or less have a built-in braking transistor. Torque control, droop control, speed/torque control switching, feedforward control, zero-servo control, momentary power loss restart, speed search, overtorque detection, toruque limit, 17-step speed operation (maximum), accel/decel time changeover, S-curve accel/decel, 3-wire sequence, autotuning (dynamic, static), DWELL, cooling fan ON/OFF, slip compensation, torque compensation, jump frequency, frequency upper/lower limit settings, DC injection braking at start/stop, high slip braking, PID control (with sleep function), energy-saving control, MEMOBUS communication (RS-485/422 max. 19.2 kbps), fault retry, constant copy, etc. Electronic thermal overload relay Motor coasts to stop at approx. 200 rated output current. Motor coasts to stop at blown fuse. CT mode: Motor coasts to stop at 150 rated output current for 1 min. (Not available when using 200 V class 110 kW, 400 V class 220 to 300 kW inverters.) VT mode: Motor coasts to stop at 120 rated output current for 1 min. Motor coasts to stop if the main circuit voltage exceeds approx. 410 VDC (approx. 820 VDC for 400 V class). Motor coasts to stop if the main circuit voltage drops to approx. 190 VDC (approx. 380 VDC for 400 V class) or below. Immediately stop after 15 ms or longer power loss (at factory setting). Continuous operation during power loss less than 2 s (standard). Thermistor Stall prevention during acceleration/deceleration and constant speed operation Provided by electronic circuit (overcurrent level) Indicates until the main circuit voltage reaches 50 V. Indoor (Protected from corrosive gases and dust) 95 RH (non-condensing) 20 to 60 (for short period during shipping) 10 to 40 for NEMA1 type, 10 to 45 for open chassis type 1000 m or below
Control Characteristics
Motor Overload Protection Instantaneous Overcurrent Fuse Protection Protective Functions Overload Overvoltage Undervoltage Momentary Power Loss Fin Overheat Stall Prevention Ground Fault5 Power Charge Indication Location Humidity Storage Temperature Ambient Temperature Altitude
1Specifications for open vector control and flux vector control require dynamic auto-tuning. 2When exceeding the overload capacity, increase the inverter capacity. 3The speed control accuracy depends on the installation conditions and type of motor used. Contact your Yaskawa representative for details. 4When using a braking resistor or braking resistor unit, set L3-04 = 0 (deceleration stall prevention). If not, motor may not stop at the set time. 5The ground fault here is one that occurs in the motor wiring during operation. Ground faults may not be detected under the following conditions. A ground fault with low resistance which occurs in motor cables or terminals. The inverter power supply is turned ON after a ground fault has occurred.
Environmental Conditions
11
Specifications
G2
B1
B2
U/T1
Varispeed F7
V/T2 W/T3
IM
S1
3
Reverse Run/Stop
S2 S3 S4 S5 S6 S7 S8
CN5NPN Setting
External Fault
MP AC
Fault Reset
Multi-function Input
Factory Setting
AM
20 k
10 to 10 V 2 mA Output Current 0 to +10V at Factory Setting
AM
FM
24V 8mA
20 k
AC SC
1 3
FM
E G E G
Shielded Wire Connection Terminal
1
2 k
Frequency Meter Adjusting Potentiometer
RP
Frequency Setter 3
V A1 A2
MA
Freq. Setting Power Supply
15 V 20 mA
MA MC
2 k
0 to 10 V 4 to 20 mA P
MB MC
2 1
0 to 10 V
A3
P P
M1 M2
AC
0V V
15 V 20 mA
P1
Terminal Resistance
Multi-function
Open Collector Output 48 VDC 50 mA or less
R
MEMOBUS Communication RS-485/422
1
P2 PC
R S S IG
2Terminal symbols: shows main circuit; shows control circuit. 3Connection when sequence input signals (S1 to S8) are no-voltage contacts or sequence connections (0 V common/sink mode) by NPN transistor (factory setting). When sequence connections by PNP transistor (24 V common/source mode) or preparing a external 24 V power supply, see Typical Connection Diagrams (p64). 4Multi-function analog output is only for use on meters (frequency, current, voltage and watt), and not available for the feedback control system. 5DC reactor is built-in for inverters of 200 V 22 to 110 kW and 400 V 22 to 300 kW to improve the inverter input rate (option for 18.5 kW or less). When connecting a DC reactor for inverters of 18.5 kW or less, remove the shorting bar. 6When connecting mounted type braking resistor (ERF), set system constant L8-01 to 1. When using an externally installed braking resistor unit, a sequence is required to break the power by thermal trip.
Control Circuit and Communication Circuit Terminal ArrangementSpecifications in blue letters are available for inverters of Spec E or later
E G FM SC S1 S2 AC A1 S3 AM A2 S4 P1 A3 S5 P2 V S6 PC AC S7 SC V S8 MP RP S9 P3 R S10 C3 R S11 P4 S S12 C4 S IG MA M1 MB MC M2 E G
12
Terminal Functions
Main Circuit
Voltage Model CIMR-F7A _ 20P4 to 2018 Max Applicable Motor Output 0.4 to 18.5 kW R/L1 Main circuit input S/L2 power supply T/L3 R1/L11 S1/L21 T1/L31 U/T1 V/T2 W/T3 B1 Braking resistor unit B2 F DC reactor G1 G 1 G 2 G2 G3
DC power supply1 G 1 F
200 V 20222030 22 to 30 kW
Main circuit input power supply R-R1, S-S1 and T-T1 have been wired before shipment (See P59).
Main circuit input power supply R-R1, S-S1 and T-T1 have been wired before shipment (See P59).
Inverter output
Ground terminal100 or less Cooling fan power supply
2
Cooling fan power supply
3
s/b2 s s
r/b1 200/b2 200 400/b2 400 J
1G 1 F DC power input does not conform to UL/c-UL listed standard. 2Cooling fan power supply r/l1s/l2: 200 to 220 VAC 50 Hz, 200 to 230 VAC 60 Hz (A transformer is required for 230 V 50 Hz or 240 V 50/60 Hz power supply.) 3Cooling fan power supply r/l1s 200/l2 200: 200 to 220 VAC 50 Hz, 200 to 230 VAC 60 Hz, r/l1s 400/l2 400: 380 to 480 VAC 50/60 Hz
Control Circuit (200 V/400 V Class)Specifications in blue letters are available for inverters of Spec E or later
Classification Terminal S1 S2 S3 S4 S5 S6 S7 S8 SC V V A1 A2 A3 AC E G P1 Open-collector Output P2 PC MA MB MC M1 M2 FM AM AC RP MP Signal Function
Forward run-stop signal Reverse run-stop signal Multi-function input selection 1 Multi-function input selection 2 Multi-function input selection 3 Multi-function input selection 4 Multi-function input selection 5 Multi-function input selection 6 Sequence control input common 15 V Power supply output 15 V Power supply output Master speed frequency ref.
Description
Signal Level
Relay output
Forward run at closed, stop at open Reverse run at closed, stop at open Factory setting: external fault at closed Factory setting: fault reset at closed Photo-coupler insulation Factory setting: multi-step speed setting 1 is valid at closed Input 24 VDC 8 mA Factory setting: multi-step speed setting 2 is valid at closed Factory setting: JOG run at closed Factory setting: external baseblock at closed For analog reference 15 V power supply 15 V (Allowable current 20 mA max.) For analog reference 15 V power supply 15 V (Allowable current 20 mA max.) 0 to 10 V/100 , 10 to 10 V/100 to 100 0 to 10 V (Input impedance 20 k ) 4 to 20 mA (Input impedance 250 4 to 20 mA/100 , 0 to 10 V/100 , 10 to 10 V/100 to 100 Murti-function analog input Factory setting: added to the terminal A1 (H3-09=0) 10 to 10 V, 0 to 10 V (Input impedance 20 k 10 to +10V/100 to +100%, 0 to +10V/100% Master speed analog input 10 to 10V, 0 to 10 V (Input impedance 20 k Factory setting: Not used Analog common 0V Connection to shield wire and option ground wire Factory setting: zero speed signal Multi-function PHC output 1 Closed at or below zero speed level (b2-01) 48 VDC 50 mA or less Factory setting: frequency agreement Multi-function PHC output 2 Closed within 2 Hz of setting frequency Photo-coupler output common Fault at closed between terminals MA and MC Fault output (NO contact) open between terminals MB and MC Fault at Fault output (NC contact) Dry contact, contact capacity Relay contact output common 250 VAC 10 mA to 1 A 30 VDC 10 mA to 1 A Factory setting: Run signal Multi-function contact output (NO contact) Running at closed between terminals M1 and M2 Factory setting: output frequency 0 to 10 V/100 freq. Multi-function analog monitor 1 10 to 10 VDC 5 Factory setting: current monitor 5 V/inverter rated current Multi-function analog monitor 2 2 mA or less Analog common Factory setting: frequency reference input (H6-010) Multi-function pulse input 0 to 32 kHz3 k Multi-function pulse monitor Factory setting: output frequency (H6-062) 0 to 32 kHz2.2 k
Description
When using two RS-485 wires, short-circuit between R and S, R and S.
Signal Level
Differential input PHC isolation Differential output PHC isolation
13
Dimensions
Open Chassis TypeIEC IP00
W1 4-d 4-d
H1
H1
H2
D1 3 D
T1
W1 W 6-d
T1 D1 3 D
Drawing 1
W1 W1 4-d W2
Drawing 2
H1
H1 T1 D1 W3 W1 W Dimensions in mm W2 W3 H1
H*
H2 H
H2*
H2
(5)
(5)
(5)
T1 D1 D
Drawing 3
Voltage
Max. Applicable Motor Output kW
Drawing 4
W H D 157 W1 H2 D1 39 126 177 200 300 350 400 450 600 725 850 885 197 207 258 298 328 348 358 378 157 186 216 195 220 250 325 370 445 285 335 385 435 575 12.5 700 820 855 15 130 140 39 126 177 200 300 350 450 550 725 850 916* 1305 1475 197 207 258 283 348 358 378 413 186 216 220 260 325 370 445 540 730 240 365 270 365 285 335 435 535 700 820 855 1270 1440 12.5 130 500 575 710 916 15 45.8* 15 140 125.5 4.5 M12 7.5 8 266 7 59 65.5 78 100 105 3.2 M10 2.3 M6 5 M5 4 6 10 21 36 88 89 102 120 160 260 280 405 Fan cooled 4.5 M12 7.5 100 100 3.2 M10 8 266 7 59 65.5 78 2.3 M6 5 M5 4 6 7 11 21 24 57 63 86 87 108 150 3 Fan cooled T1 d Approx. Mass Cooling kg Method 3 Self cooled
Inverter CIMR-F7A _
DWG
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 200 V 15 Class 18.5 3-phase 22 30 37 45 55 75 90 110 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 400 V 22 30 Class 3-phase 37 45 55 75 90 110 132 160 185 220 300
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160* 4185 4220 4300
140
280
H2
Self cooled
140
280
H1
H1
H0
H0
T1 H2 D W H3 D1 W1 4 3 D
T1 D1
H2
Drawing 1
W1 4-d
Drawing 2
H2
(5)
(5)
Max.10
H3
T1 D1 (5) D
Drawing 3
Voltage
Max. Applicable Motor Output kW
Inverter CIMR-F7A _
DWG
D 157
W1
Dimensions in mm H0 H1 H2
H3
D1 39
T1
0.4 0.75 1.5 2.2 3.7 5.5 7.5 200 V 11 Class 15 3-phase 18.5 22 30 37 45 55 75 90 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 400 V 18.5 Class 22 3-phase 30 37 45 55 75 90 110 132 160
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160
140
280 177
126
280
266
59
M5 4 6 7
8 7.5
12.5 700 820 15 302 393 39 126 280 266 7 59 186 216 220 260 325 370 445 300 350 450 550 725 850 916 285 335 435 535 700 820 855 12.5 15 46 7.5 85 165 302 130 393 408 140 8 0 65.5 78 100 105 130
4.5
Self cooled
140
280 177
M5 4 6 10
2.3
M6
24 40
Fan cooled
15
Dimensions
H1
H0 H
Internal Heatsink Upper Cover 55 Upper Part Air Temperature 10 to 55 Heatsink Open Chassis Type Inverter Lower Cover Inverter Inlet Temperature 10 to 45 45 Peripheral Temperature 40
Upper Cover
A mm or more B mm or more Air
Heatsink
30 mm or more 50 mm or more
30 mm or more
Side Spaces
Note: Refer to the following specifications for securing spaces. 200 V class inverters of 110 kW or 400 V class inverters of 160 to 220 kW: A = 120, B = 120 A = 300, B = 300 400 V class inverters of 300 kW: A = 50, B = 120 All other inverters: : If, however, there is a fan in the top of the control panel with sufficient exhaust capacity, the following dimensions may be used: A = 50, B = 120.
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110
1.2 1.6 2.7 3.7 5.7 8.8 3.2 4.1 7.0 9.6 20 27 50 15 23 12 31 17 45 22 58 27 71 32 44 55 69 82 110 130 160
70 112 164 219 374 429 501 586 865 1015 1266 1588 2019 2437 2733
Inside Unit
39
42
50
59
74
84 113 170 183 211 274 352 411 505 619 838 997 1242
59
69 100 129 186 248 332 544 612 712 860 1217 1426 1771 2207 2857 3434 3975 Self cooled Fan cooled
400 V Class
Model CIMR-F7A _ Inverter Capacity Rated Current Heat Loss W Fin kVA A W 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
1.4 1.6 2.8 4.0 5.8 9.5 13 18 24 24 31 30 39 34 45 46 60 57 75 69 85 110 140 160 200 230 280 390 510
80 127 193 252 326 426 466 678 784 901 1203 1399 1614 2097 2388 2791 3237 3740 5838
Inside Unit
39
41
48
56
68
82 114 158 172 208 259 317 360 415 495 575 671 853 1002 1147 1372 1537 2320
53
58
84 115 148 209 307 410 498 634 725 995 1144 1316 1698 1974 2285 2950 3390 3938 4609 5277 8158 Fan cooled
Self cooled
16
Attachments
Heatsink External Mounting Attachment
The Varispeed F7 inverters under the 200/400 V class 18.5 kW or less need this attachment for mounting the heatsink externally. This attachment expands the outer dimensions of the width and height of the inverter. (Attachment is not required for inverters of 22 kW or more.) Note: Contact your Yaskawa representative about reusing an attachment that was used with a conventional model such as the VS-616G5. in mm
Mounting Panel Wall
Model CIMR-F7A Attachment Order Code W H W1 H1 D1 D2 D3
W1 W
D1
D2 D3 or more
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018
37.4 EZZ08676A 155 302 126 290 122.6 57.4 EZZ08676B EZZ08676C 210 250 330 392 180 216 316 136.1 63.4 372 133.6 76.4 37.4 EZZ08676A 155 302 126 290 122.6 57.4 EZZ08676B EZZ08676C 210 250 330 392 180 216 316 136.1 63.4 372 133.6 76.4
40
60 70 85 40
H1 H
60 70 85
(Heatsink)
in mm
Drawing W H W1W2 W3H1H2 H3 A B d
30
20
6-d Tap
H2
(H2)
Model CIMR-F7A
H2
(W3)
(W3)
W1 W
H2 H3
Drawing 1
4-d Tap
a a
H3
(W2)
(W2) (H2)
W1 (W)
Drawing 4
H1 H 20 6-d Tap
W3
W3 (H2)
H3 H2
W2
W2
W1 W
Drawing 2
19 H3 4-d Tap
a a
15
H1 (H)
W3 W2
W3 W2
(W3) (W2)
(W3) (W2)
W1 (W)
W1 W
H3 59
W2
W2
Drawing 5
15
W3
W3
20P4 20P7 21P5 155 302 126 6 8.5 290 9.5 6 138 271 M5 22P2 23P7 1 25P5 27P5 210 330 180 7 197 298 6.5 316 9 2011 8.5 2015 250 392 216 8.5 372 9.5 10 233 353 M6 2018 250 400 195 244 369 385 2022 8 7.5 24.5 3 275 450 220 269 419 435 2030 2037 375 600 250 359 545 575 15 2045 M10 54.5 8 12.5 2 2055 450 725 325 434 673 700 13.5 2075 500 850 370 57 484 782 8 820 2090 19 15 M12 575 885 445 55 10 855 555 817 2110 40P4 40P7 41P5 155 302 126 6 8.5 290 9.5 6 138 271 M5 42P2 43P7 1 45P5 47P5 210 330 180 7 197 298 6.5 316 9 4011 8.5 4015 250 392 216 8.5 372 9.5 10 233 353 4018 M6 4022 275 450 220 269 419 3 435 4030 8 7.5 24.5 4037 325 550 260 309 519 8 535 4045 2 4055 4075 450 725 325 54.5 8 700 13.5 12.5 434 673 M10 4090 4110 500 850 370 57 8 820 19 15 484 782 M12 4132 3 575 925 445 55 10 895 15 555 817 4160 4185 4 710 1305 540 76.5 8.5 1270 21.5 693 1227 M12 4220 5 916 1475 730 72.5 20.5 1440 21.5 875 1397 4300 : The sizes are different between the top and the bottom. Refer to Drawings 3 to 5.
H1 H
H1 H
(H2)
H1 (H)
Drawing 3
17
Dimensions
Software Functions
The Varispeed F7 flexible inverter incorporates a variety of application features. Select special functions from a multitude of possibilities to perfectly match your machine requirements.
Digital Reference Input
Power Supply
Varispeed F7
R S T S1 S2 S3 S4 S5 S6 S7 S8 RP
Digital Operator
U V W
IM
PG Option
MP AM FM AC
MEMOBUS Communication
A1 A2 Option Card M1 A3 M2 AC P1 P2 R+ PC R S+ S IG
Input Option
Output Option
Function
Target Market
Application
Description of Function
Choose one of four methods of stopping the inverter depending on the braking torque or machine inertia: deceleration to stop, coast to stop, DC braking stop, and coast to stop with timer. DC injection braking is performed at top speed. The duty is 5 or less. Can generate 50 to 70 of the braking torque. When the direction of the free running motor is not fixed, the speed search operation function is difficult to use. The motor can be automatically stopped by DC injection braking, and be restarted by the inverter. Switching of commercial power source to inverter or vice versa is done without stopping the motor. Starts the inverter at the specified frequency, automatically detects the synchronization point, and performs at the operation frequency. No speed detector is required. Use as a timer for setting the delay time on or off. Processes PID operation in the inverter and the result is used as frequency reference for controlling air/water amounts and pressure. Prevents the motor from stalling by temporarily storing the output frequency during acceleration and deceleration. Allows the user to regulate the speed. If droop control is used, highresistance motor characteristics can be set to maintain balance of the loads of multiple motors. Supplies voltage to motor to always be most effective according to load and rotating speed. (Automatic temperature compensation function provided) Stops the motor even if an external force acts on the motor when the motor is stopped. The accel/decel times are switched by an external contact signal. Necessary for switching operation of two machines with different functions by a single inverter.
Stopping Method Selection DC Injection Braking Stop DC Injection Braking at Start Commercial Power Source/inverter Switchover Operation Speed Search Operation Timer Function
To choose the best stopping method General machines for the machine characteristics. High-speed routers,etc. DC injection braking stop of induction motor
b1
45
b1 b2
45
Blowers, pumps, Starting the free etc. which have running motor wind-mill effects Blowers, pumps, mixers, extruders, etc. Automatic switching between commercial power source and inverter
b2
39
b3
39 55
Inertia load drives Synchronize with such as blowers, the coasting winders, etc. motor General machines Easy operation Pumps, air Automatic conditionings, etc. process control Machines with heavy To smoothly accelerate loads such as centrifugal and decelerate with a heavy load. separators Distributed drives To maintain the of conveyors torque and speed Multi-motor alances of the load. drives General Most efficient automatic operation
b3 H1 b4 H1 b5
39
46
PID Control
52
DWELL Function
b6
Droop
Control
b7
b8
54
To lock a motor in Elevating devices, position when the carriages, etc motor is stopped. Transporting equipment for automatic control panels, etc. The accel/decel time changeover with an external signal
b9
C1 H1
36
18
Function
Target Market
Application
Description of Function
S-curve Characteristics Carrier Frequency Setting Multi-step Speed Operation Upper/lower Frequency Limit Operation Prohibit Setting of Specific Frequency (Frequency Jump Control) Trim Control Increase/Decrease Command Frequency Hold Operation
Transport equipment To reduce shock when such as conveyors starting and stopping and carriages the machine. General machines Lower noise, eliminates resonance Schedule operation under fixed speed command and positioning stop
A machine moves smoothly by setting the S-curve characteristics in the start or stop time for acceleration and deceleration. The carrier frequency can be set to reduce the resonance or acoustic noise from the motor and machine system. Multi-step operation (up to 17-step) can be set by setting the contact combinations, so the connection with PLC becomes very easy. When combined with jog speed can also allow simple positioning. The upper and lower limits of the motor speed, command signal bias and gain can be set independently without peripheral operation units.
C2
36
C6
43
Transporting equipment
d1 H1
35
d2
37
Prevent mechanical The motor simply passes through the preset speed, but continuous running General machines vibration in the can be done at this speed. This function is used to avoid the mechanical equipment resonance point of the equipment.
d3
37
General machines Easy operation Winding machines To maintain constant tension control (winding/rewinding) To provide torque Helper drives upon starting Simple General machines configuration of control circuit General machines Easy operation
d4 H1 d5 H3
40
Torque
Control
Adjusts motors rated torque by external reference. For tension control of winders and for torque control with helper drives. Operation can be accomplished using a spring-loaded push-button switch. Operation and settings can be selected while the inverter is online. (digital operator/external instruction, signal input/output).
3-wire Sequence
H1
46
H1
46
UP/DOWN Command
H1
46
Transporting equipment
2 motors/ inverter
Uses one inverter for alternate control of two motors. Functions as supplementary frequency reference. Also used for fine control of input reference, output voltage adjustment, external control of accel/decel time, and fine adjustment of overtorque detection level. Two of the following items can be used: frequency meter, ammeter, voltmeter, or wattmeter. PID target and PID feedback values are input with pulse train when PID control as well as frequency reference function. Six items including PID target and PID feedback values can be monitored as well as frequency reference and output frequency. Motor overload protection using electric thermal function. Set the motor rated current, and select the allowable load characteristics for each motor model. Automatically restarts the motor after the main power supply is restored with the residual energy from the control power supply.
H1
H3
38
H4
43
H6
44
General machines
H6
44
Electric Thermal
General machines
L1
51
L2
39
19
Software Functions
d4 H1
Function
Target Market
Application
Description of Function
If a power failure or momentary power loss occurs, this function continues to control the inverter with the kinetic energy of the machine until the motor comes to a complete halt. Stops acceleration or deceleration if the inverter output current reaches the respective set value during acceleration, deceleration, or operation. And, continues operation when the inverter output current value becomes less than the set value. If the output frequency is out of the set range, the signal is output from the multi-function output terminal. When the frequency reference signal is lost, operation is automatically continued at the pre-programmed speed. (If the host computer fails.) This function is important for air conditioning systems in intelligent buildings. When the inverter trips, it begins to coast, is immediately diagnosed by computer, resets automatically, and returns to the original operation speed. Up to 10 retries can be selected. Closed when overtorque setting operation is accomplished. Can be used as a torque limiter. The inverter can be switched to coasting or motor speed reducing mode as soon as it reaches a certain preset torque level. For pump or blower, the operation frequency can be automatically reduced to the load balancing point, according to the overload condition, and prevent overload tripping.
KEB Braking
General-purpose Deceleration at machines, momentary machine tools power loss. Protects machines, General machines and ensures operation to be continued. Detects frequency and General machines outputs the signal to be used for interlock. Improvement of Air conditioners continuous operation reliability Air conditioners, Improvement of etc. operation reliability Machine tools, blowers, cutters, extruders, etc. Protection of machine, improvement of continuous operation reliability
Stall Prevention
L3
49
Frequency Detection Automatic Continuous Operation when the Frequency Reference is Lost Fault Trip Retry Operation
L4 H2 L4 H2
42
39
L5
40
Torque Detection
L6 H2
41
Torque Limit
Protection of machine Blowers, pumps, Improvement of continuous operation extruders, etc. reliability Torque limit Fans, blowers Centrifuges, centrifugal casing machines, flywheel drives General machines Emergency stop for a load with high moment of inertia Optimal acceleration/ deceleration for a load with a high moment of inertia Monitor function enhancement Stores inverter constants in the digital operator
L7 H3
48
High-slip Braking
Reduces the deceleration time close to 50% without using a braking resistor.
N3 H1
Feedforward Control
Estimates the acceleration/deceleration torque to improve the follow-up of the speed reference for a load with a high moment of inertia and adds torque to the internal torque reference. Can indicate motor speed (min-1), machine speed under load (min-1), line speed (m/min), etc. Reduces startup time by copying the stored inverter constants to another inverter or for maintenance purpose.
N5
o1
34
Copy Function
Any machines
o3
54
20
Constants List
How to read this list Constants not described in this list are not displayed in the digital operator. Setting constants vary in accordance with password setting (A1-04). A, Q and represent access level and capability. AADVANCED (when the advanced program mode is selected) QQUICK (when the quick program mode and the advanced mode are selected) Cannot be accessed.
Function
Name
Factory Setting
1 2 0 0 0 0 1 1 0 0 0 1 0 0 0.5 Hz 50 0.00 s 0.50 s 0 22 120 2 2.0 s 0.2 s 1.10 1 150 0.01 s 0 0.0 s 0.0 s 0 1.00 1.0 s 100.0 0.00 s 100.0 0.0 0.00 s 0 1.0 0 0 0 1.0 s 0.0 Hz 0.0 s 0.0 s
Control Mode Online V/f V/f Open Changing without with Loop Flux PG PG Vector Vector
A A Q A A A A Q Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A Q Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A Q Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A Q Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
Ref. Page
Language selection for digital operator display1 0 to 6 Constant access level Control method selection Initialize Password Password setting
Initialize
30
A2-01 User setting constant to A2-32 b1-01 b1-02 b1-03 Sequence b1-04 b1-05# b1-06 b1-07 b1-08 b2-01 DC Braking b2-02 b2-03 b2-04 b2-08 b3-01 b3-02 b3-03 Speed Search b3-05 b3-10# b3-14# b3-17# b3-18# b3-19# Timer Functions b4-01 b4-02 b5-01 b5-02 b5-03 b5-04 b5-05 b5-06 b5-07 PID Control b5-08 b5-09 b5-10 b5-11 b5-12 b5-13 b5-14 b5-15 b5-16 b5-17
Master frequency reference selection Operation method selection Stopping method selection Prohibition of reverse operation Read sequence input twice
34 45 35
Operation selection for setting E1-09 or less 0 to 3 Operation after switching to remote mode 01 Run command selection in programming modes 012 # Zero speed level (DC injection braking start frequency) 0.0 to 10.0 DC injection braking current DC injection braking time at start DC injection braking time at stop Speed search selection Speed search operating current Speed search deceleration time Speed search wait time Rotation direction search selection Speed search retrial current level Speed search retrial detection time Number of speed search retrials Timer function ON-delay time Timer function OFF-delay time PID control selection Proportional gain (P) Integral (I) time Integral (I) limit Differential (D) time PID limit PID offset adjustment PID primary delay time constant PID output characteristics selection PID output gain PID reverse output selection 0 to 100 0.00 to 10.00 0.00 to 10.00 0 to 3 0 to 200 0.1 to 10.0 0.0 to 20.0 01 0 to 200 0.00 to 1.00 0 to 10 0.0 to 300.0 0.0 to 300.0 0 to 4 0.00 to 25.00 0.0 to 360.0 0.0 to 100.0 0.00 to 10.00 0.0 to 100.0 100.0 to 100.0 0.00 to 10.00 01 0.0 to 25.0 01
39
45
39
47
52
Selection of PID feedback command loss detection 0 to 2 PID feedback command loss detection level 0 to 100 PID feedback command loss detection time 0.0 to 25.5 Slip function braking level PID slip braking delay time Acceleration/deceleration time for PID
0.0 to 400.03 0.0 to 300.0#4
0.0 to 25.5
0.0 to 25.5 0.0 to 6000.0#
Available for inverters of Spec E or later. 1 : Displayed only when using an optional LCD monitor type operator (JVOP-160). 2 : The factory setting depends on the control mode. The factory settings given above are for V/f without PG control. 3 : Factory setting when C6-01=1(VT). When C6-01=0(CT), the factory setting is 0.0 to 150.0. 4 : Factory setting when C6-01=0(CT) for inverters of Spec E or later. When C6-01=1(VT), the factory setting is 0.0 to 400.0.
21
Constants List
Function
No. b6-01
Name
Dwell frequency at start Dwell time at start Dwell frequency at stop Dwell time at stop Droop control gain Droop control delay time Energy-saving mode selection Energy-saving coefficient Energy-saving filter time constant Energy-saving coefficient Power detection filter time constant Search operation voltage limiter Zero-servo gain Zero-servo completion width Acceleration time 1 Deceleration time 1 Acceleration time 2 Deceleration time 2 Acceleration time 3 Deceleration time 3 Acceleration time 4 Deceleration time 4 Emergency stop time Accel/decel time setting unit Accel/decel time switching frequency S-curve characteristic time at acceleration end S-curve characteristic time at deceleration end Slip compensation gain Slip compensation primary delay time Slip compensation limit Slip compensation during regeneration Output voltage control brake selection Torque compensation gain Forward starting torque Reverse starting torque Starting torque time constant ASR integral (I) time 1 ASR proportional (P) gain 2 ASR integral (I) time 2 ASR limit ASR primary delay time ASR switching frequency ASR integral (I) limit
Factory Setting
0.0 Hz 0.0 s 0.0 Hz 0.0 s 0.0 0.05 s 0 0.73 0.50 s4
5
Control Mode Online V/f V/f Open Changing without with Loop Flux PG PG Vector Vector
A A A A A A A A Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A Q Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q Q A A A A A A A A A A A A A A A A A A A A A A
Ref. Page
b6-02 b6-03 b6-04 b7-01# b7-02# b8-01 b8-02 b8-03 b8-04 b8-05 b8-06 b9-01# b9-02# C1-01 C1-02 C1-03 C1-04 C1-05 C1-06 C1-07 C1-08 C1-09 C1-10 C1-11 C2-01 C2-02 C2-03 C2-04 C3-01
0.0 to 10.0
0.0 to 400.01 0.0 to 300.0#2
0.0 to 10.0 0.0 to 100.0 0.03 to 2.00 01 0.0 to 10.0 0.00 to 10.00 0.00 to 655.00 0 to 2000 0 to 100 0 to 100 0 to 16383
Energysaving Control
54
20 ms 0 5 10
Zero-servo
Accel/Decel Time
0.0 to 6000.06
0.1 s
10.0s
33 36
01
0.0 to 400.01 0.0 to 300.0#2
1 0.1 Hz 0.01 s 0.01 s 0.01 s 0.01 s 0.1 1 ms 1 1 1 0.01 1 ms 0.1 0.1 1 ms 0.01 0.001 s 0.01 0.001 s 0.1 0.001 s 0.1 Hz 1
1 0.0 Hz 0.20 s 0.20 s 0.20 s 0.00 s 0.07 2000 ms7 200 0 0 1.00 200 ms7 0.0 0.0 10 ms 0.208 0.200 s8 0.028 0.050 s8 5.0 0.004 s 0.0 Hz 400
S-curve characteristic time at acceleration start 0.00 to 2.50 0.00 to 2.50 0.00 to 2.50 0.0 to 2.5 0 to 10000 0 to 250 01 01 0.00 to 2.50 0.0 to 200.0 200.0 to 0.0 0 to 200 0.000 to 10.000 0.00 to 300.00 0.000 to 10.000 0.0 to 20.0 0.000 to 0.500 0.0 to 300.02 0 to 400 S-curve characteristic time at deceleration start 0.00 to 2.50
S-curve Characteristics
36
50
C3-02 C3-03 C3-04 C3-05 C4-01 C4-02 C4-03 C4-04 C4-05 C5-01 C5-02 C5-03
Torque Compensation
48
50
Available for inverters of Spec E or later. 1 : Factory setting when C6-01=1(VT). When C6-01=0(CT), the factory setting is 0.0 to 150.0. The factory setting is 0.0 to 300.0 for inverters of Spec E or later. 2 : Factory setting when C6-01=0(CT) with inverters of Spec E or later. When C6-01=1(VT), the factory setting is 0.0 to 400.0. 3 : The factory setting is 1.0 when using flux vector control. 4 : The factory setting is 2.00 s when Inverter capacity is 55 kW min. The factory setting will change when the control method is changed. The open-loop vector factory setting is given. 5 : By setting E2-11 (Motor rated output), the appropriate value will be set. The factory setting depends on the Inverter capacity. The value for a 200 V class inverter of 0.4 kW is given. 6 : The setting ranges are depend on the setting of C1-10. If 0 is set in C1-10, the setting range of acceleration and deceleration is 0.00 to 600.00 s. 7 : The factory setting depends on the control mode. The factory settings given above are for V/f without PG control. 8 : When the control method changes, the factory setting is changed. The flux vector control factory settings are given.
22
Function
No. C6-01 C6-02 C6-03 C6-04 C6-05 d1-01 d1-02 d1-03 d1-04 d1-05 d1-06 d1-07 d1-08 d1-09 d1-10 d1-11 d1-12 d1-13 d1-14 d1-15 d1-16 d1-17 d2-01 d2-02 d2-03 d3-01 d3-02 d3-03 d3-04 d4-01 d4-02 d5-01# d5-02#
Name
CT/VT selection Carrier frequency Carrier Frequency Upper Limit2 Carrier Frequency Lower Limit2 Carrier Frequency Gain2 Frequency reference 1 Frequency reference 2 Frequency reference 3 Frequency reference 4 Frequency reference 5 Frequency reference 6 Frequency reference 7 Frequency reference 8 Frequency reference 9 Frequency reference 10 Frequency reference 11 Frequency reference 12 Frequency reference 13 Frequency reference 14 Frequency reference 15 Frequency reference 16 Jog frequency reference Frequency reference upper limit Frequency reference lower limit Master speed reference lower limit Jump frequency 1 Jump frequency 2 Jump frequency 3 Jump frequency width Speed limits Torque control selection Torque reference delay time Speed limit selection Speed limit Speed limit bias Speed/torque control switching timer Field weakening level Field frequency Field forcing function selection Field forcing limit
Factory Setting
01 Depends on setting of C6-01 15.0 kHz4 15.0 kHz4 0
Control Mode Online V/f Open V/f Changing without with Loop Flux PG PG Vector Vector
Q Q A A A Q Q Q Q A A A A A A A A A A A A Q A A A A A A A A A A A Q Q A A A Q Q Q Q A A A A A A A A A A A A Q A A A A A A A A A A A Q Q A Q Q Q Q A A A A A A A A A A A A Q A A A A A A A A A A A Q Q A Q Q Q Q A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A
Ref. Page
31 43
Carrier Frequency
Preset Reference
400.005,6
0.01 Hz
0.00 Hz
35
6.00 Hz 0.0 to 110.0 0.0 to 110.0 0.0 to 110.0 0.0 to 400.06 0.0 to 300.0#7 0.0 to 20.0 0 to 100 01 0 to 1000 12 120 to 120 0 to 120 0 to 1000 0 to 100
0.0 to 400.06 0.0 to 300.0#7
Reference Limit
37
37
39
Torque Control
Fieldweakening Control
01 100 to 400
Available for inverters of Spec E or later. 1 : The factory setting is 0 (CT) for inverters of Spec E or later. Only 1 (VT) can be set for 200-V class 110 kW as well as 400-V class 220 kW and 300 kW inverters. 2 : The factory setting depends on inverter capacity. 3 : The setting range depends on inverter capacity. 4 : This value can be monitored or set only when C6-02= 0F and C6-01=1 (VT selection) 5 : The upper limit of the setting range depends on the upper limit set in E1-04. 6 : Factory setting when C6-01=1(VT). When C6-01=0(CT), the factory setting is 0.0 to 150.0. 7 : Factory setting when C6-01=0(CT) with inverters of Spec E or later. When C6-01=1(VT), the factory setting is 0.0 to 400.0.
23
Constants List
Function
Name
Input voltage setting V/f pattern selection Max. output frequency Max. voltage Max. voltage output frequency Mid. output frequency Mid. output frequency voltage Min. output frequency Min. output frequency voltage Mid. output frequency 2 Mid. output frequency voltage 2 Base voltage Motor rated current Motor rated slip Motor no-load current Motor line-to-line resistance Motor leak inductance Motor iron saturation coefficient 1 Motor iron saturation coefficient 2 Motor mechanical loss Motor rated current Motor 2 control method selection Motor 2 max. output frequency Motor 2 max. voltage Motor 2 max. voltage frequency Motor 2 mid. output frequency Motor 2 mid, output frequency voltage Motor 2 min. output frequency Motor 2 min. output frequency voltage Motor 2 rated current Motor 2 rated slip Motor 2 no-load current Motor 2 number of poles Motor 2 line-to-line resistance Motor 2 leak inductance Motor 2 rated capacity
Control Mode Factory Online V/f V/f Open Setting Changing without with Loop Flux PG PG Vector Vector
200 V1 F 60.0 Hz 200.0 V1 60.0 Hz 3.0 Hz2 15.0 V1,2 1.5 Hz2 9.0 V1,2 0.0 Hz3 0.0 V3 0.0 V4 1.90 A7 2.90 Hz7 1.20 A7 4 pole 9.842 7 18.2 7 0.50 0.75 0.0 14 W7 0.4 kW7 0 60.0 Hz 200.0 V1 60.0 Hz 3.0 Hz2 15.0 V1,2 1.5 Hz2 9.0 V1,2 1.90 A7 2.90 Hz7 1.20 A7 4 pole 9.842 7 18.2 7 0.40 kW7 Q Q Q Q Q A A Q A A A A Q A A A A A A A A A A A A A A A A A A Q Q Q Q Q A A Q A A A A Q A A Q A A A A A A A A A A A A A A A A A Q Q Q Q A A Q A A A Q Q A A A A A A A A A A A A A A A A A A A A Q Q Q Q A A A Q Q A A Q A A A A A Q A A A A F F A F A A A A A A A
Ref. Page
1V 1 0.1 Hz 0.1 V 0.1 Hz 0.1 Hz 0.1 V 0.1 Hz 0.1 V 0.1 Hz 0.1 V 0.1 V 0.01 A 0.01 Hz 0.01 A 2 0.001 0.1 0.01 0.01 0.1 1W 0.01 kW 1 0.1 Hz 0.1 V 0.1 Hz 0.1 Hz 0.1 V 0.1 Hz 0.1 V 0.01 A 0.01 Hz 0.01 A 2 0.001 0.1 0.01 kW
0.0 to 255.01
0.0 0.0 0.0 0.0 to to to to 400.05 300.0#6 400.05 300.0#6
V/f Pattern
E1-07 E1-08 E1-09 E1-10 E1-11 E1-12 E1-13 E2-01 E2-02 E2-03 E2-04 E2-05 E2-06 E2-07 E2-08 E2-09# E2-10 E2-11 E3-01 E3-02 E3-03
32 33
0.0 to 255.01
0.0 to 400.05 0.0 to 300.0#6
0.0 to 255.01
0.0 to 400.05 0.0 to 300.0#6
0.0 to 255.01 0.0 to 255.01 0.32 to 6.408 0.00 to 20.00 0.00 to 1.899 0.000 to 65.000 0.0 to 40.0 0.00 to 0.50 0.00 to 0.75 0.0 to 10.0 0.40 to 650.00 0 to 23 #
40.0 to 400.05 40.0 to 300.0#6
31
Motor Setup
0.0 to 255.01
0.0 0.0 0.0 0.0 to to to to 400.05 300.0#6 400.05 300.0#6
0.0 to 255.01
0.0 to 400.05 0.0 to 300.0#6
0.0 to 255.01 0.32 to 6.408 0.00 to 20.00 0.00 to 2 to 48 0.000 to 65.000 0.0 to 40.0 0.40 to 650.00 1.899
Available for inverters of Spec E or later. 1 : Setting for 200 V class inverters. For 400 V class inverters, double the value. 2 : The factory setting depends on the control mode. The factory settings given above are for V/f without PG control. 3 : E1-11 and E1-12 are disregarded when set to 0.0. 4 : E1-13 will have the same value as E1-05 after auto-tuning. 5 : Factory setting when C6-01=1(VT). When C6-01=0(CT), the factory setting is 0.0 to 150.0. 6 : Factory setting when C6-01=0(CT) with inverters of Spec E or later. When C6-01=1(VT), the factory setting is 0.0 to 400.0. 7 : The factory setting depends on the control mode. The value for a 200 V class inverter of 0.4 kW is given. 8 : The setting range is 10 to 200 of the inverter rated output. (The value given is for a 200 V class inverter of 0.4 kW.) 9 : The factory setting depends on inverter capacity. (The value given is for a 200 V class inverter of 0.4 kW.)
24
Function
Name
Factory Setting
600 1 1 3 0 1 0 115 1.0 s 10 0.5 s 0 0 2.0 s 0 0 2 1.00 3 0.5 0.0 0.0 0 0 0 1 2 4 6 37 0F 0F 0 1 0 1 0 0 1 2
Control Mode Online V/f V/f Open Changing without with Loop Flux PG PG Vector Vector
A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
Ref. Page
Operation selection at PG open circuit (PGO) 0 to 3 Operation selection at overspeed Operation selection at deviation PG rotation PG division rate (PG pulse monitor) Overspeed detection level Overspeed detection delay time
Excessive speed deviation detection level 0 to 50 Excessive speed deviation detection delay time 0.0 to 10.0 Number of PG gear teeth 1 Number of PG gear teeth 2 PG open-circuit detection time Bi-polar or uni-polar input selection Digital input option Channel 1 monitor selection Channel 1 gain Channel 2 monitor selection Channel 2 gain Channel 1 output monitor bias Channel 2 output monitor bias Analog output signal level for channel 1 Analog output signal level for channel 2 Channel 1 output selection Channel 2 output selection Channel 3 output selection Channel 4 output selection Channel 5 output selection Channel 6 output selection Channel 7 output selection Channel 8 output selection DO-08 output mode selection Input level of external error from Communications Option Card Stopping method for external error from Communications Option Card Trace sampling from Communications Option Card Torque reference/torque limit selection from optical option Number of SI-T BUS error detection 0 to 1000 0.0 to 10.0 01 0 to 7 1 to 40 0.00 to 2.50 1 to 40 0.00 to 2.50 10.0 to 10.0 10.0 to 10.0 01 01 0 to 37 0 to 37 0 to 37 0 to 37 0 to 37 0 to 37 0 to 37 0 to 37 0 to 2
F2-01# F3-01# F4-01 F4-02 F4-03 F4-04 F4-05 F4-06 F4-07 F4-08 F5-01 F5-02 F5-03
25
Constants List
Function
No. H1-01
Name
Multi-function input (terminal S3) Multi-function input (terminal S4) Multi-function input (terminal S5) Multi-function input (terminal S6) Multi-function input (terminal S7) Multi-function input (terminal S8) Terminal M l-M2 function selection (contact)
Factory Setting
24 14 3 0 1 4 3 1 6 4 1 8 6 1 0 1 2 0 100.0 0.0 0 2 100.0 0.0 2 0 100.0 0.0
0.00 s 0.03 s#
Control Mode Online V/f V/f Open Changing without with Loop Flux PG PG Vector Vector
A A A A A A A A A A A A A A A A A A A A A A A Q A A Q A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A Q A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A Q A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A Q A A A A A A A A A A A A A A A A A Q A A A A
Ref. Page
H1-02 H1-03 H1-04 H1-05 H1-06# H2-01 H2-02 H2-03 H3-01# H3-02 H3-03 H3-04# H3-05#
46 47
Terminal P1 function selection (open collector) 0 to 37 Terminal P2 function selection (open collector) 0 to 37 Signal level selection (terminal A1) Gain (terminal A1) Bias (terminal A1) Signal level selection (terminal A3) Function selection (terminal A3) Gain (terminal A3) Bias (terminal A3) Signal level selection (terminal A2) Function selection (terminal A2) Gain (terminal A2) Bias (terminal A2) Analog input filter time con-stant Terminal A1/A2 switching Analog Monitor selection (terminal FM) Analog Monitor Gain (terminal FM) Analog Monitor Bias (terminal FM) Analog Monitor selection (terminal AM) Analog Monitor Gain (terminal AM) Analog Monitor Bias (terminal AM) Analog output 1 signal level selection Analog output 2 signal level selection Station address Transmission speed selection Transmission parity selection Transmission error detection selection Send wait time RTS control ON/OFF Pulse train input function selection Pulse train input scaling Pulse train input gain Pulse train input bias Pulse train input filter time Pulse train monitor selection Pulse train monitor scaling Motor protection selection Motor protection time constant Motor overheating operation selection 01 0.0 to 1000.0 100.0 to 100.0 01 0 to 1F 0.0 to 1000.0 100.0 to 100.0 0 to 2 0 to 1F 0.0 to 1000.0 100.0 to 100.0 0.00 to 2.00 01 1 to 99 0.00 to 2.50 10.0 to 10.0 1 to 99 0.00 to 2.50 10.0 to 10.0 01 01
2 0 to 20
47
H3-06# H3-07# H3-08 H3-09 H3-10 H3-11 H3-12 H3-13 H4-01 H4-02
38
0 2 1.00 0.0 3 0.50 0.0 0 0 1F 3 0 3 1 5 ms 1 0 1440 Hz 100.0 0.0 0.10 s 2 1440 Hz 1 1.0 min 3 1 0.20 s
43
0 to 4 0 to 2 01 5 to 65 01 0 to 2 1000 to 32000 0.0 to 1000.0 100.0 to 100.0 0.00 to 2.00 1252024 3136 only 0 to 32000 0 to 3 0.1 to 5.0 0 to 2
MEMOBUS Communication
H5-03 H5-04 H5-05 H5-06 H5-07 H6-01 H6-02 H6-03 H6-04 H6-05 H6-06 H6-07 L1-01 L1-02 L1-03 L1-04 L1-05
53
37
Pulse I/O
44
51
Motor Protection
Alarm operation selection during motor overheating 0 to 3 Motor temperature input filter time constant 0.00 to 10.00
Available for inverters of Spec E or later. 1 : Factory setting in the parentheses is for 3-wire sequence. 2 : If the set value is 0, inverter will not respond to MEMOBUS communication.
26
Function
No. L2-01 L2-02 L2-03 L2-04 L2-05 L2-06 L2-07 L2-08 L3-01 L3-02 L3-03
Name
Momentary power loss detection Momentary power loss ridethru time Min. baseblock (BB) time Voltage recovery time Undervoltage (UV) detection level KEB deceleration time Momentary recovery time Frequency reduction gain at KEB start Stall prevention selection during accel Stall prevention level during accel Stall prevention limit during accel Stall prevention selection during decel Stall prevention selection during run Stall prevention level during run Overvoltage inhibit selection Overvoltage inhibit voltage level Frequency detection level Frequency detection width Frequency detection level (/) Frequency detection width (/) Number of auto restart attempts Auto restart operation selection Torque detection selection 1 Torque detection level 1 Torque detection time 1 Torque detection selection 2 Torque detection level 2 Torque detection time 2 Forward torque limit Reverse torque limit Forward regenerative torque limit Reverse regenerative torque limit Integral time setting for torque limit
Factory Setting
0 0.1 s1 0.1 s1 0.3 s 190 V2 0.0 s 0 s3 100 1 120 4 50 1 1 120 4 0 380 V 0.0 Hz 2.0 Hz 0.0 Hz 2.0 Hz 0 0 0 0 150 0.1 s 0 150 0.1 s 200 200 200 200 200 ms 0 0 95 1 3 0 0 1 0 60 s 45 1 1 1 1.00
Control Mode Online V/f V/f Open Changing without with Loop Flux PG PG Vector Vector
A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A Q A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
Ref. Page
39
1 0.1 s 0.1 s 0.1 s 1V 0.1 s 0.1 s 1 1 1 1 1 1 1 1 1V 0.1 Hz 0.1 Hz 0.1 Hz 0.1 Hz 1 1 1 1 1 0.1 s 1 1 0.1 s 1 1 1 1 1 ms 1 1 1 1 1 1 1 1 1s 1 1 1 1 0.01
Stall Prevention
L3-04 L3-05 L3-06 L3-11# L3-12# L4-01 L4-02 L4-03 L4-04 L4-05 L5-01 L5-02 L6-01 L6-02
49
Frequency Detection
0.0 to 20.0
400.0 to 400.07 300.0 to 300.0#8
42
0.0 to 20.0 0 to 10 01 0 to 8 0 to 300 0.0 to 10.0 0 to 8 0 to 300 0.0 to 10.0 0 to 300 0 to 300 0 to 300 0 to 300 5 to 10000
Fault Retry
40
Overtorque Detection
41
Torque Limit
48
Control method selection for torque limit during accel/decel 01 Protect selection for internal DB resistor (Type ERF) Overheat pre-alarm level Operation selection after overheat pre-alarm Input open-phase protection selection Output open-phase protection selection Ground protection selection Cooling fan control selection Cooling fan control delay time Ambient temperature Software CLA selection Hunting-prevention function selection Hunting-prevention gain 01 50 to 130 0 to 3 01 012 # 01 01 0 to 300 45 to 60 01 01 0.00 to 2.50
Hardware Protection
Hunting Prevention
N1-01 N1-02
Available for inverters of Spec E or later. 1 : The factory setting depends on inverter capacity. (The value given is for a 200 V class inverter of 0.4 kW.) 2 : Setting for 200 V class inverters. For 400 V class inverters, double the value. 3 : If the set value is 0, acceleration will be to the speeds for acceleration times (C1-01 to C1-08). 4 : Value when C6-01=1(VT). For inverters of Spec E or later, the factory setting is 150% when C6-01=0(CT). 5 : Factory setting when C6-01=1(VT). When C6-01=0(CT), the factory setting is 0.0 to 150.0. 6 : Factory setting when C6-01=0(CT) with inverters of Spec E or later. When C6-01=1(VT), the factory setting is 0.0 to 400.0. 7 : Factory setting when C6-01=1(VT). When C6-01=0(CT), the factory setting is -150.0 to +150.0. 8 : Factory setting is C6-01=0(CT) for inverters of Spec E or later. When C6-01=1(VT), the factory setting is -400.0 to +400.0.
27
Constants List
39
Function
No.
Name
Speed feedback detection control (AFR) gain Speed feedback detection control (AFR) time constant Speed feedback detection control (AFR) time constant 2
Factory Setting
1.00 50 ms 750 ms 5 150 1.0 s 40 s 02 0.178 s1 1.0 6 1 0 0 3 1 1 0 0 0 0 0 hour 0 0 hour 0 0 0 0 1 2 (V/f, V/f with PG) 0 (Open loop vector)2 Same as inverter rated output 200.0 V7 Value of general motor whose output is same as inverter 60.00 Hz 4 1750 min1 600 1.20A
Control Mode Online V/f V/f Open Changing without with Loop Flux PG PG Vector Vector
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
Ref. Page
N2-01 AFR N2-02 N2-03 N3-01 High Slip Braking N3-02 N3-03 N3-04 Feedforward N5-02# Control N5-03# o1-01 Display Setting/ Selection o1-02 o1-03 o1-04# o1-05# o2-01 o2-02 o2-03 o2-04 Multifunction Selection o2-05 o2-06 o2-07 o2-08 o2-10 o2-12# o2-14# Copy Functions o3-01 o3-02 T1-00 N5-01#
High-slip braking deceleration frequency width 1 to 20 High-slip braking current reference High-slip braking stop dwell time High-slip braking OL time Feedforward control selection Motor acceleration time Feedforward proportional gain Monitor selection Monitor selection after power up 100 to 200 0.0 to 10.0 30 to 1200 0.1 0.001 to 10.000 0.0 to 100.0 4 to 33 1 to 4
34 34
Frequency units of reference setting and monitor 0 to 39999 Setting unit for frequency constants related to V/f characteristics 01 LCD brightness adjustment LOCAL/REMOTE key selection STOP key selection User constant initial value kVA selection 0 to 5 01 01 0 to 2 0 to FF
Frequency reference setting method selection 01 Operation selection when digital operator is disconnected 01 Cumulative operation time setting Cumulative operation time selection Fan operation time setting Fault trace/fault history clear function Output power monitor clear selection Copy function selection Read permitted selection Auto-tuning mode selection1 0 to 65535 01 0 to 65535 01 01 0 to 3 01 12
54
T1-01
0 to 2
T1-02 Motor Autotuning T1-03 T1-04 T1-05 T1-06 T1-07 T1-08# T1-09#
Motor rated voltage3 Motor rated current3, 4 Motor base frequency3 Number of motor poles3, 4 Motor base speed Auto-tuning mode selection3 Number of PG pulses when turning Motor no load current
10 to 200 of inverter rated output5 0 to 255.5 V7 10 to 200 of inverter rated current5 0 to 400.006 2 to 48 0 to 240006 0 to 60000 0.00 to 1.89
A A
A A
A A A A A A
A A A A A A
Available for inverters of Spec E or later. 1 : Not displayed normally. Displayed only when motor switch command is set to the multi-function digital input (either H1-01 to H1-06 is set to 16). 2 : Only 2 (line resistor auto-tuning) is available for V/f with or without PG control. 3 : When using constant output motors, set the base speed value. 4 : Do not fail to verify the rated frequency or voltage by the name plate or test report when using inverter motors or vector motors. If possible, set the no-load voltage to T1-03 and no-load frequency to T1-05 to secure the control accuracy. 5 : The settings that will ensure stable vector control are between 50% and 100% of the inverter rating. 6 : The setting range depends on inverter capacity or setting of C6-01 (CT/VT selection). 7 : Setting for 200 V class inverters. For 400 V class inverters, double the value.
28
Constant Descriptions
The Varispeed F7 provides various functions to upgrade machine functions and performances. Refer to each sample.
Objective Function Settings
Set Environment of Inverter Initialize Constants Set, Reset Password Select Control Method Select Application, Overload Resistance Set Input Voltage Set Motor Rated Current Set V/f (Fixed V/f Pattern) Set V/f (Optional V/f Pattern) Set Accel/Decel Time Select Operation Method Select Operator Key Functions Set Frequency Reference/Monitor Setting Unit Freely Limit the Direction of Rotation Run at Low Speed Multi-Step Speed Selection Use Four Types of Accel/Decel Time Soft Start Limit the Speed Operation to Avoid Resonance Frequency Reference by Pulse Train Input Adjust the Speed Setting Signal
Used Constants
A1-00A1-01 A1-03o2-03 A1-04A1-05 A1-02 C6-01 E1-01 E2-01 E1-03 E1-04 to 13 C1-01 to 08 b1-01b1-02 o2-01o2-02 o1-03 b1-04 d1-17H1-01 to 06 A1-01b1-01b1-02d1-01 to 17 C1-01 to 08C1-10H1-01 to 06 C2-01 to 04 d2-01 to 03 d3-01 to 04 b1-01H6-01H6-02 L2-01L2-02 L4-05 b2-01 to 03H1-01 to 06 L5-01L5-02 H1-01 to 06d4-01 L6-01 to 06 H2-01 to 03L4-01 to 04 C6-02 H4-01H4-04H4-07H4-08 H4-02H4-03H4-05H4-06 H6-06H6-07 b1-03 H1-01 to 06 H2-01 to 03 C4-01 L7-01 to 04 L3-01 to 06 C3-01C5-01 to 04 E2-01L1-01L1-02 H3-02H3-03H3-08 to 11
Ref. Page
30
31 32 33
34
35
36
37 38 39
Automatic Restart after Momentary Power Loss Continue Operation at Constant Speed when Frequency Reference Missing Operate Coasting Motor without Trip Continue Operation by Automatic Fault Reset Temporary Hold of Accel/Decel Torque Detection Frequency Detection Reduce Motor Noise or Leakage Current Use Frequency Meter or Ammeter Calibrate Indications of Frequency Meter or Ammeter Use Pulse Monitor
40 41 42 43 44 45 46 47 48 49 50 51 52 53
3Select Stopping Method 4Build Interface Circuits with External Devices 5Adjust Motor Torque 6Reduce Motor Speed Fluctuation 7Motor Protection 8PID Control 9Control by MEMOBUS Communication 10Energy-saving Control 11Use Constant Copy Function 12Torque Control 13Droop Control 14Zero-servo Function 15Feedforward Control
Select Stopping Method Use Input Signals Use Output Signals Compensate for Torque at Start/Low-speed Operation Limit Motor Torque Prevents Motor from Stalling Control Motor Slip Motor Overload Detection Use Energy-saving Mode Copy or Compare Constants Torque Control (Valid only in flux-vector control) Droop Control (Valid only in flux-vector control) Zero-servo Function (Valid only in flux-vector control) Feedforward Control (Valid only in flux-vector control)
b1-01b5-01 to 10H3-08 b1-01b1-02H5-01 to 07 U1-39 b8-01b8-04 o3-01o3-02 d5-01H3-04H3-05H3-08 H3-09H1-01 to 06 b7-01b7-02 b9-01b9-02H1-01 to 06 H2-01 to 03 N5-01N5-02N5-03
54
55 55 56 56
29
Constant Descriptions
Initialize Constants
Initialize A1-03 User constant initial value o2-03
Initializing indicates that the set value is returned to the factory setting. When replacing the control board, or when returning the
constants to the initial setting for test operation, set A1-03 to the following value to initialize the constant. Initialize to user-defined constants using o2-031110 Initialize to factory-set constants (2-wire sequence)2220 Initialize to factory-set constants (3-wire sequence)3330 Constant o2-03 stores or clears the initial value used for the user constant initialization. By using this constant, the user-set constants can be stored in the inverter as the user initial values.
Setting Value 0 1 2 Description
Memory held/not set Starts memory. (Stores the constants that have been set when o2-03 was set to 1, as user-set initial values.) Clears memory. (Clears stored user-set initial values.)
A1-00 = 0 : English, 1 : Japanese, 2 : German, 3 : French, 4 : Italian, 5 : Spanish, 6 : Portuguese 2Constant access level This inverter classifies the constants reference level according to the significance, as follows. 0For monitoring only (Possible to read in drive mode, set/read A1-01 and A1-04) 1User selected constants only (Possible to set/read only the constants that are set to A2-01 to 32) 2ADVANCED (Possible to set/read the constants that can be changed in the advanced program mode and quick program mode) To switch to the quick program mode, press the and then press the
This inverter selects the control methods according to the machines applied. V/f control is suitable for the fluid machines such as fans, blowers or pumps while current vector control without PG is suitable for machines that require high torque at low speed such as feeding machines. The factory setting is: A1-02 = 0 (V/f control without PG). 0V/f control without PG 1V/f control with PG (Either of the following PG control cards is required.) 2Open loop vector control 3Flux vector control (A PG-B2 or PG-X2 control card is required.) Specifications of PG control cards PG-A2 For single-pulse open collector type PG PG-B2 For 2-phase (A, B) type, complementary type PG PG-D2For single pulse, RS-422 (line driver) PG PG-X2 For 2-phase (A, B) type or RS-422 (line driver) PG with origin point (A, B, Z)
displays A1-04.
30
Select CT/VT according to your application and overload capability. C6-010CT mode (constant-torque load applications, overload capability 150 for one minute) C6-011VT mode (variable torque load applications, overload capability 120 for one minute) The inverter overload capability and carrier frequency setting ranges depend on the setting of C6-01.
C6-01 Set Value Application Inverter Specifications
Overload Maximum Carrier Frequency Resistance Current
200 V Class
Inverter Model 20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 CIMR-F7A = Maximum Applicable Motor Output kW Inverter Rated Output Current A
0.4 3.2 0.75 4.1 3.3 1.5 7.0 6.2 2.2 9.6 8.5 3.7 15.0 14.0 5.5 23.0 19.6 7.5 31.0 26.6 11 45.0 39.7 15 58.0
150
Low carrier frequency 2 kHz (selected by C6-02) High carrier frequency 2 to 15 kHz (selected by C6-02)
Variable torque load 1 120 for applications (fans, 1 min. VT Mode pumps)
120
2 For the factory setting of inverters with Spec E or later, constant C6-01 is set to zero (0) for CT mode. For 200-V-class 110 kW and 400-V-class 220 kW to 300 kW inverters, however, C6-01 can only be set to one (1) for VT mode.
Inverter Model 2018 2022 2030 2037 2045 2055 2075 2090 2110 CIMR-F7A = Maximum Applicable 18.5 Motor Output kW Inverter Rated 71.0 Output Current A
22 30 37 45 55 75 90 110
85.0 115.0 145.0 180.0 215.0 283.0 346.0 415.0 77.2 105.0 131.0 160.0 190.0 260.0 260.0 260.0
400 V Class
Inverter Model 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 CIMR-F7A = Maximum Applicable 0.4 0.75 1.5 2.2 3.7 5.5 7.5 Motor Output kW
11 15 18.5 22 30
Set the inverter input voltage value. This value will be the reference value for the protective functions. 200 V classsetting range 155 to 255 V (Factory setting : 200 V) 400 V classsetting range 310 to 510 V (Factory setting : 400 V)
Inverter Rated 1.8 2.1 3.7 5.3 7.6 12.5 17.0 24.0 31.0 39.0 45.0 60.0 Output Current A Motor Current A 1.0 1.6 3.1 4.2 7.0 9.8 13.3 19.9 26.5 32.9 38.6 52.3 Factory Setting Inverter Model 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300 CIMR-F7A = Maximum Applicable 37 Motor Output kW
45 55 75 90 110 132 160 185 220 300
Inverter Rated 75.0 91.0 112.0 150.0 180.0 216.0 260.0 304.0 370.0 506.0 675.0 Output Current A Motor Current A 65.6 79.7 95.0 130.0 156.0 190.0 223.0 270.0 310.0 370.0 500.0 Factory Setting
31
Constant Descriptions
Notes: 1 When VT is selected for the constant-torque load applications (generalpurpose machines), the inverter service lifetime will be remarkably deteriorated. Be sure to select CT or VT suitable for the load application. 200 V class 110 kW and 400 V class 220 to 300 kW inverters can set only C6-01 = 1 (VT mode).
53.0
E1-03
Application
Specification
Medium starting torque 50 Hz High starting torque Medium starting torque 60 Hz High starting torque
E1-03
8
3
V/f Pattern1
50 Hz
9
Hz
Hz
60 Hz saturation 60 Hz 50 Hz saturation
1 F
A
3
2
Hz
B
Hz
72 Hz
90 Hz
C
3
Hz
Hz
120 Hz
D
3
Hz
Hz
180 Hz
7
3
Hz
E
3
Hz
1 : Consider the following items as the conditions for selecting a V/f pattern. They must be suitable for: (1) The motor voltage and frequency characteristics. (2) The maximum rotational speed of motor. 2 : Select high starting torque only in the following conditions. Normally, this selection is not required since sufficient starting torque is secured by full-automatic torque boost function. (1) The wiring distance is long (approx. 150 m or more). (2) The voltage drop at startup is large. (3) AC reactor is inserted in the input or output of the inverter. (4) A motor smaller than the nominal output of the inverter is used. 3 : The V/f characteristics (A)/(B) value is A : 1.5 kW or less, B : 55 kW or more.
32
, Cont d
Constant No.
Name
Unit
Setting Range
Factory Setting
60.0 Hz2 200.0 V1, 2 60.0 Hz2 3.0 Hz2 15.0 V12 1.5 Hz2 9.0 V12 0.0 Hz3 0.0 V3 0.0 V4
E1-08 Mid. output frequency voltage 0.1 V 0.0-255.0 V1 E1-09 Min. output frequency
0.1 Hz 0.0-300.0 Hz5 V1
E1-11 Mid. output frequency 23 0.1 Hz 0.0-300.0 Hz5 E1-12 Mid. output frequency voltage 23 0.1 V 0.0-255.0 V1 E1-13 Base voltage4
0.1 V 0.0-255.0 V1
Set the following when using special motor (high-speed motor, etc.), or when the torque of the machine is especially required. The motor torque increases by increasing the V/f pattern voltage, but, too high voltage can cause the following failure. Excessive current flows into the motor to cause failure of the inverter. Increase the voltage gradually, while checking the motor current.
VoltageV
E1-05 E1-12 E1-13 3 4
1 : The value doubles for 400 V class. 2 : The factory setting differs according to the control method. The setting of this table is for V/f control without PG. 3 : When 0.0 is set, the setting in E1-11, -12 is disregarded. 4 : When 0.0 is set, E1-13 = E1-05. 5 : When 1 is set to C6-01 (VT mode), the upper limit value of the setting will be 400.0 Hz.
E1-08
and the time from when the motor runs at the maximum output frequency to when it stops (or deceleration time). : Factory setting: Acceleration time C1-01 = 10.0 s
E1-09 E1-07 E1-06 E1-11 E1-04 3 FrequencyHz
E1-10
Set E1-04 to 11 so that E1-04E1-11E1-06E1-07E1-09. To make the line of the V/f characteristics straight, set E1-07 and E1-09 to the same value. At this time, the set value of E1-08 is disregarded. E1-11, 12 and 13 must be set only at V/f minute adjustment in the constant output area. Normally, they do not have to be set.
33
Constant Descriptions
Functions aW
o2-01 o2-02
o2-010LOCAL/REMOTE changeover disabled 1LOCAL/REMOTE changeover enabled o2-020Operator STOP key disabled during control circuit terminal operation (b1-02=1) 1Operator STOP key always enabled during control circuit terminal operation (b1-02=1)
Set Value 0 1 2 3
d1-01 to 17: Set in the units of 0.01 Hz d1-01 to 17: Set in the units of 0.01 (maximum output frequency: 100 ) Set in the units of min-1. min-1 = 120frequency reference (Hz) / o1-03 (o1-03 sets the number of motor poles.) Set the number of displayed digits below the decimal point with the value in the fifth digit of o1-03. 5th digit value = 0 : Displayed as 5th digit value = 1 : Displayed as . 5th digit value = 2 : Displayed as .
1By setting b1-01 to 0, frequency reference can be input from the digital operator. 2By setting b1-01 to 1, frequency reference can be input from control circuit terminal A1 (voltage input) or control circuit terminal A2 (voltage/current input).
Note: To input a current signal (4 to 20 mA) to terminal A2, turn ON 2 of dip switch S1 (factory setting: ON). Then set H3-08 to 2 (factory setting: 2). To input a voltage signal (0 to 10 V) to terminal A2, turn OFF 2 of dip switch S1. Finally, set H3-08 to 0 or 1.
40 to 39999
5th digit value = 3 : Displayed as . The set value of 100 frequency is specified with the first to fourth digits of o1-03. (Example) 1 Set o1-03 to 12000 when the set value of 100 speed is 200.0. 2 Set o1-03 to 26500 when the set value of 100 speed is 65.00.
3By setting b1-01 to 2, frequency reference can be input from the master controller at MEMOBUS communications. 4By setting b1-01 to 4, the pulse train input which is input to control circuit terminal RP becomes the frequency reference.
o1-03 0 1 2 to 39
d1-01 to 17 : Displayed in the units of 0.01 Hz. d1-01 to 17 : Displayed in the units of 0.01 . Set in the units of min-1. min-1 = 120frequency reference (Hz) / o1-03 (o1-03 sets the number of motor poles.) Displayed with numerical value and accuracy specified by the set value of o1-03. (Example) 1 100 speed and 60 speed are displayed as 200.0 and 120.0, respectively when o1-03 is set to 12000. 2 60 speed is displayed as 39.00 when o1-03 is set to 26500.
40 to 39999
34
Description
Reverse run enabled Reverse run disabled
Note: When an inverter forward run command is given, the motor output shaft rotates in the counterclockwise (CCW) direction viewed from the motor at the load side (output shaft side).
Set Jog frequency in Multi-function contact input terminals S3 to S8. Next, input the Jog frequency reference and the forward (reverse) run command. Jogging can be performed with the jogging frequency set in d1-17. When multi-speed reference 1 to 4 is set along with Jog reference, the Jog reference has priority.
Name Jog reference Constant No.
d1-17
Name
Multi-step speed reference 1 Multi-step speed reference 2 Multi-step speed reference 3 Jog reference selection
Setting Value
(Factory setting: 6.0 Hz) Set 6 in one of the terminals (JOG frequency selection).
S5 S6 S7 S8
3 4 6 8
3 4 5 6
The same operation can be also accomplished by the digital operator. Press the
a key, and check that the remote LED a again to turn the light OFF. l key on the digital operator for jogging,
(SEQ. REF) is OFF. When the remote LED (SEQ. REF) is ON, press the key Press the
Preset Preset Reference 8 Reference 7 d1-08 Preset Reference 6 d1-07 Preset Reference 5 d1-06 Preset Preset2 Frequency Reference 2 Preset Reference 4 d1-05 Reference Reference 3 d1-04 Preset1 d1-03 Jog Frequency Reference 1 d1-02 d1-17 d1-01 Time Terminal Closed Forward Run Open Command S1 Closed Multi-step Speed Open Ref. 1 S5 Main/Auxiliary Closed Switch Open Multi-step Speed Ref. 2 S6 Closed Open Jog Command Selection S7 Closed Open Multi-step Speed Ref. 3 S8
1When the preset reference 1 is b1-01= 0, constant setting value (d1-01) is applied; when b1-01 = 1, the analog command set by control circuit terminal A1 is applied. 2When the preset reference 2 is H3-09 = 2, the analog frequency reference input through terminal A2 is applied; when the setting is H3-09 = 1F, constant setting value (d1-02) is applied. 3When the preset reference 3 is H3-05 = 3, the analog frequency reference input through terminal A3 is applied; when the setting is H3-05 = 0, constant setting value (d1-03) is applied.
35
Constant Descriptions
By combining 16-step frequency references, one jog frequency reference and multi-function terminal function selection, up to 17 steps of speed variations can be set step by step. (The following shows an example of 9-step speed.) Operation method selection: b1-01=0, b1-02=1 Constant access level: Advanced program The range where multi-step speed frequency reference can be set or read depends on the program mode as follows: QUICK : Up to 5 steps of speed variations can be set or read. d1-01, 02, 03, 04, 17 ADVANCED: Up to 17 steps of speed variations can be set or read. d1-01 to 17 Multi-function input terminals S5 (function selection) H1-03 S6 H1-04 S7 H1-05 S8 H1-06 Frequency reference 1 to 8 d1-01 to 08 Jog frequency reference d1-17
Soft Start
S-curve characteristic time C2-01 to 04
Accel/decel by S-curve pattern can be accomplished to prevent shock at start, or stop of the machine.
Constant No. Function
S-curve characteristic time at acceleration start S-curve characteristic time at acceleration end S-curve characteristic time at deceleration start S-curve characteristic time at deceleration end
Setting Range
0.00 to 2.50 s 0.00 to 2.50 s 0.00 to 2.50 s 0.00 to 2.50 s
Factory Setting
0.20 s 0.20 s 0.20 s 0.00 s
C2-01 C2-02
Time
C2-03 C2-04
ON
OFF
ON
Note: S-curve characteristic time is the time required for the 0 accel/decel rate to reach the formal accel/decel rate determined by the preset accel/decel time.
ON Accel/Decel Time Switch (one of terminals S3 to S7)
Set 07 or 1A (accel/decel time switch 1 or 2) in multi-function input (H1-01 to H1-06), to allow selection of 4 sets of accel/decel times by the ON/OFF of the accel/decel time switch (one of terminals S3 to S8).
Accel/decel Time Selection 1 Accel/decel Time Selection 2 Accel Time Decel Time Multi-function Input Multi-function Input Setting = 07 Setting = 1A
Open or not set Closed Open or not set Closed Open or not set Open or not set Closed Closed C1-01 C1-03 C1-05 C1-07 C1-02 C1-04 C1-06 C1-08
S-curve Characteristic Time (Tsc) Output Frequency Time
Setting the S-curve characteristic time, the acceleration or deceleration time will be longer by 1/2 of the S-curve characteristic time at start or end.
Forward Run Command Reverse Run Command Acceleration C2-01 C2-02
Constant No.
Name
Unit
C1-01 Accel time 1 C1-02 Decel time 1 C1-03 Accel time 2 C1-04 Decel time 2 C1-05 Accel time 3 C1-06 Decel time 3 C1-07 Accel time 4 C1-08 Decel time 4
0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s 0.1 s 0.0 to (1s for 1000s or more) 6000.0 s
Deceleration DC Braking Time at Stop C2-03 Min. Output Frequency b2-04 C2-04 E1-09 Output Frequency C2-01 Minimum Output Frequency C2-04 E1-09 Acceleration Deceleration Characteristics in C2-02 C2-03
Time Chart when Switching Forward Run and Reverse Run at Deceleration to Stop (V/f control mode example)
C1-10 = 0 : Units of 0.01 sec. (Max. 600.00 seconds) C1-10 = 1 : Units of 0.1 sec. (Max. 6000.00 seconds)
36
d3-01
d3-02 d3-04
At Frequency Reference Upper Limit
d3-03
1Limiting maximum frequency Use d2-01 when the motor is to be rotated at certain min-1 or less. Set the frequency reference upper limit value (d2-01) in the units of 0.1 . (E1-04 maximum output frequency is 100%.) : Factory setting: d2-01 = 100 2Limiting minimum frequency Use d2-02 or d2-03 when the motor is to be rotated at certain min-1 or more. There are two methods to limit the minimum frequency as follows: Adjust the lower limit levels of all frequencies (d2-02) Adjust the lower limit level of the master speed frequency (d2-03) The lower limit levels of the jog frequency, multistep speed frequencies or auxiliary frequency are not adjusted. When running at frequency reference 0, operation continues at the lower limit value of the frequency reference. However, operation is not performed if the frequency lower limit value is set to less than the minimum output frequency (E1-09). : Factory setting: d2-02 = 0.0 , d2-03 = 0.0
d3-04
d3-04
By setting reference selection b1-01 to 4, frequency reference can be set by pulse train input from the control circuit terminal RP. 1Input pulse specifications Low level voltage High level voltage H duty Pulse frequency 0.0 to 0.8 V 3.5 to 13.2 V 30 to 70 0 to 32 kHz
2How to give frequency reference The value obtained by multiplying the maximum output frequency by the ratio of the set maximum value of input pulse frequency and the actual input pulse frequency makes reference frequency. Frequency Maximum output Input pulse frequency reference Pulse train maximum frequency (H6-02) frequency (E1-04)
Constant No. b1-01 H6-01 H6-02 Name
Reference selection Pulse train input function selection Pulse train input scaling
37
Constant Descriptions
, Cont d
Frequency Selects 0 to 10V, 0 to10V or 4 to 20mA input. 0 to10V input reference level selection reverses with negative input. Frequency % gain Reference % bias
Sets the ratio () against the Maximum frequency (E1-04) of the virtual output frequency when terminal input is 10 V (20 mA). Sets the ratio () against the Maximum frequency (E1-04) of the output frequency when terminal input is 0 V (4 mA).
50
0 : 0 to 10V H3-01, 04 1 : 10 to 10V 0 2 : 4 to 20mA H3-082 0.0 to 1000.0 100.0 to 100.0 100.0 0.0
0 1V 25 5V 10 V Terminal Input
38
L2-01 L2-02
Description
Operation not continued (Factory setting) Operation continues after power recovery within momentary power loss ridethru time (L2-02). Operation continues after power recovery (no fault signal). (However, restarts only within the time established by the control power.)
2 2
1 : Hold the run command to continue the operation after recovery from momentary power loss. 2 : When 2 is selected, the operation restarts if power supply voltage reaches its normal level. No fault signal is indicated.
Momentary power loss ridethru time Set L2-02 to the ridethru time when L2-01 is set to 1. The initial values depend on the inverter capacities as follows.
Inverter Model CIMR-F7A _ 20P4 to 2011 2015 to 2110 40P4 to 4011 4015 to 4300 L2-02 Initial Value
0.1 to 1.0 s 2.0 s 0.1 to 1.0 s 2.0 s
is input at the same time or after the search reference. reference is disabled.
Forward (Reverse) Run Command Speed Search Reference Frequency Reference When Max. Output Frequency or Operation Command is Input Output Frequency
ON ON
0.5 s or more
2DC injection braking at start This function is used to restart the motor after applying DC injection braking current to the coasting motor. The time for direct current injection braking at start can be set unit of 0.1 sec in b2-03. The DC injection braking is set in b2-02. When setting of b2-03 is 0, direct current injection braking is not performed, and acceleration is performed from the minimum frequency.
39
If a failure occurs in the inverter, the inverter performs selfdiagnosis and automatically restarts operation. The self-diagnosis and restart count can be set in constant L5-01 (up to 10 times). Fault retry signal can be set to be output (L5-02 : 1) or no output (L5-02 : 0). The following faults are dealt with by this function. OCovercurrent PUFfuse blown GFground fault OVDC main circuit overvoltage RHbraking resistor overheat RRbraking transistor failure
LFoutput open-phasePFmain circuit voltage fault OL1motor overload OL2inverter overload OL3overtorque OL4overtorque OH1heatsink overheating main circuit undervoltage, main circuit MC malfunction UV1
: Retry enabled when main circuit undervoltage (L2-01) is set to 1 or 2 (operation continues after power recovery).
The accumulated error retry count is cleared in the following cases. When no error occurred for 10 minutes after retry When error set signal is input after defining the error When power is turned OFF If any fault other than the above faults occurs, a fault contact output operates to shut off the output and the motor coasts to a stop. Note: Do not use this function for any lifting loads.
OFF OFF ON
Frequency Reference
Output Frequency
40
, Cont d
Torque Detection
Torque detection selection 1, 2 L6-01L6-04 Torque detection level 1, 2 L6-02L6-05 Torque detection time 1, 2 L6-03L6-06
If excessive load is applied on the machine, alarm signals are output to the multi-function terminals M1-M2, P1-PC and P2-PC. The Varispeed F7 has two kinds of overtorque/ undertorque detection. Overtorque/undertorque detection signal is activated by setting torque detection selection 1 (NO contact: 0B, NC contact: 17) or torque detection selection 2 (NO contact: 18, NC contact: 19) in output terminal function selection H2-01, H2-02 or H2-03. Torque detection level is the current level (inverter rated output current 100 ) at V/f control and the motor torque level (motor rated torque 100 ) at vector control. 4Detection of overtorque To detect overtorque, select 1, 2, 3 or 4 for the set value of L6-01 or L6-04. L6-02 or L6-05 becomes the overtorque detection level.
Motor Current Overtoruque Detection Level (L6-02, L6-05) Time Multi-function Output Signal (Overtorque Detection ON Signal) Terminal M1-M2, P1-PC, P2-PC Overtorque Detection Time L6-03L6-06
Setting for Overtorque/Undertorque Detection Function Constant No. L6-01 L6-02 L6-03 L6-04 L6-05 L6-06 Function
Torque detection 1 selection Torque detection 1 level Torque detection 1 time Torque detection 2 selection Torque detection 2 level Torque detection 2 time
Setting Range
0 to 8 0 to 300 0.0 to 10.0 s 0 to 8 0 to 300 0.0 to 10.0 s
Factory Setting
0 150 0.1 s 0 150 0.1 s
Setting Values of L6-01 and L6-04 The following table shows relations between setting values of L6-01 or L6-04 and alarms at overtorque/undertorque detection.
Constant Descriptions Setting Value 0 1 2 3 Function
Overtorque/undertorque detection disabled Overtorque detection only during speed agree/operation continued after detection (warning) Overtorque detection at any time during operation/operation continued after detection (warning) Overtorque detection only during speed agree/output shut off at detection (protective operation) Overtorque detection at any time during operation/output shut off at detection (protective operation) Undertorque detection only during speed agree/operation continued after detection (warning) Undertorque detection at any time during operation/operation continued after detection (warning) Undertorque detection only during speed agree/output shut off at detection (protective operation) Undertorque detection at any time during operation/output shut off at detection (protective operation)
ON
4 5 6 7 8
: The releasing width of overtorque detection is approx. 10 of the inverter rated current (or motor rated torque).
4Detection of undertorque To detect undertorque, select 5, 6, 7 or 8 for the set value of L6-01 or L6-04. L6-02 or L6-05 becomes the undertorque detection level.
Motor Current Undertorque Detection Level (L6-02, L6-05) Time Multi-function Output Signal (Undertorque Detection Signal) ON Terminal M1-M2, P1-PC, P2-PC Undertorque Detection Time (L6-03, L6-06)
ON
: The releasing width of undertorque detection is approx. 10 of the inverter rated current (or motor rated torque).
41
Description
Zero-speed Frequency (speed) agree 1
Optional frequency (speed) agree 1 L4-01 Optional frequency (speed) agree without detection 1 (Less than preset value) Optional frequency (speed) agree sign detection 1 (More than preset value) Frequency (speed) agree 2 Optional frequency (speed) agree 2 L4-03 Optional frequency (speed) agree detection 2 (Less than preset value) with sign Optional frequency (speed) agree detection 2 (More than preset value)
L4-04
Fref/Fout Agree 2 OFF ON
L4-04
As shown above, select the detection with or without sign in the Varispeed F7. The following is the frequency (speed) agree timing chart. The figure shows the case of forward rotation; the direction for reverse rotation without sign is the same. When detection with sign is selected, detection signal against the specified direction of rotation is detected according to the direction of rotation. 1Setting Value02Fref/Fout Agree 1
Frequency reference Output frequency or motor speed L4-02 L4-02 Fref/Set Agree 2 OFF ON Output frequency or motor speed
Fref/Fout Agree 1
OFF
Freq. Detection 4
OFF
ON
42
If the wiring between the inverter and the motor is excessively long, the inverter output current will be increased because of the increased leakage current of harmonics from the cable, which may affect the peripheral devices. Refer to the following table to adjust the inverter output transistor switching frequency (carrier frequency). Reducing such carrier frequency is effective for reduction of radio noise.
Wiring Distance between 50 m or less 100 m or less More than 100 m Inverter and Motor Carrier Frequency C6-02 Value
FM AM
AM
FM
Note: The setting range of C6-02 depends on the value of C6-01 (CT/VT selection).
Carrier Frequency Metallic Noise Noise and C6-01 C6-02 (kHz) from Motor Leakage Current Setting Value Setting Value
0 1 (VT selection) 1 to 6 0 (CT selection) 0 1 15.0 (Low carrier frequency) 2.0 Small Small Large More Less Less (Low carrier frequency) 2.0 Small Large Less Less
Constant No.
Name
Monitor selection (terminal FM)
Description
Set the number of the monitor item to be output from terminal FM or AM. (Number in the part == of U1-==.) The monitor items that can be set depends on the control method. 4, 10 to 14, 25, 28 to 31, 34, 35, 39 to 43 cannot be set. Set the signal level of terminal FM or AM. 0 : 0 to 10 V output 1 : 0 to 10 V output
H4-01
H4-04
H4-07
Signal level selection (terminal FM) Signal level selection (terminal AM)
H4-08
43
Constant Descriptions
Outputs the monitor items [U1-== (status monitor)] of the Used when analog output terminals FM-AC and AM-AC output voltage with gain and bias. For gain, set how many times of 10V the monitor item 100 output is to be made. Set the bias in the units of assuming that the amount to move the output characteristics upward and downward in parallel is to be 10 V/100 .
Analog Output Voltage Gain10 V
digital operator from pulse monitor terminals MP-SC. Set H6-06 to the numerical value in == of U1-== (status monitor). (Only the following 6 items can be output.)
H6-06 Setting Value 1 2 5 20 24 36 Output Item
Frequency reference (U1-01) Output frequency (U1-02) Motor speed (U1-05) Output frequency after soft-start (U1-20) PID feedback (U1-24) PID input (U1-36)
10 V
number of pulses to be output in the units of Hz. To use the pulse monitor, connect the peripheral devices according to the following load conditions. If any of the following load conditions is not met, sufficient characteristics may not be obtained or the devices may be damaged. Used as source output
Output Voltage (Insulation Type) Load Impedance (k) VRL V 5 V or more 8 V or more
1.5 k or more 3.5 k or more 10 k or more
AM FM
Analog Output Voltage 10 V Factory Setting H4-021.0H4-030 Factory Setting H4-050.5H4-060 Example H4-02 = 0.3 of H4-05 = 0.3
10 V or more
Inverter MP
5V
VRL
3V
Load Impedance
AC
For frequency meter that displays 0 to 60 Hz at 0 to 3 V 10 V H4 - 02 0.3 3 V This is the voltage when the output frequency is 100 .
Note: Set 1.00 when using a 10 V full-scale meter.
Inverter MP
Load Impedance
AC
Sink Current
44
, Cont d
By setting b1-03 to 2, the inverter stops by applying DC injection braking when L2-03 (minimum baseblock time) elapses after turning OFF the run command. To stop the inverter when a stop command is given, select one of the following four methods according to the application.
Setting 0 1 2 3 Stopping Method
Deceleration stop Coasting to stop Entire area DC injection braking at stop Coasting to stop with timer
Inverter Output DC Injection Shut OFF Braking Time Forward (Reverse) Run Command Output Frequency Min. Baseblock Time (L2-03) ON OFF
1Deceleration stop By setting b1-03 to 0, the motor decelerates to stop according to the selected deceleration time. When output frequency is less than b2-01 at deceleration to a stop, DC injection braking is applied for the time set to b2-04.
Output Acceleration Time 1 Deceleration Time 1 Frequency (C1-01) (C1-02) Deceleration Time 1 (C1-02) Min. Output Frequency (Frequency at DC Injection Braking Start) b2-01 (Factory Setting: 0.5 Hz) Time Forward (Reverse) Run Command ON DC Injection Braking Time to Stop (b2-04) (Factory Setting: 0.5 s)
The DC injection braking time is as follows, according to the output frequency when stop command is input.
b2-0410
4Coasting to stop with timer By setting b1-03 to 3, the inverter output voltage is shut off at the same time as run command OFF and the motor coasts to a stop. At this time, the run command is disregarded until operation waiting time T elapses.
2Coasting to stop By setting b1-03 to 1, the inverter output voltage is shut off at the same time as run command OFF. The motor coasts to a stop in the deceleration ratio suitable for the inertia and machine loss including the load. Restart is accepted immediately after the run command is turned OFF, but restart command during rotation of the motor may cause alarms for OV or OC.
Output Frequency Acceleration Time 1 Deceleration Time 1
(C1-01) (C1-02)
Output Frequency Deceleration Time 1 (C1-02) Acceleration Time 1 (C1-01) Time Forward (Reverse) ON Run Command ON ON
Coasting
Operation waiting time T is as follows according to the output frequency and deceleration time at run command OFF.
Operation Waiting Time T Deceleration Time
45
Constant Descriptions
Functions of the multi-function input terminals S3 to S8 can be changed as necessary by setting constants H1-01 to H1-06. The same values cannot be set in each constant. Function of terminal S3 : Set in H1-01. Function of terminal S4 : Set in H1-02. Function of terminal S5 : Set in H1-03. Function of terminal S6 : Set in H1-04. Function of terminal S7 : Set in H1-05. Function of terminal S8 : Set in H1-06. Select the function of the input signal by control circuit terminals S3 to S8.
Setting 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 20 to 2F 30 31 32 34 35 60 61 62 63 64 65 66 67 68 71 72 77 78 Function
3-wire control, forward/reverse selection Local/remote selection Option/inverter selection Multi-step reference 1 Multi-step reference 2 Multi-step reference 3 Jog frequency reference Accel/decel time selection 1 External baseblock N.O. External baseblock N.C. Accel/decel stop hold Overheat 2 alarm signal Multi-function analog input selection No speed V/f control with PG ASR integral reset Terminal not used UP command DOWN command Forward jog Reverse jog Fault reset Emergency stop (NO contact) Motor changeover Emergency stop (NC contact) Timer function input PID disable Accel/decel time selection 2 Program enable speed frequency speed frequency Analog frequency reference sample/hold External fault (can be set freely) PID integral reset PID integral hold Multi-step speed reference 4 PID SFS ON/OFF PID input characteristics changeover DC injection activate External search command 1 : maximum output frequency External search command 2 : frequency reference Magnetic field weakening command External search command 3 KEB (deceleration at momentary power loss) command (NC contact) KEB (deceleration at momentary power loss) command (NO contact) Communication test mode HSB (high-slip braking) Speed/torque control change (ON: torque control) Zero-servo command (ON: zero-servo) ASR proportional gain switch (ON: C5-03) Polarity reversing command for external torque reference
Run Command (Operates at Closed) Stop Command (Stops at Open.) Forward/Reverse Selection (Forward at Open, Reverse at Closed)
Note: To set the 3-wire sequence, follow these procedures. Set the parameter for the multi-function input terminal and wire the control circuit. Set terminal S3 (H1-01) to 0.
Control Mode V/f V/f Open- Flux without with loop Vector PG PG Vector
2Local (digital operator)/Remote (control circuit terminal) selection (setting: 01) Select digital operator or control circuit terminal to operate. Local/remote can be switched only while the motor is held. Open Operates according to the setting of REMOTE operation mode (b1-01, b1-02). ClosedOperates in LOCAL mode by the frequency reference, run command from the digital operator. ExampleIt can be switched between the digital operator and control circuit terminal by setting b1-01 = 1 or b1-02 = 1 Open Can accept frequency reference (terminal A1), run command (terminals S1, S2) from control circuit terminal. ClosedCan accept frequency reference, run command from digital operator. 3UP/DOWN command (setting: 10, 11) Accel/decel to the desired speed can be accomplished while the forward (reverse) run command is enabled, without changing the frequency reference, by inputting the UP/DOWN by remote signal.
UP Command DOWN Command Operation
Forward Run UP Command DOWN Command
46
, Cont d Symbols U UP (acceleration) status D DOWN (deceleration) status H HOLD (constant speed) status U1UP status, but clamped at upper speed limit D1DOWN status, but clamped at lower speed limit
Notes: 1. When using the UP/DOWN command, always set b1-01 at (frequency reference). Setting value = 1 : enables the UP/DOWN command. Setting value = other than 1 : disables the UP/DOWN command. 2. The upper speed limit is: Max. output frequency (E1-04) frequency reference upper limit (d2-01). 3. The lower speed limit is: Max. output frequencyfrequency reference lower limit (d2-02) and the largest of main frequency references inputs via the control circuit terminal A1. 4. When frequency reference command storage function is provided (d4-01 = 1), the output frequency is stored even after the power is turned OFF with the accel/decel hold (HOLD) command input. 5. When JOG command is input during operation by UP/DOWN command, JOG command is prioritized. 6. Setting error (OPE03) occurs if the UP/DOWN command is not set at the same time. 7. Setting error (OPE03) occurs if multi-function input accel/decel hold (HOLD) command is set at the same time.
Control Mode V/f V/f Open- Flux without with loop Vector PG PG Vector
The external inverter timer can be combined with the timer input (setting = 18) and the multi-function output terminal timer output (setting = 12), to set the internal inverter timer. Set the ON side delay time in 0.1-second unit. Set the OFF side delay time in 0.1-second unit.
Closed Timer Input b4-01 Timer Output b4-01 b4-02 Closed b4-02 Closed
Operation When the timer input closed time is shorter than b4-01, the timer output stays open. When the timer input becomes closed, the timer output closes after the time set in b4-01. When the timer input open time is shorter than b4-02, the timer output stays closed. When the timer input becomes open, the timer output closes after the time set in b4-02.
Frequency Reference
47
Constant Descriptions
Torque compensation is a function to detect the increase of the motor load and increase output torque. If control method selection (A1-02) is set to 0 (V/f control without PG) or 1 (V/f control with PG), this function compensates for insufficient torque at start or low-speed operation using the entire area full-automatic torque boost function according to output voltage. When control method selection (A1-02) is set to 2 (openloop vector control), motor torque is automatically controlled according to the load by calculating motor primary current to compensate for undertorque. Automatic torque offset gain normally does not need adjustment. The factory setting is C4-01 = 1.0 Make necessary adjustments when the wiring distance between the inverter and motor is long, or when the motor vibrates excessively. The motor torque can be increased by increasing the torque offset gain, but may also cause the following failures. Excessive motor current may cause failure of the inverter. The motor may heat or vibrate excessively. Increase the torque offset gain little by little, while observing the motor current.
The motor torque limit function is enabled only at vector control. Since torque that is output from the motor is calculated internally in the vector control mode, torque limit can be applied with any value. This function is effective when torque exceeding a certain amount is not to be applied to the load or when the regenerative value is not to be generated at a certain amount or more. Set the torque limit value in the for the motor rated torque. It can be set individually in each quadrant.
Torque Reference Positive Forward Torque Limit L7-01 Reverse Regenerative Torque Limit L7-04 Motor Rotation Forward
Reverse
Forward Regenerative Torque Limit L7-03 Reverse Torque Limit L7-02 Negative
Notes:Since torque control has a priority when the torque limit function operates, the motor revolution control or compensation will be disabled. Therefore, accel/decel time may increase or the motor revolutions may reduce. Notes:When torque limit is used for lifting load applications, set such a torque limit value that the load may not drop or slip. Notes:To increase the torque limit value, the inverter capacity may have to be increased.
48
2Stall prevention during run A function to prevent the motor from stalling reducing inverter output frequency automatically when a transient overload occurs while the motor is running at a constant speed. By setting L3-05 to 1 or 2, the stall prevention during running is enabled only in the V/f control mode. Deceleration starts when inverter output current exceeds 150 (L3-06 set value) of inverter rated current during constant speed operation. While output current exceeds 150 (L3-06 set value), the motor continues decelerating in the set deceleration time. When inverter output current is 148 (L3-06 set value - 2 ) or less, the motor accelerates up to the set frequency in the set acceleration time.
Motor Current 150% of L3-06 Inverter Rated Current
1 : Frequency is reduced to prevent stalling in the meantime. 2 : Unless output current is less than the set level, output frequency is held at the minimum value. Factory setting is 150 . By setting L3-05 to 0, the stall prevention during running will be disabled.
Time
: Output frequency is controlled so that stall status may not be caused in the meantime. Factory setting of L3-02 is 150 . By setting L3-01 to 0, the stall prevention during acceleration will be disabled.
3Stall prevention during deceleration A function to extend the deceleration time automatically according to the size of main circuit DC voltage so that overvoltage may not occur during deceleration. When a braking resistor (optional) is used, be sure to set L3-04 to 0 or 3. The following shows an example of the stall prevention during deceleration when 1 is set to L3-04.
Output Frequency Control Deceleration Time to Prevent Overvoltage When Stall Prevention during Deceleration Operates
Stall prevention level during acceleration is automatically reduced by the following equation in the constant output area (output frequency max. voltage frequency E1-06). Stall prevention level during acceleration in constant output area Max. voltage frequency (E1-06) Stall prevention level during accel (L3-02) Output frequency However, in order to avoid this stall prevention level in the constant output area from being reduced more than necessary, use L3-03 to set the limit. : Factory setting: L3-03 = 50
L3-04 Setting 0 1 2 3
49
Constant Descriptions
Time
, Cont d Set the speed control proportional gain (C5-01) and integral time (C5-02) at the maximum output frequency. Set the speed control proportional gain (C5-03) and integral time (C5-04) at the minimum output frequency. Normally, C5-03 and C5-04 do not have to be set.
Proportional Gain C5-01
C5-03
f1 (Small Load)
f2 (Large Load)
C5-04
0
Load Torque Speed
Control without PG
Constant No. C3-01 E2-01 E2-02 E2-03 Name
Slip compensation gain Motor rated current Motor rated slip Motor no-load current
Setting Range
0 to 2.5 0.00 to 1500.0 A 0.00 to 20.00 Hz 0.00 to 1500.0 A
Factory Setting
1.0 1 2 2 2
Control with PG
Constant No. C5-01 C5-02 C5-03 C5-04 E2-04 F1-01 Name
ASR proportional gain 1 ASR integral time 1 ASR proportional gain 2 ASR integral time 2 Number of motor poles PG constant (P/R)
Setting Range
1.00 to 300.00
3
Factory Setting
20.00 4 0.500 4 20.00 4 0.500 4 4 600
1 : When using V/f control without PG, the initial value is 0.0 (without slip compensation). 2 : Initial value differs according to the inverter kVA setting or motor selection. 3 : When using V/f control with PG, the setting range is 0.00 to 300.00. 4 : Initial values of V/f control with PG are C5-01=0.20, C5-02=0.20 s, C5-03=0.02, C5-04=0.05 s.
50
7. Motor Protection
Motor Overload Detection
Motor rated current Motor protection selection Motor protection time constant E2-01 L1-01 L1-02
, Cont d operation time when 150 overload is applied after continuous operation at rated current (hot-start). : Factory setting: L1-02 = 1.0 min (150 yield stress) The following diagram shows an example of protective operation time characteristics of the electronic thermal overload relay [L1-02 = 1.0 minute, operation at 60 Hz, generalpurpose motor characteristics (when L1-01 is set to 1)].
Operating Time (min.)
10 7 3
The inverter protects against motor overload with a built-in electronic thermal overload relay. Make the correct settings as follows.
Constant No. E2-01 Name Setting Range Factory Setting
Motor rated Setting range is from 10 to 200 current of the inverter rated output current. 0 to 3 Motor 0Disabled (No motor protection) protection 1Protects general-purpose motors. 2Protects inverter exclusive-use motors. selection 3Protects vector control motors. Motor protection time constant 0.1 to 5.0 min
Cold Start
L1-01
1 0.4
L1-02
1.0 min
: Initial value differs according to the inverter kVA setting or motor selection.
1Set E2-01 to the rated current value on the motor nameplate. This set value becomes electronic thermal overload relay reference value. 2According to the applicable motor, set L1-01 for the overload protective function. Motor has different cooling capacity depending on the speed control range. Therefore, it is necessary to select the protective characteristics of the electronic thermal overload relay according to the allowable load characteristics of the applicable motor. The table below shows motor types and their allowable load characteristics. 3Set L1-02 to the motor protective operation time. (Normally, this setting is not needed.) Set the electronic thermal overload relay protective
The electronic thermal overload function monitors motor temperature, based on the inverter output current, frequency and time, to protect the motor from overheating. When electronic thermal overload relay is enabled, an OL1 error occurs, shutting OFF the inverter output and preventing excessive overheating in the motor. When operating with one inverter connected to one motor, an external thermal relay is not needed. When operating several motors with one inverter, install a thermal relay on each motor. In this case, set constant L1-01 to 0. Thermal overload calculated value is reset when the power supply is turned OFF so that protection may not be enabled in applications where the power supply is frequently turned ON and OFF even if L1-01 is set to either 1, 2 or 3.
100
Torque
Torque
Torque
Continuous Rating
Max. Speed of Frame No. 200LJ or more Max. Speed of Frame Nos. 160MJ to 180LJ Max. Speed of Frame No. 132MHJ or less
Continuous Rating
Max. Speed of Frame No. 200LJ or more Max. Speed of Frame Nos. 160MJ to 180LJ Max. Speed of Frame No. 132MJ or less
Continuous Rating
Max. Speed of Frame No. 200LJ or more Max. Speed of Frame Nos. 160MJ to 180LJ Max. Speed of Frame No. 132MJ or less
Torque
50
0.1
Rotation Speed
Rotation Speed
Rotation Speed
Motor to operate with commercial power supply. Has motor configuration where cooling effect can be obtained when operating at 50/60 Hz. Detects motor overload protection (OL1) at Electronic Thermal continuous operation at less than 50/60 Hz. Overload Relay Operation Inverter outputs a fault contact and the (at 100% Motor Load) motor coasts to a stop.
Cooling
Has motor configuration where cooling Has motor configuration where cooling Has motor configuration where cooling effect can be obtained even if operating in effect can be obtained even if operating at effect can be obtained even if operating at low-speed area (approx. 6 Hz). super low-speed area (approx. 0.6 Hz). super low-speed area (approx. 0.6 Hz).
Performs continuous operation at 6 to 50/60 Hz. Performs continuous operation at 0.6 to 60 Hz. Performs continuous operation at 0.06 to 60 Hz.
51
Constant Descriptions
8. PID Control
PID Control
PID control selection b5-01 Reference selection b1-01 Multi-function analog input terminal A2 Signal level selection H3-08 PID constant b5-02 to 10
PID control makes the set reference selection coincide with the feedback value (detected value). By combining proportional control (P), integral control (I) and differential control (D), PID control is enabled even for applications (machine systems) having idle time. Each control feature of PID control is as follows: P controlOutputs the operation amount in proportion with the deviation. However, the deviation cannot be made zero only by P control. I control Outputs the operation amount obtained by integrating the deviation. Effective to make the feedback value coincide with the reference selection. However, cannot follow up with rapid variation. D control Outputs the operation amount obtained by differentiating the deviation.
b5-01 Setting 0 1 2 3 4 PID Control Function
No PID control With PID control (D-control of deviation) With PID control (D-control of feedback value) With PID control (D-control of frequency reference + PID output or deviation) With PID control (D-control of frequency reference + PID output or feedback value)
How to Set PID Reference Selection
, Cont d
Setting Conditions
Set b1-01 to 1 and H3-09 to C (PID reference selection). At this time, set H6-01 to 1 (PID feedback value) and input the detected value to pulse train input terminal RP.
Input from MEMOBUS Set b1-01 to 2 and bit of MEMOBUS register Communication 000FH to 1, and register 0006H can be input as the Register 0006H PID reference selection through communications. Input from Pulse Train Set b1-04 to 4 and H6-01 to 2 (PID reference selection) Input Terminal RP
: Terminal A2 current signal (4 to 20mA) or voltage signal (0 to 10V) can be used. Terminal A2 current signal: H3-08 = 2 Terminal A2 voltage signal : H3-08 = 0 When the voltage signal is used, turn OFF dip switch S1-2 on the control board.
2Detected value setting The setting of the detected value can be selected from the following table.
How to Input Input from Multi-function Analog Terminal A2
Setting Conditions
Set H3-09 to B (PID feedback value).
Input from Pulse Train Set H6-01 to 1 (PID feedback value). Input Terminal RP
: Same as the asterisk in the above table.
The integral value is reset to 0 in the following cases: When command is input or during hold When multi-function input PID control cancel (set value: 19) is selected, and terminal PID is set as PID control cancel when closed The upper limit of I can be set by b5-04. When upgrading the control capacity by integration, increase the value of b5-04. If the control system vibrates and cannot be corrected by adjusting the integral time or primary delay time constant, decrease the b5-04 value. The PID control can be canceled by the multi-function input signal. The PID control is canceled by setting 19 in one of H1-01 to 06, and closing the contact; the reference selection signal is directly used as the frequency reference signal.
34 0
PID OFF
1Reference selection setting The frequency reference selected by b1-01 or the frequency reference selected by multi-step speed reference 1, 2 or 3 will be the reference selection for PID control. However, the reference selection can be set as shown in the following table.
Reference Selection
Deviation P b5-02 b5-01 I b5-03 D Limiter b5-04 13 Offset b5-07 b5-01 Limiter b5-06 Primary Lag Time Constant b5-08
Frequency Reference
24 13
b5-05 24
52
, Cont d provide a run command and frequency reference by communication, set these constants to setting 2. Also without regard to this selection, monitoring of running status, constant setting/reference, fault reset and multifunction input command from the PLC are enabled. The multi-function input command becomes OR with the command input from control circuit terminals S3 to S8. 2MEMOBUS frequency reference unit (o1-03) The frequency reference units from the PLC and in the frequency reference and output frequency monitors (by communication) are selected. 3MEMOBUS slave address (H5-01) The slave address number is set. It is necessary to set the address number so that it will not overlap with the address number of another slave connected on the same transmission line.
Note: To change the values set in constant H5-01 to H5-07 and enable new settings, it is necessary to turn OFF the power supply, and then turn it ON again.
The Varispeed F7 can perform serial communication through the programmable controller (hereafter referred to as PLC) and the MEMOBUS communication. MEMOBUS is composed of one master (PLC) and 1 to 31 slaves (Varispeed F7). In the signal transmission (serial communication) between the master and the slave (s), the master always starts signal transmission and the slaves respond to it. The master performs signal transmission simultaneously with one slave. Therefore, set address number for each slave in advance, and the master can specify the number for signal transmission. The slave that receives the command from the master executes the specified function, and returns a response to the master. Communication specifications InterfaceRS-485/422 SynchronizationNon-synchronous (start stop synchronization) Communication parameter Can be selected from baud rate 2400, 4800, 9600 or 19200 bps (constant H5-02). Data length Parity Stop bit 8-bit fixed with/without parity, odd/even parity selectable (constant H5-03) 1 bit fixed ProtocolMEMOBUS or equivalent (RTU mode only) Max. connection31 units (when RS-485 is used) Data that can be transmitted/received on-line Data that can be transmitted/received on-line are the run command, frequency reference, fault, inverter status, constant setting/reference. 1Operation mode selection (b1-01, b1-02) Select the run command and frequency reference input method in constants b1-01 and b1-02, respectively. To
4MEMOBUS communication error code (U1-39) If an error occurs in the MEMOBUS communication, the error contents can be displayed on the digital operator.
=*<*
1 : CRC Error 1 : Improper Data Length Not Used 1 : Parity Error 1 : Overrun Error 1 : Framing Error 1 : Time Over Not Used
53
Constant Descriptions
The Varispeed F7 standard digital operator (JVOP-161) can store the inverter constants. The constant capacity to be stored is for one unit. Since EEPROM (non-volatile memory) is used as the data memory elements, any backup power supply is not needed. Copy function selection (o3-01) The digital operator uses the incorporated EEPROM to perform the following three functions: Stores inverter constant set values in the digital operator (READ). Writes in the constant set values stored in the digital operator to the inverter (COPY). Compares the inverter constants with the constants stored in the digital operator (VERIFY). (Factory setting: o3-01)
o3-01 Setting 0 1 2 3
Normal operation READ (from inverter to operator) COPY (from operator to inverter) VERIFY (comparison)
For the constants used in the energy-saving mode, the optimum values have been set at factory. They do not have to be adjusted under normal operation. If the motor has very different characteristics from those of YASKAWA standard motors, refer to the following description of the constants and change them. The following describes the case where constant A1-02 is set to 0 (V/f control with PG) or 1 (V/f control without PG). Energy-saving coefficient (b8-04) In the energy-saving mode, the voltage at which the motor efficiency will be the maximum is calculated using this energy-saving coefficient, which is regarded as output voltage reference. This value has been set to the YASKAWA standard motors as the factory setting. Increasing the energy-saving coefficient makes output voltage larger. When using any motor other than YASKAWA standard motors, change the value by approx. 5 from the factory setting so that you can find the optimum value in which output power will be the minimum.
Contents
1READ Set o3-01 to 1 so that the inverter constant set values will be stored in the digital operator. 2COPY Set o3-01 to 2 so that the constant set values stored in the digital operator will be written in to the inverter. 3VERIFY Set o3-01 to 3 so that the inverter constants will be compared with the constant set values in the digital operator.
Note: Constants can be written (copied) only between the Varispeed F7 units with the same product code, software number, capacity and control mode (V/f control without PG, V/f control with PG or openloop vector control). However, some constants cannot be copied. If the conditions are not met, the digital operator displays an error such as CPE (ID unmatched), vAE (inverter capacity unmatched) or CrE (control mode unmatched). Depending on the revision level, some constants may not be copied. Refer to the Instruction Manual for details.
Read permitted selection (o3-02) Prohibition of constant read-out form the inverter can be set. By using this function, you can prevent the constant stored in the EEPROM of the digital operator from being changed by mistake. (Factory setting: o3-02 = 0)
o3-02 Setting 0 1
READ prohibited READ permitted
Contents
By setting o3-02 to 0, reading operation is disabled so that the constant data stored in EEPROM of the digital operator can be protected.
54
The droop control is a function that allows the user to set the slip of the motor. If a single load is moved with two motors (such as in a crane conveyor), a high-resistance motor is usually used. This is to maintain the balance of the loads torque and the overall speed using the torque characteristics that change in proportion to changes in the secondary resistor. If droop control is used, high-resistance motor characteristics can be obtained with a general-purpose motor.
Constant No. Name Description Setting Factory Range Setting
1Inputting torque reference The torque reference can be changed according to an analog input by setting H3-09 or H3-05 to 13 (torque reference) or 14 (torque compensation).
Torque Reference Input Method Description
b7-01
Set the slip as a percentage of maximum frequency when the maximum output 0.0 to Droop control frequency is specified and the rated gain torque occurs. 100.0 Droop-control is disabled when the setting is 0.0. Droop control responsiveness Droop control constant delay time When hunting or oscillation occurs, increase the value.
0.0
Input from the multiSet H3-04 to1 and H3-05 to 13. function analog terminal Set H3-04 to 0 for a 0 to 10V torque reference. A3 (0 to 10V) Input from the option board (A1-14B) Set F2-01 to 0, H3-08 to 1, and H3-09 to 13. terminal TC2 (0 to 10V)
Torque
The balance of the load is very different with different amounts of slip.
Torque
, Motor A s torque characteristics , Motor B s torque characteristics TA Load torque The difference between TA and TB is getting smaller. Reference speed Speed
2Speed/torque control switching function It is possible to switch between speed control and torque control when one of the multi-function inputs (H1-01 to H1-06) is set to 71. Speed control is performed when the input is OFF and torque control is performed when the input is ON. Set d5-01 to 0 to switch speed/torque control. Multi-function contact inputs (H1-01 to H1-06)
Setting Value 71 78 Function
Speed/torque control switching (ON: Torque control) Polarity reverse command for external torque reference (OFF: Positive, ON: Negative)
Torque compensation from analog input Torque reference from analog input Speed limit from analog input from terminal A1 Speed limit d5-04 Speed limit bias d5-05 Speed feedback Speed limiter Torque primary delay filter d5-02
Reference speed
d5-03
Speed controller (ASR)
55
Constant Descriptions
Set H3-08 to 2 and H3-09 to 13. Input from the multifunction analog terminal To switch the torque reference between positive and negative torque, set a multi-function analog input to 78. A2 (4 to 20 mA)
b7-02
2Zero-servo End (Completion) To output the zero-servo status externally, assign the Zero-servo End signal (setting 33) to one of the multifunction outputs (H2-01 to H2-03). Multi-function contact outputs (H2-01 to H2-03)
Setting Value 33
Run signal Zero-servo command
Function
Zero-servo end ON when the current position is within the range zeroservo start position zero-servo completion width
ON ON OFF OFF
The zero-servo function holds the motor when the motor is stopped in what is called a zero-servo status. This function can be used to hold the motor stopped even if an external force acts on the motor or the analog reference input is offset.
Constant No. Name Description Setting Factory Range Setting
Motor speed
b9-01
Zero-servo gain
Adjusts the strength of the zero-servo lock. Enabled when thezero-servo command is set for a multi-function input. When the zero-servo command has been input and the frequency reference drops below the 0 to zero-speed level (b2-01), a position control 100 loop is created and the motor stops. Increasing the zero-servo gain increases the strength of the lock. However, excessively large zero-servo gain will cause vibration.
Sets the output width of the zero-servo end signal. Enabled when thezero-servo completion (end)is set for a multi-function output. The zero-servo end signal is ON when the current position is within the range 0 to zero-servo start position zero-servo 16383 completion width . Set the allowable position displacement from the zero-servo start position to 4 times the pulse rate of the PG (pulse generator, encoder) in use.
Zero-servo status
b9-02
10
1Zero-servo command Set one of the multi-function contact inputs (H1-01 to H1-06) to 72. The zero-servo signal turns ON when the corresponding terminal turns ON. Multi-function contact inputs (H1-01 to H1-06)
Setting Value 72 Function
Zero-servo command (ON: Zero-servo)
Use feedforward control to increase the response to speed references. This function is effective for machines for which the ASR gain cannot be increased to a large value because doing so results in vibrations. There is also the additional effect of making the system less prone to overshoot.
Constant No. Name Description Setting Factory Range Setting
0 or 1 0
N5-01 control
Motor time
Sets the time required to accelerate 0.001 Depends on to the inverter rated speed. 10.000 capacity
Feedforward Response to speed references will 0.00 1.00 to gain setting is increased. 100.00
N5-02, N5-03
U1-45
Frequency reference
C5-01 to C5-04 U1-44 U1-05 Detected speed (Estimated speed) Speed controller (ASR)
56
Application Examples
Fans and BlowersContributes to Energy-saving and Improved Performance
Example of the Use of Inverter with Air Scrubber
MC1 Exhaust
Varispeed F7
Damper Power Supply Controller MC3 Frequency Reference 4-20 mA Manual 0-10 V MC1 R S T U V W MC2 Dust Collection Device Blower M Motor
200 VAC r s
MC3 Interlock
SA STOP RUN
MX
MX SA
R Power Supply S T
, User s Requirements Function and Parameter Settings Operate using control circuit terminals Frequency reference switching between 0 to 10V and 4 to 20mA Energy-saving control Operation method selection b1-01021
MC2 MX
MC1 SA
S1 FWD/Stop S5 A1 and A2 Switching SC 0-10 V 4-20 mA 0V A1 A2 AC M1 Running P1 Signal during Frequency Missing PC M2
Commercial Inverter
MC1
MC2 SA
Terminal A2 signal level selection H3-082 Terminal A2 function selectionH3-092 Terminal A1 and A2 switching (A2 when terminal S5 is ON) Energy-saving mode selection b8-01=1
RUNX
SA
Continue operation Operation when frequency L4-051 even if failure occurs reference is missing in frequency reference Reference loss signal H2-020 C Note: In this case, be sure to select coast to stop for inverter stopping method.
High-efficiency operation with light load Apply the torque limit function. Select the momentary power loss reset and restart mode. Select the automatic continuous operation mode when frequency reference is missing. Turn the monitor to the output power indication. Use the frequency reference lower limit. Use the preset frequency band prohibition function (frequency jump control). Up to 3 frequencies prohibited. Use the fault retry function.
Energy-saving mode selection b8-011 Torque limit L7-010-300 Momentary power loss protection L2-010 to 2 Operating signal selection L4-050 to 1 Frequency reference is missing H2-01 to 030 C Monitor display U1-08 Frequency reference lower limit d2-020 to 110 Jump frequency d3-01 to 030 to 400 Hz Jump frequency width d3-040 to 20.0 Hz Fault retry count L5-010 to 10 times
Dust Collection System Blower, Fan for Boilers Fan for Cooling Towers
Avoid overload tripping. Continue operation even when momentary power loss not longer than 2 seconds occur. Continue operation even if a failure occures in higher-order frequency reference equipment. Monitor output power. min-1 lower limit for lubricating the gear bearing. Avoid mechanical resonance.
The resonance point will be passed, and continuous operation is eliminated at this point.
57
Application Examples
Varispeed F7
R.S.T U.V.W
PID
Digital operator
Motor U V W FM AC
IM
, User s Requirements Function and Parameter Settings Operate using variable torque CT/VT selection C6-011
Frequency Meter
PID control PID control characteristics adjustment Feedback signal 4 to 20 mA Meter indication of motor current or output frequency
PID control selection b5-01 1 or 2 PID adjustment b5-02 to 10 PID control cancel H1-01 to 0619 Terminal A2 signal level selection H3-082 Terminal A2 function selection H3-090B Analog monitor selection H4-01041 to 38
S7 PID Control Cancel SC V Target Setting A1 (Target Value) AC PID Detected Value 4 to 20 mA A2 Sensor Detected Value Frequency Reference Value
M1 M2 During Run
User,s Requirements
Easy automatic control Constant rotating speed under load fluctuation
ChemicalFeeding Pump
Keep the mixed water ratio constant. Easy control for master/aux. switching Ammeter for monitoring load conditions. Drive the pump directly using 4-20mA signal.
Master/Aux. switching H1-01 to 0603 Output selection function Run signal selection H4-01040203
Function to maintain minimum speed. Run the system using the commercial power supply when an emergency occurs, then return to inverter. Function that can keep the system working without resetting it even when a momentary power loss occurs. Keep a constant water level inside a tank using a water gauge. Keep the motor min-1 above the minimum because if the min-1 is too low, water flows in the reverse direction.
Discharge Pump
58
Varispeed F7
Painting Booth Running BR Brake FWD/STOP Relay Sequence REV/STOP 2-Step Speed Referense Braking Resistor Unit
Shock Absorber
RUN/STOP Sequence
40m/min
Forward Run
1m/min
BX Mechanical Brake
Varispeed F7 R S T S1 FWD/Stop S2 REV/Stop S6 Multi-step Speed Input SC Frequency Detection M1 M2 MB Fault S5 Master/Aux Speed Digital U Operator V W B1 B2
Reverse Run
IM Motor
r Forward Run
(Sequencer)
RUNR
RUNF
LS2 SA
LS4 LS1
RUNR
SA
RUNF
RUNR
N
LS3 SA
Operate using Operation method b1-021 control circuit terminals selection Set multi-step speed Frequency operation reference Braking signal Frequency detection d1-030 to 400Hz d1-040 to 400Hz H2-0105 L4-010 to 400Hz
BX
MC
SA
Conveyor Circuit
Application Example User,s Requirements
Increase precision of positioning stop. Perform 2-step speed operation. Shuttle Conveyor Smooth accel/decel Variable accel/decel time
Control the braking motor using contact Operation method selection b1-021, H2-0105, Slip prevention L4-010 to 400Hz output from terminals M1 and M2. Use the multi-step speed function. Apply S-curve accel/decel. Frequency reference d1-01 to 040 to 400Hz S-curve accel/decel C2-01 to 040.0 to 2.5 s H1-01 to -0607 H1-01 to -0620 to 2F L7-01 to -040 to 300%2
Accel/decel time Use the accel/decel time setting function. switching External fault Torque limit
Select stop procedure according to Select stop procedures. degree of emergency. Increase starting torque Raw Material Input Conveyor (with a constant-torque motor). Steel Pipe Conveyor Drive more than one motor with a single inverter. Increase torque limit value. The function is provided. (Select V/f mode)
Control method selection A1-020 Over torque detection Over torque detection level Over torque detection time Control method selection V/f selection Free V/f setting L6-01, 040 to 4 L6-02, 050 to 300% L6-03, 060 to 10.0 s A1-020 E1-030F E1-04 to 10Setting
Check the motor generation torque Simple slip compensation function. using the torque detection function. Lifter Use non-excitation operating type braking motor. Use the free V/f setting function to turn the motor without excess excitation.
: Inverter capacity cannot be exceeded. Choose larger inverter capacity for the maximum torque required.
59
Application Examples
X-Axis Motor
NC Equipment
Operating Signal Status Signal Zero Speed Speed Agreed Running Digital Input Command
Spindle
Belt
Cutter Worker
MCCB
Power R Supply NC Equipment
Speed Setter
DI-08 (option) DI-16H2 (option) Overtorque detection selection Overtorque detection level Overtorque detection time Multi-function digital output Multi-function contact output L6-010 to 4 L6-020 to 300% L6-030 to 10.0 sec. H2-030B H2-0202
Running Fault
FM AC
FM
Frequency Meter
Digital Command
Interface Circuit to NC
User,s Requirements
Application Example
Overtorque detection selection Overtorque detection level Overtorque detection time Multi-function digital output Connect Frequency reference setting mode
L6-01, 040 to 4 L6-02, 050 to 300% L6-03, 060 to 10.0 s H2-01 to 030B DI-08 or -DI-16H2. F3-010 to 7
Use the digital speed command cards. Apply the zero-speed function.
Multi-function contact output H2-01 to 0301 Multi-function contact output H2-01 to 0302 Multi-function contact output H2-01 to 030B Option
Interface to NC
Apply the speed agreed function. Apply the overtorque detection function. (Cutting loss)
60
Protective Functions
Fault Detection
When the inverter detects a fault, the fault contact output operates, and the inverter is shut OFF causing the motor to coast to stop. (The stopping method can be selected for some faults, and the selected stopping method will be used with these faults.) A fault code is displayed on the digital operator. Turn off a run command and use one of following methods to reset after restarting the inverter. Set a multi-function input (H1-01 to H1-06) to 14 (Fault Reset) and turn ON the error reset signal. Press the key on the digital operator. Turn the main circuit power supply OFF and then ON again.
Fault Overcurrent Ground Fault Fuse Blown Main Circuit Overvoltage OC GF PUF OV
Display oC GF PUF ou Uu1 Uu2 Uu3 PF LF oH oH1 oH3 oH4 MH MM oL1 oL2 oL3 oL4 oL7 UL3 UL4 o5 PGo dEu CF FbL
Meaning
The inverter output current exceeded the overcurrent detection level.(200 of rated current) The ground fault current at the inverter output exceeded approx. 50 of the rated output current. The fuse in the main circuit is blown. The main circuit DC voltage exceeded the overvoltage detection level. 200 V class: approx. 410 V, 400 V class: approx. 820 V The maincircuit DC voltage detection level setting (L2-05). 200 V class: approx. 190 V, 400 V calss: approx. 380 V The control power supply voltage dropped. The MC did not respond for 10 s even though the MC-ON signal has been output. (200 V class: 37 to 110 kW, 400 V class: 75 to 300 kW) The main circuit DC voltage oscillates unusually. (Detected when L8-05 = 1) An open-phase occurred at the inverter output. (Detected when L8-7 = 1) , The temerature of the inverter s cooling fins exceeded the setting in L8-02 or 105 . , (OH: Exceeded the setting in L8-02 [L8-03 = 0 to 2], OH1: Exceeded 105 ) Inverter s cooling fan stopped.
Main Circuit Undervoltage Main Circuit MC Operation Fault UV1 Control Power FaultUV2 Inrush Prevention Circuit UV3 Fault Main Circuit Voltage Fault PF Output Open-phase LF Cooling Fin Overheating OHOH1 Motor Overheating Alarm OH3 Motor Overheating Fault OH4 Mounting Type Braking Resistor OverheatingRH Built-in Braking Resistor RR Fault Motor Overload Inverter Overload OL1 OL2
The inverter will stop according to the setting of L1-04. The protection function has operated if it has been enabled in L8-01. The braking transistor in not operating properly. The motor overload protection function has operated based on the internal electronic thermal value. The inverter overload protection function has operated based on the internal electronic thermal value. There has been a current greater than the setting in L6-02 for longer than the time set in L6-03. There has been a current greater than the setting in L6-05 for longer than the time set in L6-06. The output frequency did not change for longer than the time set in N3-04. There has been a current less than the setting in L6-02 for longer than the time set in L6-03. There has been a current less than the setting in L6-05 for longer than the time set in L6-06. The speed has been higher than the setting in F1-08 for longer then the time set in F1-09. PG pulses were not input when the inverter was outputting a frequency (soft start output E1-09). The speed deviation has been greater than the setting in F1-10 for longer the time set in F1-11. The torque limit was reached continuously for 3 seconds or longer during a deceleration stop at open-loop vector control. A PID feedback reference loss was detected (b5-12 = 2) and the PID feedback input was less than b5-13 (PID feedback loss detection level) for longer than the time set in b5-14 (PID feedback loss detection time).
Overtorque Detected 1 OL3 Overtorque Detected 2 OL4 OL7 High-slip braking OL Undertorque Detected 1 UL3 Undertorque Detected 2 UL4 Overspeed OS
The ground fault here is one that occurs in the motor wiring during operation. Ground faults may not be detected under the following conditions. A ground fault with low resistance which occurs in motor cables or terminals. The inverter power supply is turned ON after a ground fault has occurred.
61
Protective Functions
The inverter will stop or continue to operate according to the setting of L1-03.
Fault External Fault Input from Communications Option CardEF0 External Fault (Input Terminal S3) EF3 External Fault (Input Terminal S4) EF4 External Fault (Input Terminal S5) EF5 External Fault (Input Terminal S6) EF6 External Fault (Input Terminal S7) EF7 External Fault (Input Terminal S8) EF8 Zero-servo Fault SVE
Meaning
An external fault was input from a communications option card.
Exceeded Allowable Number of Speed Search Retrials SEE Digital Operator Connection OPR Fault MEMOBUS Communications CE Error Option Communications BUS Error SI-T Watchdog Error E5 SI-F/G Option Board CPU E-10 Failure
Digital Operator CPF00 Communications Error 1 CPF00 CPU External RAM Fault CPF01 CPF01 Baseblock Circuit Error CPF02 CPF02 EEPROM Error CPF03 C P F 0 3
CPU Internal A/D Converter CPF04 Error CPU External A/D Converter CPF05 Error Option Card Connection CPF06 Error ASIC Internal RAM Fault CPF07 Watchdog Timer Fault CPF08 CPU-ASIC Mutual Diagnosis Fault CPF09 ASIC Version Fault CPF10
Option Card ErrorCPF20 C P F 2 0 Communications Option Card CPF21 Self Diagnosis Error CPF21 Communications Option Card CPF22 Model Code Error CPF22 Communications Option Card CPF23 DPRAM Error CPF23
62
Alarm Detection
Alarms are detected as a type of inverter protection function that do not operate the fault contact output. The system will automatically returned to its original status once the cause of the alarm has been removed.
Alarm Foward/Reverse Run Commands Input Together EF Main Circuit Undervoltage UV Display EF Meaning
Both the forward and reverse run commands have been ON for more than 5 seconds. The following conditions occurred when there was no Run signal. The main circuit DC voltage was below the undervoltage detection level setting (L2-05). The inrush current limit contactor opened. The control power supply voltage was below the CUV level. The main circuit DC voltage exceeded the overvoltage detection level. 200 V class: approx. 410 V, 400 V class: approx. 820 V The temperature of cooling fins exceeded the setting in L8-02. (Factory setting: L8-03) An OH2 alarm signal (inverter overheating alarm signal) was input from a multi-function input terminal (S3 to S8). E was set in H3-09 and the motor temperature thermistor input exceeded the alarm detection level. There has been a current greater than the setting in L6-02 for longer than the time set in L6-03. There has been a current greater than the setting in L6-05 for longer than the time set in L6-06. There has been a current less than the setting in L6-02 for longer than the time set in L6-03. There has been a current less than the setting in L6-05 for longer than the time set in L6-06. The speed has been greater than the setting in F1-08 for longer than the time set in F1-09. PG pulses were not input when the inverter was outputting a frequency. The speed deviation has been greater than the setting in F1-10 for longer the time set in F1-11. Continuing operation was specified for EF0 (F6-03 = 3)and an external fault was input from the option card.
Uu
Main circuit Overvoltage OV Cooling Fin Overheating OH Inverter Overheating Pre-alarm OH2 Motor Overheating OH3 Overtorque 1 OL3 Overtorque 2 OL4 Undertorque 1 UL3 Undertorque 2 UL4 Overspeed OS PG Disconnected PGO Excessive Speed Deviation DEV External Fault Detected for Communications Board Other than SI-K2 EF0 External Fault (Input Terminal S3)EF3 External Fault (Input Terminal S4)EF4 External Fault (Input Terminal S5)EF5 External Fault (Input Terminal S6)EF6 External Fault (Input Terminal S7)EF7 External Fault (Input Terminal S8)EF8 PID Feedback Reference Lost FbL MEMOBUS Communications ErrorCE Option Card Communications Error BUS Communications on StandbyCALL Reset during Run Command Input ErrorCRST SI-T Watchdog Error Detected E5 SI-T Station Number Setting ErrorAEr SI-T Communications Cycle Setting ErrorCyC Receiving External Baseblock Command bb o o o o U U
ou o H H L L L L o PG dE H 2 3 3 4 3 4 5 0 u
EF0 E E E E E E F F F F F F 3 4 5 6 7 8
A normal reception was not possible for 2 seconds or longer after control data was received ounce. A communications error was detected during a run command or a frequency reference mode from a communications option card. Data was not received properly when the power supply was turned on. The reset signal was input during Run Command input from an external terminal or other source. A Watchdog error was detected when the Run Command or a frequency reference was set from an option card and continuous operation was set for the E5 operation selection. Station number of SI-T option card was out of setting range. Communications cycle of SI-T option card was out of range. External baseblock was input from external terminal again while it was input.
Operation Errors
An operation error will occur if there is an invalid setting or a contradiction between two constant settings. The inverter will not start until the constants have been set correctly. (The alarm output and fault contact outputs will not operate wither.)
Error Incorrect Inverter Capacity OPE01 Setting Constant Setting Range ErrorOPE02 Multi-function Input Selection Error OPE03 Option Card Reference OPE05 Selection Error Control Mode Selection Error OPE06 Multi-function Analog Input Selection Error OPE07 Constant Selection Error OPE08 PID Control Selection Error OPE09 V/f Data Setting Error OPE10 Constant Setting ErrorOPE11 EEPROM Write Error ERR Display oPE01 oPE02 oPE03 oPE05 oPE06 oPE07 oPE08 oPE09 oPE10 oPE11 EMM Meaning
The inverter capacity setting doesn,t match the unit. (Contact your YASKAWA representative.) The constant setting is out of the valid setting range. The same setting has been selected for two or more multi-function inputs (H1-01 to 05) or UP or DOWN command was selected independently, etc. An option card is not connected when the option card was selected as the frequency reference source by setting b1-01 to 3. A PG speed control card is not connected when V/f control with PG was selected by setting A1-02 to 1 or flux vector control was selected by setting A1-02 to 3. The same setting has been selected for the analog input selection and the PID function selection. A setting not required in the control mode has been selected. PID sleep function is valid (b5-01 0 and b5-15 0) and stop method has been set to 2 or 3. Constants E1-04, E1-06, E1-07, and E1-09 do not satisfy the conditions. Constant setting error occurred. A verification error occurred when writing EEPROM.
63
Protective Functions
A PID feedback reference loss was detected (b5-12 = 2) and the PID feedback input was less than b5-13 (PID feedback loss detection level) for longer than the time set in b5-14 (PID feedback loss detection time).
Varispeed F7
IM
Varispeed F7
IM
S8 8
S8 8
A3 3
A3 3
Varispeed F7
IM
S8 8
10 mA to 1 A A A 10 mA to 1 A
10 mA to 1 A A A 10 mA to 1 A
A3 3
64
Varispeed F7 Varispeed F7
S8 8
10 mA to 1 A A 10 mA to 1 A A
10 mA to 1 A A 10 mA to 1 A A
S8 8
1Use the phase difference 30 transformer with a dual star delta on secondary side and el tertiary side. 2Make sure to remove the wiring between RR1, SS1, TT1 (wired at shipment). If connecting a transformer with a dual star delta secondary with wiring, transformer may burn out.
Varispeed F7 Varispeed F7
10 mA to 1 A A A 10 mA to 1 A
S8 8
S8 8
10 mA to 1 A A A 10 mA to 1 A
Notes: 1 Braking function is not activated at stop. (Motor coasts to a stop.) 2 Use delay release type MC and MCX when restart function is required upon momentary power loss. 3 When using digital operator setting value as frequency reference, frequency setting resistor is not required. 4 Turn OFF the switch after motor completely stops.
65
MC
G1
G2 R/L1
S/L2 T/L3
F
Power Supply
Control Circuit
Power Supply
Control Circuit
CIMR-F7A20222030
G3
CIMR-F7A4022 to 4055
G3
G1
MC
G1
MC
Power Supply
Control Circuit
Power Supply
Control Circuit
CIMR-F7A2037 to 2110
G3
CIMR-F7A4075 to 4300
G3
G1
G1
r/r 1 s /r 2 a b
Power Supply
Control Circuit
400/200
a b
Power Supply
Control Circuit
1When using 12-pulse input, contact your YASKAWA representative. 2r/l1R and s/l2 S are short circuited at shipment. When using a DC power supply for the main circuit of models CIMR-F7A2037 to F7A2110 or using a separate power supply for cooling fin and MC operator, remove the wiring for the short circuits and input 200 V power supply to r/l1 and s/l2 . For 230 V 50 Hz or 240 V 50/60 Hz power supply, a transformer for cooling fin and MC is required. 3r/l1R and s400/l2 400S are short circuited at shipment. When using a DC power supply for the main circuit of models CIMR-F7A4075 to F7A4300 or using a separate power supply for cooling fin and MC operator, remove the wiring for the short circuits and input 200 V power supply to r/l1 and s400/l2 400 or r/l1 and s200/l2 200.
66
Details
Always install the braker on the power supply side to protect the inverter wiring. The leakage braker must be of high frequency specifications. When braking resistor is attached, install the contactor to prevent the braking resistor from burning. Also inset a surge suppressor on the coil. Absorbs the open / close surge of electro-magnetic contactors and control relays. Always insert the surge suppressor on magnetic contactors and relays near the inverter. Isolates the inverter input / output signal, and is effective to prevent inductive noise. Applied to improve the input power ratio of the inverter. The Varispeed G7 incorporates DC reactor on model of 18.5 kW or more (option for model 15 kW or less). When using large power supply capacity (600 kVA or more ), also install the DC reactor or AC reactor. Reduces noise circulating to the inverter input power system, or originating from the wiring. Insert the filter as near the inverter as possible.
P.73
Power Supply
To prevent burning Magnetic (with braking contactor resistor) To prevent open/ close surge to Surge suppressor the exterior To isolate input/ Isolator output signal
P.73
SC series
DCR2 - = DGP=
P.85
UZDA-= UZBA-=
Input noise filter To reduce effect of noise interference to radios and control devices
P.74
F6045GB FIL001098 Reduces noise from the line that sneaks into the Finemet F11080GB inverter input power system. Insert as close to zero-phase reactor to reduce FIL001097 the inverter as possible. F200160PB Can be used on both the input side and output side. radio noise 300-001-041
Output noise filter Braking resistor To stop the machine within the preset time
LF-=
Reduces noise originating from the output side wiring of the inverter. Insert the filter as near the inverter as possible.
P.76
ERF-150WJ== Shortens the deceleration time by consuming the regenerative R00==== energy of the motor by the resistor. (Use rate 3 ED)
P.78
To operate the inverter by external control To operate the inverter by system control
Used in combination with the braking resistor unit CDBR-= 72600-R===0 to reduce the deceleration time of the motor. Control panel that allows remote (50 m max.) frequency JVOP-95= setting and start/stop operation by analog reference. 73041-0905X-= Frequency meter scale: 60/120 Hz, 90/180 Hz
Varispeed F7
P.83, P.86
Control panel that allows remote (50 m max.) frequency VS operator JVOP-96= setting and start/stop operation by analog reference. (Standard sheet 73041-0906X-= Frequency meter scale: 75 Hz, 150 Hz, 220 Hz metal)
P.84
VS system module
JGSM-=
System controller that allows optimum system integration by combining with the necessary VS system module according to the automatic control system.
P.85 Output Noise Filter
To secure inverter Backup capacitor For momentary power loss of the control power P00=0 momentary power unit for momentary 73600-P00=0supply (Power holding time : 2 sec. ) loss recovery time power loss DCF-6A Monitors frequencies and currents. Frequency meter, ammeter Monitor frequencies, currents, and voltages Output voltmeter SCF-12NH Measures the output voltage externally and
designed for use with PWM inverters.
Grounding
Potentiometer for ETX003270 Connected to the control circuit terminals to frequency reference (2k) adjust frequency references and the scales on Potentiometer for scale ETX003120 the meters. adjustment (20k) Frequency setting RV30YN20S 2 k potentiometer (2k) RH000739 Adjusts frequency references and the scale on Frequency meter adjusting RV30YN20S 20 k the meters. potentiometer (20k) RH000850 CM-3S Frequency setting knob -
P.84
Motor
P.84
When applying the leak breaker, use those with 200 mA or more current sensitivity, operation time 0.1 seconds or more, to prevent malfunction. Or, use those with high-frequency adaptation. (Example) Mitsubishi Electric Ltd. NV series (those produced after 1988) Fuji Electric Ltd. EG, SG series (those produced after 1984)
Grounding
67
Shortens the deceleration time by consuming the regenerative Braking resistor LKEB-= 75600-K===0 energy of the motor by the resistor. (Use rate 10 ED) unit
Option Cards
Items in blue letters are available for inverters of Spec E or later Type Speed (frequency) reference card Name Analog reference card AI-14U Analog reference card AI-14B Digital reference card DI-08 Digital reference card DI-16H2 MECHATROLINK communicaitons I/F card SI-T DeviceNet communications I/F card SI-N11 CC-Link communications I/F card SI-C Profibus-DP communications I/F card SI-P11 Code No.
73600-C001X
Function
Allows high precision, high resolution analog speed reference setting. Input signal level: 0 to 10 VDC (20 k) 1 channel 4 to 20 mADC (250 ) 1 channel Input resolution: 14 bits (1/16384) Allows bipolar high precision, high resolution analog speed reference setting. Input signal level: 0 to 10 VDC (20 k) 4 to 20 mADC (500 ) 3 channels Input resolution: 13 bits code (1/8192) Allows 8-bit digital speed reference setting. Input signal: Binary 8 bits/BCD 4 digits SIGN signal SET signal Input voltage: 24 V (isolated) Input current: 8 mA Allows 16-bit digital speed reference setting. Input signal: Binary 16 bits/BCD 2 digits SIGN signal SET signal Input voltage: 24 V (isolated) Input current: 8 mA With 16-bit/12-bit select function Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through MECHATROLINK communication with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through DeviceNet communication with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through CC-Link communication with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through Profibus-DP communication with the host controller. Used for HVAC control, running or stopping the inverter,setting or referencing parameters, and monitoring output current,watt-hours, or similar items through LONWORKS communications with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through InterBus-S communication with the host controller. Used for running or stopping the inverter, setting or referencing parameters, and monitoring output frequency, output current, or similar items through CANopen communication with the host controller. Outputs analog signal for monitoring inverter output state (output freq., output current etc.) after absolute value conversion. Output resolution: 8 bits (1/256) Output voltage: 0 to 10 V (non isolated) Output channel: 2 channels Outputs analog signal for monitoring inverter output state (output freq., output current etc.) Output resolution: 11 bits (1/2048) + code Output voltage: 10 to 10 V (non isolated) Output channel: 2 Outputs isolated type digital signal for monitoring inverter run state (alarm signal, zero speed detection etc.) . Output channel: Photo coupler 6 channels (48 V, 50 mA or less) Relay contact output 2 channels 250 VAC, 1 A or less 30 VDC, 1 A or less Two multi-function contact outputs (2C-relay) can be used other than those of the inverter proper unit. Pulse generator on motor performs speed feedback to correct speed fluctuations caused by slipping (for V/f control with PG). Phase A pulse (single pulse) inputs (voltage, complementary, open collector input) PG frequency range: Approx. 30 kHz max. [ Power supply output for PG: 12 V, max. current 200 mA ] Pulse monitor output: 12 V, 20 mA Used for vector control with PG or V/f control with PG Phase A and B pulse inputs (exclusively for complementary input) PG frequency range: Approx. 30 kHz max. [ Power supply output for PG: 12 V, Max. current 200 mA] Pulse monitor output: Open collector, 24 V, Max. current 30 mA
Manual No.
TOEC736-30.13
73600-C002X
TOEC736-30.14 TOEC736-30.14 TOEC736-40.7 Contact your YASKAWA representative. SIBP C73060001 TOBZC736-70.6 SIBZC736-70.9 TOBP C73060011A SIBP C730600 07A
73600-C003X
73600-C016X
73600-C030X
73600-C021X-01
73600-C032X
73600-C033X
LONWORKS 73600-C035X communications I/F card SI-J1 InterBus-S communications I/F card Under development SI-R CANopen 73600-C038X communications I/F card SI-S1 Analog monitor card AO-08
73600-D001X
TOEC736-30.21
73600-D002X
TOEC736-30.22
73600-D004X
TOEC736-30.24
73600-D007X
TOEC736-40.8
PG-A2
73600-A012X
TOEC736-40.1
PG-B2
73600-A013X
TOEC736-40.2
68
Name
Code No.
Function
Used for V/f control with PG Phase A pulse (differential pulse) input for V/f control (RS-422 input) PG frequency range: Approx. 300 kHz max. [ Power supply output for PG: 5 V or 12 V, Max. current 200 mA] Pulse monitor output: RS-422 Used for vector control with PG or V/f control with PG Phase A, B and Z pulse (differential pulse) inputs (RS-422 input) PG frequency range: Approx. 300 kHz max. [ Power supply output for PG: 5 V or 12 V, Max. current 200 mA] Pulse monitor output: RS-422
Manual No.
TOEC736-40.3
PG-D2
73600-A014X
PG-X2
73600-A015X
TOEC736-40.4
1When using configuration software installed in an inverter on various field networks, a file is required to connect the software to the inverter. Contact your Yaskawa representative for the appropriate file. 2PG speed controller card is required for PG control.
MCCB
MCCB
Inverter R S T U V W Motor IM
0-10 V
TC1 10 k
20 k
20 k 2 F
Varispeed F7
2CN 2CN
4-20 mA P 0V
Standard Voltage Current Generator etc.
TC2 TC3
10 k 10 k 250 2 F 0V 0V
TC11
0V
Notes: 1 All TC1 to TC10 input circuits are common. 2 TC6 input circuit is represented.
MCCB
Inverter
R S T U V W
MCCB
Inverter R S T U V W Motor IM
Motor IM
TC1
Varispeed F7
0.1F 2.4 k 8 mA
TC2
2CN 0V
TC1
10 k 20 k 600 20 k 1 F 1.0
Varispeed F7
2CN
TC2
2CN 2CN
TC3
10 k 600 20 k
0V
TC3 E
12
TC4
Notes: 1 TC1-1 to -10, TC2-1 to -9 input circuits are common. 2 TC1-6 input circuit is represented.
69
D0 D1 D2 D3 D4 D5 D6 D7 SIGN SET
TC1 TC2 TC3 TC4 TC5 TC6 TC7 TC8 TC9 TC10
24 V
Photo Coupler
6.2 V 5.1 k
Varispeed F7
0.1F 2.4 k 8 mA
2CN
0V
2CN
Input2 CN MECHATROLINK Communications I/F Card SI-T Profibus-DP Communications I/F Card SI-P1
Note: If using the SI-T card, an optional card for monitoring cannot be MCCB installed in the inverter.
Inverter R S T U V W
Inverter U V W
Motor IM
Varispeed F7
DATA DATA + SLD
1 2 3 4 1 2 3 4 DS485 D/R
Varispeed F7
2CN
E G
MCCB R S T
Inverter U V W
Motor IM
MCCB R S T
Inverter U V W
Motor IM
Varispeed F7
5 V 5 V 5 V 2CN VCC
V V CAN_L CAN_H Shield P P
Black Blue White Red
Varispeed F7
2CN
A SLD B
2CN 2CN
CAN
Transceiver
5 V E E G
DA DB DC SLD
FTT-10A
MCCB R S T
Inverter U V W
Motor IM
MCCB
Inverter R S T U V W Motor IM
Varispeed F7
2CN
DA DB DG SLD SLD
Varispeed F7
+ 5 V + 5 V + 5 V 2CN VCC
CAN_GND CAN_L CAN_H Shield 1 2 3 4
2CN
2CN
DA DB DC SLD
CAN transceiver
E
FG
E(G)
70
Inverter
MCCB
Motor
Inverter
Motor
Varispeed F7 Varispeed F7
Converter
E G
Inverter Motor
MCCB
Inverter
Varispeed F7 Varispeed F7
Converter
71
Motor
Pulse
Pulse
Pulse
Pulse
Pulse A
Pulse B Pulse Z
Inverter
Motor
Inverter
Motor
Pulse
Pulse
Pulse
Power supply for PG (from PG-D2) TA1 1-2 (0 V): 12 V 200 mA max TA1 1 3-2 (0 V): 5 V 200 mA max DO NOT use the both supplies at the same time.
PG Speed Controller Card PG-D2
FWD
Coils of Magnetic Contactor and Control Relay 200 V LY-2-3 to Control 230 V Relay HH-22-23 MM-2-4 380 to 460 V Units Large-size Magnetic Contactors
Lead
6
250
16
16
76
24 30
6 18 Dia. 3
34
Mass22 g
Mass5 g
Mass150 g
Type RFN3AL504KD
72
33
4.8 Dia. L
200 V Class
Molded-case Circuit Breaker (MCCB) Motor Varispeed F7 Model Capacity Without DC Reactor With DC Reactor CIMR-F7A _ Model Rated Current (A) Model Rated Current (A) W 5 NF30 5 NF30 0.4 20P4 10 NF30 10 NF30 0.75 20P7 10 NF30 15 NF30 1.5 21P5 15 NF30 20 NF30 2.2 22P2 20 NF30 30 NF30 3.7 23P7 40 NF50 50 NF50 5.5 25P5 50 NF100 60 NF50 7.5 27P5 75 NF100 75 NF100 11 2011 100 NF225 125 NF100 15 2015 125 NF225 150 NF225 18.5 2018 150 NF225 22 2022 175 NF225 30 2030 225 NF225 37 2037 250 NF400 45 2045 300 NF400 55 2055 400 NF400 75 2075 500 NF600 90 2090 600 NF600 110 2110 Note: Models of 22 to 110 kW are equipped with built-in DC reactor to improve power factor.
Magnetic Contactor Without DC Reactor With DC Reactor Model Rated Current (A) Model Rated Current (A)
SC-03 SC-05 SC-4-0 SC-N1 SC-N2 SC-N2S SC-N3 SC-N4 SC-N5 11 13 18 26 35 50 65 80 93 SC-03 SC-03 SC-05 SC-4-0 SC-N1 SC-N2 SC-N2S SC-N4 SC-N4 SC-N5 SC-N6 SC-N7 SC-N8 SC-N10 SC-N11 SC-N12 SC-N12 SC-N14 11 11 13 18 26 35 50 80 80 93 125 152 180 220 300 400 400 600
400 V Class
Motor Capacity W
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300
Molded-case Circuit Breaker (MCCB) Without DC Reactor With DC Reactor Model Rated Current (A) Model Rated Current (A)
NF30 NF30 NF30 NF30 NF30 NF30 NF30 NF50 NF100 NF100 3 5 10 15 20 30 30 50 60 75 NF30 NF30 NF30 NF30 NF30 NF30 NF30 NF50 NF50 NF100 NF100 NF100 NF225 NF225 NF225 NF225 NF400 NF400 NF400 NF400 NF600 NF600 NF800 3 5 10 10 15 20 30 40 50 60 75 100 125 150 175 225 250 300 350 400 500 600 800
Magnetic Contactor Without DC Reactor With DC Reactor Model Rated Current (A) Model Rated Current (A)
SC-03 SC-03 SC-05 SC-4-0 SC-4-1 SC-N2 SC-N2S SC-N2S SC-N3
7 7 9 13 17 32 48 48 65
SC-03 SC-03 SC-05 SC-4-0 SC-4-1 SC-N1 SC-N2 SC-N2S SC-N2S SC-N3 SC-N4 SC-N4 SC-N5 SC-N6 SC-N7 SC-N8 SC-N10 SC-N11 SC-N11 SC-N12 SC-N12 SC-N14 SC-N16
7 7 9 13 17 25 32 48 48 65 80 80 90 110 150 180 220 300 300 400 400 600 800
Note: Models of 22 to 300 kW are equipped with built-in DC reactor to improve power factor.
73
Noise Filter
Input Noise Filter
MCCB R S T Input Noise Filter IN
1 4 U R 2 5 V S 3 6 W T
Varispeed F7 R S T U V W IM
Manufactured by YASKAWA
2 Be sure to connect input noise filter on inverter input side (U, V, W).
200 V Class
Inverter Model Max Applicable Motor Output CIMR-F7A= kW 20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 Noise Filter without Case Current Model Code No. Qty. RatedA
LNFD-2103 DY 72600-D2103 DY LNFD-2103 DY 72600-D2103 DY LNFD-2103 DY 72600-D2103 DY LNFD-2153 DY 72600-D2153 DY LNFD-2303 DY 72600-D2303 DY LNFD-2203 DY 72600-D2203 DY LNFD-2303 DY 72600-D2303 DY LNFD-2303 DY 72600-D2303 DY LNFD-2303 DY 72600-D2303 DY LNFD-2303 DY 72600-D2303 DY LNFD-2303 DY 72600-D2303 DY 1 1 1 1 1 2 2 3 3 4 4 10 10 10 15 30 40 60 90 90 120 120
Rated Current A
Noise Filter by Schaffner Electronik AG Current Model Code No. Qty. RatedA
FN258L-42-07 FN258L-55-07 FN258L-75-34 FN258L-100-35 FN258L-130-35 FN258L-130-35 FN258L-180-07 FN359P-250-99 FN359P-250-99 FN359P-300-99 FN359P-400-99 FN359P-500-99 FN359P-600-99 FIL001065 FIL001066 FIL001067 FIL001068 FIL001069 FIL001069 FIL001070 FIL001071 FIL001071 FIL001072 FIL001073 FIL001074 FIL001075 1 1 1 1 1 1 1 1 1 1 1 1 1 42 55 75 100 130 130 180 250 250 300 400 500 600
10 10 10 15 30 40 60 90 90 120 120
Note: When two filters or more are required, connect them in parallel. (See Parallel Installation Example on P76.) One noise filter is required if the filter is made by Schanffner Electronik AG.
400 V Class
Inverter Model Max Applicable Motor Output CIMR-F7A= kW 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300 Noise Filter without Case Current Model Code No. Qty. RatedA
LNFD-4053 DY 72600-D4053 DY LNFD-4053 DY 72600-D4053 DY LNFD-4103 DY 72600-D4103 DY LNFD-4103 DY 72600-D4103 DY LNFD-4153 DY 72600-D4153 DY LNFD-4203 DY 72600-D4203 DY LNFD-4303 DY 72600-D4303 DY LNFD-4203 DY 72600-D4203 DY LNFD-4303 DY 72600-D4303 DY LNFD-4303 DY 72600-D4303 DY LNFD-4303 DY 72600-D4303 DY LNFD-4303 DY 72600-D4303 DY LNFD-4303 DY 72600-D4303 DY LNFD-4303 DY 72600-D4303 DY 1 1 1 1 1 1 1 2 2 2 3 3 4 4 5 5 10 10 15 20 30 40 60 60 90 90 120 120
Rated Current A
Noise Filter by Schaffner Electronik AG Current Model Code No. Qty. RatedA
FN258L-42-07 FN258L-55-07 FN258L-55-07 FN258L-75-34 FN258L-100-35 FN258L-130-35 FN258L-130-35 FN258L-180-07 FN359P-250-99 FN359P-300-99 FN359P-300-99 FN359P-400-99 FN359P-400-99 FN359P-500-99 FN359P-600-99 FN359P-900-99 FIL001065 FIL001066 FIL001066 FIL001067 FIL001068 FIL001069 FIL001069 FIL001070 FIL001071 FIL001072 FIL001072 FIL001073 FIL001073 FIL001074 FIL001075 FIL001076 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 42 55 55 75 100 130 130 180 250 300 300 400 400 500 600 900
5 5 10 10 15 20 30 40 60 60 90 90 120 120
74
Note: When two filters or more are required, connect them in parallel. (See Parallel Installation Example on P76.) One noise filter is required if the filter is made by Schanffner Electronik AG.
Dimensions in mm
Without Case
MTG Screws MTG Screws
With Case
1.5
1.5
(Note)
30
a. Di
5 Dia. (max.)
Drawing 1
Drawing 2
Detail of Mtg. Hole
Model Code No. DWG LNFD-= 72600W 2103DY D2103DY 1 120 2153DY D2153DY 1 120 2203DY D2203DY 1 170 2303DY D2303DY 2 170 4053DY D4053DY 2 170 4103DY D4103DY 2 170 4153DY D4153DY 2 170 4203DY D4203DY 2 200 4303DY D4303DY 2 200
D
80 80 90 110 130 130 130
M
20 20 20 20 30 30 30 30 30
Terminal Mass X Y kg
0.2 9 10 11 13 0.2 0.4 0.5 0.3 9 11 0.4 0.4 0.5 10 13 0.6
Model LNFD-= 2103HY 2153HY 2203HY 2303HY 4053HY 4103HY 4153HY 4203HY 4303HY
Code No. 72600D2103HY D2153HY D2203HY D2303HY D4053HY D4103HY D4153HY D4203HY D4303HY
W
185 185
D
95 95
Noise Filter H A B
85 85 155 155 210 210 205 205 205 240 240 65 65 95 95 110 110 110 125 125
12
Di a.
C
33 33 33 33 43 43 43 43 43
Terminal Mass X Y kg
0.9 9 10 11 13 0.9 1.5 1.6 1.6 9 11 1.7 1.7 2.2 10 13 2.2
240 125 100 240 125 100 235 140 120 235 140 120 235 140 120 270 155 125 270 155 125
B
1851 1851 220 220 240 240
C
70 80 80 900.8
D
300 300 300 3501.2
E
314 314 314 364 414 413
F
45 55 55 65 80 80
G
6.5 6.5 6.5 6.5 6.5 6.5
H
500 500 500
J
1.5 1.5 1.5 1.5 3 4
L
12 12 15
O
M6 M6 M6 M10 M10 M10
P
AWG8 AWG6 50 mm2
Mass kg
2.8 3.1 4.0 7.5 11 See the table below. 5.5
Model Mass kg FN359P-250-99 16 FN359P-300-99 16 FN359P-400-99 18.5 FN359P-500-99 19.5 FN359P-600-99 20.5 FN359P-900-99 33
Note: When using CE standard Inverters, the special EMC-compatible Noise Filter is required. Contact your Yaskawa representative.
Drawing 1
Drawing 2
Dia.
Drawing 3
Drawing 4
75
IM
200 V Class
Inverter
CIMR-F7A=
Max Applicable Motor Output kW
Model
Rated Current A
Dimensions in mm
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110
LF-310 KA LF-310 KA LF-310 KA LF-310 KA LF-320 KA LF-350 KA LF-350 KA LF-350 KA LF-350 KA LF-350 KA LF-350 KA LF-3110 KB LF-350 KA LF-375 KB LF-3110 KB LF-3110 KB LF-3110 KB LF-3110 KB LF-3110 KB
10 10 10 10 20 50 50 100 100 100 150 110 150 150 220 330 440 440 550
Model LF-310 KA LF-320 KA LF-350 KA LF-310 KB LF-320 KB LF-335 KB LF-345 KB LF-375 KB LF-3110 KB
Terminal Plate TE-K5.5 M4 TE-K5.5 M4 TE-K22 M6 TE-K5.5 M4 TE-K5.5 M4 TE-K5.5 M4 TE-K22 M6 TE-K22 M6 TE-K60 M8
A
140 140 260 140 140 140 260 540 540
B
100 100 180 100 100 100 180 320 340
C
100 100 180 100 100 100 180 480 480
D
90 90 160 90 90 90 160 300 300
E
70 70 120 70 70 70 120 340 340
F
45 45 65 45 45 45 65 240 240
Mass kg
7 4.5 4.5 7 4.5 4.5 7 4.5 4.5 7 4.5 4.5 7 4.5 4.5 7 4.5 4.5 7 4.5 4.5 9 6.5 6.5 9 6.5 6.5
400 V Class
Inverter
CIMR-F7A=
Max Applicable Motor Output kW
Model
40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300
LF-310KB LF-310KB LF-310KB LF-310KB LF-310KB LF-320KB LF-320KB LF-335KB LF-335KB LF-345KB LF-375KB LF-375KB LF-3110KB LF-3110KB LF-375KB LF-3110KB LF-3110KB
Junction Terminal
R1 Noise Filter 1 1 R 4 U 2 S 5 V 3 T 6 W E
Junction Terminal
R2
MCCB
Varispeed F7
S1
Noise Filter 2 1 R 4 U 2 S 5 V 3 T 6 W E
R S2 S
T1
Noise Filter 3 1 R 4 U 2 S 5 V 3 T 6 W E
T2
Ground
When connecting noise filters in parallel, install junction terminals to equalize ground return. Ground wires for noise filter and inverter should be thick and as short as possible.
4 5 7
76
131 max
78 max
1241 74 min
501 95 max
26 max 12.50.3
201
26 max
25.5 Dia.
801
Mass: 195g
Mass: 620g
200 V Class
Model F6045GB
Model F11080GB
400 V Class
Inverter Finemet Zero-phase Reactor Recommended2 Recommended Wire Size m Model Model Code No. Qty. Wiring Method Input Side Output Side (Connection Diagram) 2 2 CIMR-F7A40P4 2 2 CIMR-F7A40P7 2 2 CIMR-F7A41P5 3 winds F6045GB FIL001098 1 2 2 CIMR-F7A42P2 Diagram (a) 3.5 3.5 CIMR-F7A43P7 3.5 3.5 CIMR-F7A45P5 5.5 5.5 CIMR-F7A47P5 8 8 CIMR-F7A4011 3 winds F11080GB FIL001097 1 Diagram (a) 8 8 CIMR-F7A4015 8 8 CIMR-F7A4018 14 14 CIMR-F7A4022 4 series F6045GB FIL001098 4 Diagram (b) 22 22 CIMR-F7A4030 38 38 CIMR-F7A4037 38 38 CIMR-F7A4045 50 50 CIMR-F7A4055 60 50 CIMR-F7A4075 F11080GB FIL001097 100 100 CIMR-F7A4090 4 series CIMR-F7A4110 502P 502P 4 Diagram (b) CIMR-F7A4132 802P 602P CIMR-F7A4160 1002P 802P CIMR-F7A4185 1502P1 1252P CIMR-F7A4220 2502P 2002P F200160PB 300-001-041 CIMR-F7A4300 1254P 1254P
1Use the F11080GB model finemet zero-phase reactor. 2Choose the wiring method that is appropriate for the size of cables being used.
R Power Supply S T
U V W IM
Power Supply
IM
77
Inverter Finemet Zero-phase Reactor Recommended2 Recommended Wire Size m Model Model Code No. Qty. Wiring Method (Connection Diagram) Input Side Output Side CIMR-F7A20P4 2 2 CIMR-F7A20P7 2 2 3 winds F6045GB FIL001098 1 CIMR-F7A21P5 2 2 Diagram (a) CIMR-F7A22P2 2 2 CIMR-F7A23P7 3.5 3.5 CIMR-F7A25P5 5.5 5.5 F11080GB FIL001097 1 3 winds Diagram (a) CIMR-F7A27P5 8 8 CIMR-F7A2011 14 14 CIMR-F7A2015 30 30 4 series F6045GB FIL001098 4 Diagram (b) CIMR-F7A2018 30 30 CIMR-F7A2022 30 30 CIMR-F7A2030 50 50 CIMR-F7A2037 60 60 F11080GB FIL001097 CIMR-F7A2045 80 80 4 series 100 CIMR-F7A2055 502P 4 Diagram (b) CIMR-F7A2075 802P 802P CIMR-F7A2090 1502P1 1002P 2002P 1502P1 F200160PB 300-001-041 CIMR-F7A2110 or 504P or 504P
217 max
155 min
42 max
7 14
Mass: 2260g
Model F200160PB
Can be used both for input and output sides of the inverter and effective on noise reduction.
Braking Unit
Inverter Voltage
Max. Model Applicable Motor Output CIMRF7A= kW
200V Class
400V Class
0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 220 300
20P4 20P7 21P5 22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055 2075 2090 2110 40P4 40P7 41P5 42P2 43P7 45P5 47P5 4011 4015 4018 4022 4030 4037 4045 4055 4075 4090 4110 4132 4160 4185 4220 4300
Braking Registor Unit1 Inverter-mounted Type (3 %ED,10 sec. max.)2 Separately-installed Type (10 %ED,10 sec. max.)3 Braking Model Model Model Braking Connectable Min. No. of Specifications No. of No. of Torque5 Diagram LKEB CDBR ERF- Resistance Code No. Torque5 Resistance Diagram Used of Resister Used Used Value4 == 150WJ= == 201 200 R007505 1 220 A 20P7 70 W 200 1 220 B 48 200 R007505 1 125 A 70 W 200 1 125 B 48 201 20P7 100 R007504 1 125 A 125 B 48 101 21P5 260 W 100 1 70 R007503 1 120 A 120 B 16 700 22P2 260 W 70 1 62 R007510 1 100 A 125 B 16 620 23P7 390 W 40 1 Built-in 520 W 30 1 115 B 25P5 16 780 W 20 1 125 B 27P5 9.6 125 B 2011 2400 W 13.6 1 9.6 125 B 2015 3000 W 10 1 9.6 100 B 2015 3000 W 10 1 9.6 1 2022B 125 C 2022 4800 W 6.8 1 6.4 2 2015B 125 D 2015 3000 W 10 2 9.6 2 2015B 100 D 2015 3000 W 10 2 9.6 2 2022B 120 D 2022 4800 W 6.8 2 6.4 100 D 2022 4800 W 6.8 2 6.4 2 2022B 110 E 2022 4800 W 6.8 3 1.6 1 2110B 120 E 2022 4800 W 6.8 4 1.6 1 2110B 100 E 2018 4800 W 8 5 1.6 1 2110B 40P7 70 W 750 1 230 B 751 96 750 R007508 1 230 A 40P7 70 W 750 1 130 B 96 750 R007508 1 130 A 751 41P5 260 W 400 1 125 B 64 400 R007507 1 125 A 401 42P2 260 W 250 1 135 B 64 300 R007506 1 115 A 301 43P7 390 W 150 1 135 B 32 200 R007505 1 110 A 201 Built-in 520 W 100 1 135 B 32 45P5 780 W 75 1 130 B 32 47P5 135 B 20 4011 1040 W 50 1 125 B 20 4015 1560 W 40 1 125 B 19.2 4018 4800 W 32 1 4030B 1 125 C 19.2 4022 4800 W 27.2 1 4030B 1 125 C 19.2 4030 6000 W 20 1 4045B 1 125 C 12.8 4037 9600 W 16 1 4045B 1 125 C 12.8 4045 9600 W 13.6 1 4030B 2 135 D 19.2 4030 6000 W 20 2 4045B 2 145 D 12.8 4045 9600 W 13.6 2 4220B 1 100 E 3.2 4030 6000 W 20 3 4220B 1 100 E 3.2 4030 6000 W 20 3 4220B 1 140 E 3.2 4045 9600 W 13.6 4 4220B 1 140 E 3.2 4045 9600 W 13.6 4 4220B 1 120 E 3.2 4045 9600 W 13.6 4 4220B 1 110 E 3.2 4037 9600 W 16 5 4220B 2 110 3.2 4045 9600 W 13.6 6 Braking unit
3Load factor during deceleration to stop a load with constant torque. With constant output or continuous regenerative braking, the load factor is smaller than the specified value. 4Resistance value per one braking unit. Select a resistance value that is larger than connectable minimum resistance value to obtain enough braking torque. 5For an application with large regenerative power such as hoisting, the braking torque or other items may exceed the capacity of a braking unit with a braking resistor in a standard combination (and result in capacity overload). Contact your YASKAWA representatives when the braking torque or any other item exceeds the values in the table. 6The CDBR-2045B and CDBR-4090B control units are also available. Contact your Yaskawa representative for details.
1When connecting a mounting type resistor or braking resistor unit, set system constant L3-04 to 0 (stall prevention disabled during deceleration). If operating without changing the constant, motor does not stop at set deceleration time. 2When connecting mounting type braking resistor, set system constant L8-01 to 1 (braking resistor protection enabled).
78
Connections
Braking Resistor
MCCB 3-phase Power Supply MCCB Motor Use sequencer to break power supply side on overload relay trip contact.
Varispeed F7
Motor
Varispeed F7
Set constant L8-01 to 1 (mounting type braking resistor protection enabled). Set sequence to shutt off the power side at inverter fault contact output.
MC MA
Fault Contact
Diagram A
Braking Unit Braking Resistor Unit3
Diagram B
Use sequencer to break power supply side on overload relay trip contact. MCCB 3-phase Power Supply
1 G F
Level Detector
Braking Resistor Overload Relay Trip Contact (Thermal Relay Trip Contact) Motor
Braking Resistor Overload Relay Trip Contact (Thermal Relay Trip Contact)
F G
Braking Resistor Overload Relay Trip Contact (Thermal Relay Trip Contact)
Varispeed F7
Level Detector
Varispeed F7
Braking Unit 22
MC MA
Fault Contact
Diagram C
Braking Unit Braking Resistor Unit3
Diagram D
Use sequencer to turn OFF the power supply for the thermal overload relay trip contacts of the Braking Resistor Unit.
Level Detector
Varispeed F7
Braking Resistor Unit (Overload Contact)
MC MA
Fault Contact
Diagram E
1200 V class inverters do not require control circuit transformer. 2When using more than one parallel-connected braking unit, connect and select connectors: Braking units have a MASTER/SLAVE selection connector. Select MASTER side only for braking unit 1 and select SLAVE sides for other braking units. 3Disable stall prevention during deceleration by setting L3-04 to 0 when using a Braking Resistor Unit. The motor may not stop within the deceleration time if this setting is not changed. 4When connecting an separately-installed type braking resistor unit (model CDBR) to inverters with built-in braking transistor (200 V/400 V 18.5 kW or less), connect the B1 terminal of the inverter to the + terminal of the braking resistor unit and connect the terminal of the inverter to theterminal of the braking resistor unit. The B2 terminal is not used in this case.
79
Braking Unit 1
Dimensions in mm
Braking Unit
Model CDBR-2015 B-2022 B-4030 B-4045 B
100 or more 4-M4 MTG Holes 72 66.5
38 30 or more
38 30 or more
128 140
138.5
100 or more
114.5
Model Heat Loss CDBR- _ W 32 2015B 38 2022B 64 2110B 54 4030B 59 4045B 71 4220B
138
150
105
20
100 Attachment
20
Model CDBR-2110 B
12 36.5 100 or less 9 36.5 140 4-M6 MTG Holes
370
355 317
25
104
Lead Wire Inlet (28 Dia. Rubber Bush) 2-lead Wire Inlet (35 Dia. Rubber Bush)
104
Lead Wire Inlet (28 Dia. Rubber Bush) 2-lead Wire Inlet (35 Dia. Rubber Bush)
150
73
10
70
156.5 118.5
50 30 or more
30 or more
140 180
30 or more
210 250
100 or more
100 140
260 280
210
100 or more
138.5
10
MTG Screw
150 or more
MTG Screw
150 or more
Voltage
A
105 130 130 130 250 250 105 130 130 130 250 250
Mass kg
3.0 4.5 4.5 5.0 7.5 8.5 3.0 4.5 4.5 5.0 7.5 8.5
275 350 350 350 350 350 275 350 350 350 350 350
Heat Loss W 30
60 89 150 220 300 30 60 89 150 220 300
200 or more
Voltage
Model LKEB-= 2011 2015 2018 2022 4011 4015 4018 4022 4030 4037 4045
A
266 356 446 446 350 350 446 446 356 446 446
Mass kg
10 15 19 19 16 18 19 19 25 33 33
543 543 543 543 412 412 543 543 956 956 956
200 V Class
200 V Class
400 V Class
400 V Class
80
Motor
Varispeed F7
When power capacity is significantly greater when compared to inverter capacity, or when the power-factor needs to be improved, connect the AC or DC reactor. DC reactor is built in models of 200 V class 22 to 110 kW 22 to 300 kW. AC reactor can be used at the same time for harmonic measure.
Take off the common bar between G1 and G2, and wire as shown in the diagram. Power Supply Capacity (kVA)
200 V Class
Max. Applicable Current Value Motor Output A kW
Inductance mH
8 3 1 0.5 0.4
X
85 86 105 105 133
Y2
80 90 105 120
Y1
36 46 56 52.5
Dimensions in mm Z B H K
53 76 93 93 117 74 60 64 64 86 55 18 80 26 100 26 80 25
G
32
1
M4 M4 M6 M6 M6
2
M5 M6 M8 M8
Approx. Mass kg
Loss W
8 18 22 29 45
5.4 18 36 72 90
Built-in
400 V Class
Max. Applicable Current Value Motor Output A kW
Inductance mH
28 11 6.3 3.6 1.9 1.3
X
85 90 86 105 105 115
Y2
80 90 95 125
Y1
36 46 51 57.5
Dimensions in mm Z B H K
53 60 76 93 93 100 74 80 60 64 64 72 55 18 80 26 90 26 90 25
G
32 32
1
M4 M4 M4 M6 M6 M6
2
M5 M5 M6 M6
Approx. Mass kg
Loss W
9 11 16 27 26 42
5.7 12 23 33 47
Built-in
: 75 , IV wire, ambient temperature 45 , bundle of max. 3 wires
Name Plate
H
60
Name Plate
2-Terminals (2)
B X
Drawing 1
Drawing 2
Y2
Y1
81
3.2
0.8
When using low noise type inverters (high-carrier frequency of 2.5 kHz or more), do not connect an AC reactor to the output side (U, V, W) of the inverter.
When power capacity is significantly greater when compared to inverter capacity, or when the power-factor needs to be improved, connect the AC or DC reactor. Select an AC
reactor according to the motor capacity. Standard Varispeed F7 is a DC reactor. It has built-in models of 200V class 22 to 110 kW and 400 V class 22 to 300 kW.
200 V Class
Max. Applicable Motor Output kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 Current Value A 2.5 5 10 15 20 30 40 60 80 90 120 160 200 240 280 360 500 500
Inductance mH
4.2 2.1 1.1 0.71 0.53 0.35 0.265 0.18 0.13 0.12 0.09 0.07 0.05 0.044 0.038 0.026 0.02 0.02
Code No.
X 002553 X 002554 X 002489 X 002490 X 002491 X 002492 X 002493 X 002495 X 002497 X 002498 X 002555 X 002556 X 002557 X 002558 X 002559 X 002560 X 010145 X 010145
Drawing
Dimensions in mm A
120 120 130 130 130 130 130 160 180 180 180 210 210 240 240 270 330 330
Mass
B
71 71 88 88 88 88 98 105 100 100 100 100 115 126 126 162 162 162
B1
114 119 139 147.5 155 150 155 170 182.8 218 218 241 286 286
C
120 120 130 130 105 105 105 130 150 150 150 175 175 2155 2155 2305 3155 3155
D
40 40 50 50 50 50 50 75 75 75 75 75 75 150 150 150 150 150
E
50 50 70 70 70 70 80 85 80 80 80 80 95 110 110 130 130 130
F
105 105 130 130 130 130 130 160 180 180 180 205 205 240 240 260 320 320
H
20 20 22 22 22 22 22 25 25 25 25 25 25 25 25 40 40 40
J
M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M8 M8 M 10 M 10
K
10.5 10.5 11.5 11.5 11.5 9 11.5 10 10 10 10 10 10 8 8 16 16 16
L
7 7 7 7 7 7 7 7 7 7 7 7 7 7 10 10 10 10
M
M4 M4 M4 M4 M5 M5 M6 M6 M8 M8 M 10 M 10 M 10 M 10 M 12 M 12 M 12 M 12
kW 2.5 2.5 3 3 3 3 4 6 8 8 8 12 15 23 23 32 55 55
Loss W
15 15 25 30 35 45 50 65 75 90 90 100 110 125 130 145 200 200
400 V Class
Max. Applicable Motor Output kW 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90/110 132/160 185 220 300 Current Value A 1.3 2.5 5 7.5 10 15 20 30 40 50 60 80 90 120 150 200 250 330
490 660
Inductance mH
18.0 8.4 4.2 3.6 2.2 1.42 1.06 0.7 0.53 0.42 0.36 0.26 0.24 0.18 0.15 0.11 0.09 0.06 0.04 0.03
6-M: Terminal
Code No.
X 002561 X 002562 X 002563 X 002564 X 002500 X 002501 X 002502 X 002503 X 002504 X 002505 X 002506 X 002508 X 002509 X 002566 X 002567 X 002568 X 002569 X 002570 X 002690 X 002691
Drawing
Dimensions in mm A
120 120 130 130 130 130 160 160 180 180 180 210 210 240 240 270 270 320 330 330
Mass
B
71 71 88 88 88 98 90 105 100 100 100 100 115 126 126 162 162 165 176 216
B1
115 132.5 140 145 150 150 177.5 193 198 231 231 253 293 353
C
120 120 130 130 130 130 130 130 150 150 150 175 175 2055 2055 2305 2305 2305 3155 3155
D
40 40 50 50 50 50 75 75 75 75 75 75 75 150 150 150 150 150 150 150
E
50 50 70 70 70 80 70 85 80 80 80 80 95 110 110 130 130 130 150 185
F
105 105 130 130 130 130 160 160 180 180 180 205 205 240 240 260 260 320 320 320
H
20 20 22 22 22 22 25 25 25 25 25 25 25 25 25 40 40 40 40 40
J
M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M6 M8 M8 M8 M8 M 10 M 10 M 10
K
10.5 10.5 9 9 11.5 11.5 10 10 10 10 10 10 10 8 8 16 16 17.5 13 15.5
L
7 7 7 7 7 7 7 7 7 7 7 7 7 10 10 10 10 12 12 18
M
M4 M4 M4 M4 M4 M4 M5 M5 M6 M6 M6 M8 M8 M 10 M 10 M 10 M 10 M 12 M 12 M 16
Loss W
15 15 25 35 40 50 50 65 90 90 90 95 110 130 150 135 135 200 340 310
6-M: Terminal
3 4
6-M: Terminal
U X V Y W Z
Name Plate
2-M8 Eyebolts
Name Plate
Name Plate
U C V W C U V W C U V W C X Y Z 4.5 H E B B1 D F A H 4.5 D F A
Z X Y Z
4.5
D F A L
H E B
D F A L K
4.5
H E B B1
E B B1
Drawing 1
Drawing 2
Drawing 3
Drawing 4
82
VS Operator
Standard Steel Plate Type
Product Series
Model JVOP JVOP-961 JVOP-962 JVOP-963 Code No. 73041-0906X-01 73041-0906X-02 73041-0906X-03 Frequency Meter Specifications DCF-6A 3 V 1 mA 75 Hz DCF-6A 3 V 1 mA 150 Hz DCF-6A 3 V 1 mA 220 Hz
Meter Adjusting Potentiometer Freq. Setting Potentiometer Power Indication Lamp Run Fault
Frequency Meter
Dimensions in mm
Master/Aux Freq. Reference Switch
Mounting Space for Faceplate
250
Run/Stop Switch
24
40 60 100
2 4-7 Dia. MTG Holes 2-23 Dia. Rubber Bush 100 122 max. 24 85 2-4 Dia.
Mass1.8 kg
Product Series
Model JVOP JVOP-951 JVOP-952 Code No. 73041-0905X-01 73041-0905X-02 Frequency Meter Specifications TRM-45 3 V 1 mA 60/120 Hz TRM-45 3 V 1 mA 90/180 Hz
Dimensions in mm
10 5 3.5 17 17 Mounting Space for Faceplate Hole for Operator Panel 130 140 150 157 132 140 14.5 5 31.5 87 50.5 55.5 11 70 92 11 3-M3 Tapped Holes 4 4
Digital Operator
LCD Monitor LED Monitor
Mass0.8 kg
Panel Cutout
57
120
120 111
14.5 2.5
44 Through Hole 70 20
70
15.8
6.4 60
83
70 90 95
10 5 3.5
220
230
Scale
75 Hz full-scale: Code No. FM000065 60/120 Hz full-scale: Code No. FM000085
Mass0.3 kg
Resistance 2 k 20 k
Mass20 g
Dia.
Shaft 6 Dia.
Mass0.2 kg
Scale Plate
Code No. NPJT41561-1
3.6 Dia. in mm
Output Voltmeter: Code No. VM000502 Transformer for Instrument: Code No. PT000084
in mm 4-5 Dia.
9.5 Dia.
85 Dia.
Potential Transformer
(Model UPN-15B)
15 VA 440/110 V400/100 V50/60 Hz
M3.5 Screw Terminal
in mm
Name Plate
Mass2.3 kg
Grounding Point 4-M5 MTG Holes
84
Wiring Connections
Input
Terminal 1 2 3 4 5 6 7 8 Description Output Output Input Input Grounding Power supply
Product Line
Model DGP2-4-4 DGP2-4-8 DGP2-8-4 DGP2-3-4 DGP3-4-4 DGP3-4-8 DGP3-8-4 DGP3-3-4 Input Signal Output Signal Power Supply
0 to 10 V 0 to 10 V 4 to 20 mA 0 to 5 V 0 to 10 V 0 to 10 V 4 to 20 mA 0 to 5 V 0 to 10 V 4 to 20 mA 0 to 10 V 0 to 10 V 0 to 10 V 4 to 20 mA 0 to 10 V 0 to 10 V 100 VAC 100 VAC 100 VAC 100 VAC 200 VAC 200 VAC 200 VAC 200 VAC
Code No.
CON 000019.25 CON 000019.26 CON 000019.35 CON 000019.15 CON 000020.25 CON 000020.26 CON 000020.35 CON 000020.15
Cable Length
4 to 20 mAWithin 100 m 0 to 10 V Within 50 m
Dimensions in mm
Model DGP Series
Approx. Mass
DGP Series350 g Socket 60 g
Adjuster
Backup Capacitor Unit for Momentary Power Loss (Applicable to models of 0.4 to 11 kW (200 V/400 V Class))
, Use this unit for 11 kW or less to extend the inverter s power loss ride-thru ability to 2 seconds. 200 to 230 V Model P0010 Connection with Inverter Dimensions in mm 380 to 460 V Model P0020
N B1/P E
90 50
96
Motor
300 280
IM
Mass2 kg
, : When this unit is not used, the inverter s power loss ride-thru ability is 0.1 to 1 second.
4-M6MTG Screws
85
Socket
Linear acceleration/deceleration control provides smooth, uniform speed change during starting and stopping and during speed increase and decrease. Accel/decel time adjustable in 1.5 to 30 sec with A and 5 to 90 sec with B.
Operator
A1 Freq. AC Ref. E 0 to 10 V G
5 Sets or less
Converts the current signal 4 to 20 mA of master setter JVOP-031 to voltage signal and sets five types of ratios and biases.
Varispeed F7
Power Supply Motor
Transforms the frequency signal 0 to 2 kHz of master setter JVOP-041 to voltage signal and sets five types of ratios and biases.
Operator
A1 Freq. AC Ref. 0 to 10 V E G
Varispeed F7
Motor
A1 Freq. AC Ref. E 0 to 10 V G
Transforms master speed signals such as AC voltage signal (200 VAC), AC tach-gen signal (30 VAC) or DC voltage signal (10 VDC) to DC voltage. It can set five types of ratios and biases.
Varispeed F7
Power Supply Motor
A1 AC E G
Freq. Ref. 0 to 10 V
Transforms frequency signal from AC tachgen to voltage signal and sets five types of ratios and biases.
Varispeed F7
Motor
A1 AC AC Tach-gen
E 0 to 10 V G
Freq. Ref.
JGSM-05
86
Name (Model)
Appearance
Function
Application
Dancer Roller
Varispeed F7
Power Supply
Displacement Detector
A1 Freq. AC Ref.
Motor
Synchronizes displacement detector YVGC500W1 in proportion to rotary angle to permit change to DC voltage signal. Signal mixing function to take out deviation signal is available.
0 to 10 V
E G
Speed Setting
Angle/ Voltage
JGSM-06 Varispeed F7
Power Supply Operator (Ref.)
A1
Motor
Independently sets ratio gain, integral and differential time for the simple process control. Integral reset, stepless operation, and windup functions are available.
AC Ref. E G 0 to 10 V
Freq.
(Feedback)
Varispeed F7
Motor
Preamplifier (JGSM-09-==)2
Amplifies both the power of DC input signal and output of snap-in function modules JZSP-11 to 161 when inserted.
Operator
A1 Freq. AC 0 to 10 V E G
Ref.
JGSM-09-
Varispeed F7
Power Supply Ope. Sw. 1 Motor
Logic Circuit
Executes UP or DOWN command from remote control type VS operator model JVOP-101 by lowering or raising reference voltage.
Ope. Sw. 2
UP DOWN QUICK STOP
A1 Freq. Ref. AC 0 to 10 V E G
Ope. Sw. 3
Accel Decel
JGSM-10B
87
Power Supply
Name (Model)
Appearance
Function
Application
Varispeed F7
Power Supply Operator Motor
(offset)
Ref.
AC 0 to 10 V E G
Varispeed F7
Consists of power supply circuit and two relay circuits. Used as a selector circuit of control signals.
Power Supply
A1 Freq. AC Ref. E 0 to 10 V G
Motor
Contains three relay circuits. Used as a selector circuit of control signals. Power supply from model JGSM-13.
4 to 20 mA Process Detector
Comparator 1
High
Comparator 2
Comparator (JGSM-15-==)2
Compares DC voltage, current, AC tachgen, frequency, or reference signals with two preset levels. It drived relays and output contact signal (1NO, NC contact.)
Varispeed F7
Power Supply Motor
Converts DC voltage input signal to current signal of 4 to 20 mA which can be connected to instrument. Insertion of snapin module can determine input signals such as frequency or tach-gen.
Operator
A2 Freq. Ref. AC 4 to 20 mA E G
JGSM-16-
88
Name (Model)
Appearance
Function
Power Supply
Application
Varispeed F7
Motor
Converts BCD 3-digit or 12 bits binary digital signals to 0 to 10 V analog signals with high accuracy. Model JGSM-18: BCD 3-digit input type Model JGSM-19: 12 bits binary type
A1 AC E G
JGSM-19 JGSM-21
( (
) )
In addition to the functions of model JGSM10B (remote setting device), wide application is offered through the command value maintenance function at power failure, the variable acceleration/deceleration function that allows external setting times, and the analog tracking function. The two system modules must always be used together to configure the static potentiometer.
Logic Circuit
QUICK STOP
Freq. Ref.
To Terminal Accel Decel To Terminal Power Supply
UP DOWN
Generator
To Logic Circuit
Accel Decel
JGSM-22
Model
JZSP-00
JZSP-12
I/V converter
JZSP-13
F/V converter
JZSP-14
Tach-gene follower
JZSP-15
140 max.
JZSP-16 ==
Mass0.8 kg
Signal mixer
89
1Available as Yaskawa standard. 2== shows model of VS snap-in function modules. 3== indicates model of impedance. Note: Both 200/220 V at 50/60 Hz are available as standard. Use a transformer for other power supplies.
Notes
Application of Inverter
Selection
Power Supply
Setting Reactor
Use a DC reactor or AC reactor (option) on the inverter input side when the inverter is connected directly to a largecapacity power transformer (600 kVA and more within 10 m distance) or when a power factor improvement capacitor is switched. Otherwise excess peak current may occur in the power feed circuit and the converter section may be damaged. DC reactor is built in 22 to 110 kW, 200 V class inverters and 22 to 300 kW, 400 V class inverters. An AC reactor is also required when a thyristor converter such as a DC drive is connected to the same power system.
4000 DC or AC reactor required 600 0 DC or AC reactor not required 60 400 Inverter Capavity (kVA)
kVA
When a special motor is used or more than one motor are driven in parallel with a single inverter, select the inverter capacity so that 1.1 times of the total motor rated current does not exceed the inverter rated output current. The starting and accelerating characteristics of the motor driven by an inverter are restricted by the overload current ratings of the inverter. Compared to running with commercial power supply, lower torque output should be expected. If high starting torque is required, use an inverter of higher capacity or increase the capacities of both the motor and the inverter. When an error occurs, a protective circuit is activated and the inverter output is turned OFF. However, the motor cannot be stopped immediately. Use a mechanical brake and hold the equipment for a fast stop if necessary. Terminals B1, B2, F, G 1, G 2, G 3 are for YASKAWA options. Do not connect equipment other than YASKAWA options.
Installation
Installation in Enclosures
Avoid oil mist or dust. Place the inverter in a clean area or house it in a totally-enclosed case so that no contamination enters. To use the totally-enclosed case, select the cooling method and panel dimensions so the inverter ambient temperature will be within the allowable range. Do not install the inverter on flammable material, such as wood. Install the inverter on a wall with the longer side in the vertical position.
Installation Direction
Setting
Upper Limits
The inverter can be driven at an output frequency of up to 400 Hz with the digital operator. Setting errors may create a dangerous situation. Set the upper limit with the upper limit frequency setting function. (Maximum output frequency in external input signal operation is preset to 60 Hz at the factory.) Large DC injection braking operating currents and times may cause motor overheating. Motor accel/decel time is determined by the motor generating torque, load torque, and load inertia GD2/4. If the stall prevention function is activated during accel/decel, set the accel/decel time longer. After the stall prevention function is activated, the accel/decel time is extended to a length that the inverter can handle. To shorten the accel/decel time, increase the capacity of the inverter and possibly the motor. Applying power to inverter output terminals U, V, or W will damage the inverter. DOUBLE CHECK WIRING AND SEQUENCE BEFORE TURNING THE POWER ON. If magnetic contactor (MC) is used on the primary side of the inverter, do not use the MC for starting and stopping the inverter frequently. Otherwise, the inverter life may be reduced. After turning power to the inverter OFF, electric charges in the internal capacitors are retained temporarily. Wait until the charge LED goes off before touching the inside of the inverter. Use round pressure terminal when wiring UL and C-UL listed inverters. Caulking should be done by the caulking tools specified by terminal manufactures. Do not subject the inverter to halogen gases, such as fiuorine, chlovine, bromine, and iodine, at any time even during transportation or installation.
Operation
Wiring Check Magnetic Contactor Installation Maintenance and Inspections Wiring Others 90
91
Notes
Application of Motors
Application to Existing Standard Motors
Low Speed Range
A standard motor driven by the inverter generates slightly less power than it does when it is driven with commercial power supply. Also, the cooling effect deteriorates in low speed range causing a motor temperature to rise. Therefore, reduce load torque in the low speed range. Allowable , load characteristics of Yaskawa s standard motor are shown in the figure. If 100 continuous torque is required in the low speed range, use an inverter duty motor.
25ED (or 15 min.) 40ED (or 20 min.) 60ED (or 40 min.) 100 90 80 70 60 Torque 50
()
Continuous
36 20 60
Frequency (Hz)
If the input voltage is high (400 V or higher) or the wiring distance is long, the motor insulation voltage must be considered. Contact your YASKAWA representative for details. When the motor is used above 60 Hz, motor type should be verified. Contact your motor source.
Motor torque characteristics vary when the motor is driven by an inverter instead of commercial power supply. Check the load torque characteristics of the equipment to be connected. (For torque characteristics of inverter operation.) Because of the high carrier modulation technique for PWM control, the Varispeed F7 series reduces motor vibration to a level equal to operating with a commercial power supply. Greater vibrations may occur under the following conditions:
Noise
Inverter operation is as quiet as when operating with commercial power supply. At above rated speeds (60 Hz), motor noise may increase when cooling fan is operating.
Geared Motors
Lubrication method and continuous rotation limit differ with manufacturers. When oil lubrication is employed, continuous operation in low speed range may cause burnout. Before operating the motor at more than 60 Hz you should consult the motor manufacturer.
92
Synchronous motor is not suitable for inverter control. If a group of synchronous motor is individually turned ON and OFF, synchronism may be lost. Single-phase motors are not suitable for variable speed operation with an inverter. If the inverter is applied to a motor using a capacitor stack, a high harmonic current flows and the capacitor may be damaged. For split-phase start motors and repulsion start motors, the internal centrifugal switch will not be actuated and the starting coil may burn out. Therefore, use only 3-phase motors. Uras vibrator is a vibration motor which gets power from centrifugal force by rotating unbalance weights on both ends of the shaft. When driving by inverter, select inverter capacity considering followings. For details, contact your YASKAWA representative. 1Uras vibrator should be used at inverter rated frequency or less. 2V/f control should be used. 3Set acceleration time 5 to 15 sec because load inertia of uras vibrator is 10 to 20 times of motor inertia.
Note: When the acceleration time is less than 5 s, select inverter capacity. Contact your YASKAWA representative for details.
Uras Vibrators
4Inverter might not start due to undertorque because eccentric moment torque (static friction torque at start) is too large.
Use brake-equipped motors with an independent power supply. Connect the brake power supply to the inverter primary side. When the brake operates (motor stops) it turns the inverter output OFF. Some types of brakes may make abnormal sounds in low speed range.
93
Notes
Supplements
Inverter Capacity Selection
Load type
Load Characteristics
Load characteristics
Continuous operation Long-time operation at midium or low speeds Short-time operation Maximum required output (instantaneous) Constant output (continuous) Maximum Rated min-1 min-1
Rated min-1
Power supply transformer capacity percentage impedance Voltage fluctuations Number of phases, single phase protection Frequency Mechanical friction, losses in wiring Duty cycle modification
Required output for the load within the allowable range Motor capacity within the inverter ratings Current within the inverter ratings
{1 n {
nS
T
( kS 1 )
} }
{1 n {
nS
T
( kS 1 )
} }
n T I M
nS 1 nT( kS 1 )
nS n T I M 1 n T ( k S 1 )
Inverter capacity [kVA]
94
Linear motion
SI Units (International Units) W
Motor r
TM TL
60 PM 2 NM
103Nm
NM GD2M
V Po TA TB J L JL
N NM
J kgm
2
GD 2L
N NM
GD 2kgm2
V NM
1 W 4
V NM
GD 2L W
1 GD 2L 4
W0.1013
NM
Rotary motion
SI Units (International Units) T N TM TL PO NM GD2M ta td
60 PM 2 NM 103Nm
Motor r
N T Nm NM 2 T N 3
60
NM N NM T N
974
2
kgm
T kgm kW
10
kW
PO ta td
2 J M J L NM s 60 TM TL 2 J M J L NM s 60 TM TL
GD M GD 2L NM s 375 TM TL GD 2M GD 2L NM s 375 TM TL
J L
N 2 J kgm2 NM
GD 2L
N NM
GD 2kgm2
PO Running power r TM Motor rated torque e e ) TL Load torque (reflected to motor shaft) T Load torque (load axis) ) PM Motor rated output t t t t NM Motor rated speed d d N Load axis rotation speed d d NM Motor axis rotation speed d V Load speed d d W Mass of load d
Accel torque factor r r1.0 to 1.5 5 Regenerative braking factor, without braking r r r r r resister rLess than 0.2 2
with braking r r resister r0.3 to 1.5 5
PC1 Continuous capacitykVA kS Motor starting current/motor rated current nT Number of motors in parallel nS Number of simultaneously started motors GD 2 Total (GD2 ) reflected into motor shaftkgm2 TL Load torqueNm
95
Supplements
Terminology
1Vector Controls
Current vector: Directly controls the flux current and torque current that generates motor flux and torque. The primary current size I 1 and phase I2 I1 and controlled simultaneously. Flux current Im = I 1 cos Torque current I 2 = I 1 sin (Motor torque = kImI 2) Im Since this control directly affects the final target torque, response is fast and precision is high. Voltage vector: Indirectly controls the motor flux and torque via the voltage.
Voltage Motor Primary Circuit Flux Current Torque Current Motor Flux Torque
6High Harmonics
Harmonic input distortion can be minimized by attaching AC reactor to the input side or DC reactor in the main circuit. The Varispeed F7 models of 22 kW or more come equipped with a built-in DC reactor. When 12-pulse input option is utilized, current distortion is much more improved.
7Leakage Current
Current leak always occurs when voltage is applied to any component, even if it is insulated. The PWM inverter includes high frequency components in the output voltage, especially increasing the leak current that flows through the floating capacity of the circuit. However, leakage current of high frequency (of some kHz) presents no hazard to personnel.
This control can be equivalent to the current vector if the primary circuit of the motor is known completely, but this is actually difficult since the temperature of the resistance also changes.
2Auto-tuning
Auto-tuning in the Varispeed F7, allows automatic measurement of motor constant necessary for vector control. As a result, this function changes the vector control drive not only for YASKAWA motors but for any other existing motor into an outstanding performance drive.
8Noise
Noise may be generated when the inverter operates, affecting peripheral electronic devices. The transmission mediums of this noise are air (as electric wave), induction from the main circuit wiring, power source lines, etc. The noise that is transmitted through the air, affecting surrounding electronic devices is called radio noise. The noise can mostly be prevented by enclosing each inverter in a metallic cabinet, ensuring adequete grounding, or separating electronic circuits from the magnetic cabinet. However, a noise filter may sometimes be required to reduce noise interference to an acceptable level.
4Regenerative Braking
The motor is operated as a generator, converting mechanical energy into electric energy, to generate braking force while feeding back energy to the inverter or power supply. The energy is fed back to the smoothig capacitor within the inverter under regeneration status (the motor is under regenerative braking status), where it its absorbed or consumed as motor loss.
96
Service Network
7 Frankfurt
San Francisco Los Angels
8 9
1
Chicago
10 11 14 13
2 4
12
3 5 6 15 Sydney
Melbourne
Region
Service Area
Service Location Chicago(HQ) Los Angeles New Jersey Boston San Francisco, Ohio North Carolina Mexico City
Service Agency
Telephone/Fax
North America
U.S.A
Headquarters 1 1-847-887-7303 FAX 1-847-887-7070 1 FAX 1 FAX 1 FAX 1 FAX 1 FAX 52-5593-28-69 52-5651-55-73 55-11-5071-2552 55-11-5581-8795 57-91-635-7460 57-91-611-3872 598-2-402-3913 598-2-402-2514 54-11-4918-2013 54-11-4918-8120
Mexico South America South America Colombia Uruguay Argentina All of Europe and South Africa
2 3
PILLAR MEXICANA. S.A. DE C.V. YASKAWA EL ECTRICO DO BRASIL COM ERCIO LTD.A. VARIADORES LTD. A. ISAI S. R. L AUTOROL S.A.C.I.A.F.e.l. YASKAWA Electric EUROPE GmbH YASKAWA ELECTRIC KOREA Co. YASKAWA ENGINEERING KOREA Co. YASKAWA ELECTRIC (SHANGHAI) Co., Ltd. YASKAWA ELECTRIC TAIWAN Co. YASKAWA ELECTRIC (SINGAPORE) Pte. Ltd. YASKAWA ENGINEERING ASIA-PACIFIC Co., Ltd. LARSEN & TOUBRO LIMITED
~ Sao Paulo
Santafe De Bogota Montevideo Bueno Aires
4 5 6
Europe
Frankfurt
Headquarters 1 49-6196-569-300 FAX 49-6196-569-398 1 82-2-784-7844 FAX 82-2-784-8495 1 82-2-3775-0337 FAX 82-2-3775-0338 1 86-21-5353-1154 FAX 86-21-5385-3299 1 886-2-2502-5003 FAX 886-2-2505-1280 1 FAX 1 FAX 65-6282-3003 65-6289-3003 66-2-693-2200 66-2-693-2204 Service Network
South Korea
Seoul
9
10
11 12
13
14
Oceania
Australia
15
97
Varispeed F7
IRUMA BUSINESS CENTER
480, Kamifujisawa, Iruma, Saitama 358-8555, Japan Phone 81-4-2962-5696 Fax 81-4-2962-6138
BEIJING OFFICE
Room No. 301 Office Building of Beijing International Club, 21 Jianguomenwai Avenue, Beijing 100020, China Phone 86-10-6532-1850 Fax 86-10-6532-1851
TAIPEI OFFICE
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan Phone 886-2-2502-5003 Fax 886-2-2505-1280
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade LITERATURE NO. KAE-S616-55F Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply. Printed in Japan December 2004 01-4 5 Specifications are subject to change without notice 04-8 for ongoing product modifications and improvements. Printed on 100% recycled paper with soybean oil ink. 2001-2004 YASKAWA ELECTRIC CORPORATION. All rights reserved.