Você está na página 1de 4

Model: ACUM210 Diesel Generator Set

FEATURES
Armstrong provides one-source responsibility for the generator system and its accessories. All units and components are factory tested during prototype and manufacturing stages assuring long product life. Generator set accepts one-step 100% of full load per NFPA 110. A one-year limited warranty covers all systems and components. Extended warranties are available. Rugged 4 cycle heavy-duty diesel engine, with swirl intake ports for a low fuel consumption and excellent transient response. Generator features: Unique Volts per Hertz compensated electronic AVR excitation system delivers reliable voltage response for in rush loads. Brushless, rotating-field generator has low reactance, 2/3 pitch, class H insulation, minimizes voltage distortion when powering non-linear loads. More features: Controllers are available to meet your most demanding applications. In the event of low oil pressure or high coolant temperature the self-protecting system will automatically stop the engine.

GENERATOR SET RATINGS


Model ACUM210 ACUM210 ACUM210 ACUM210 ACUM210 ACUM210 ACUM210 ACUM210 ACUM210 ACUM210 Volt Code 61 63 64 65 66 67 51 53 55 57 Voltage 480 / 277 440 / 254 240 / 139 220 / 127 208 / 120 240 / 120 415 / 240 380 / 220 220 / 127 220 / 110 Winding Connection 12 - HI WYE 12 - HI WYE 12 HI DELTA 12 LOW WYE 12 LOW WYE 12 2 DELTA 12 HI WYE 12 HI WYE 12 LOW WYE 12 2 DELTA Phase 3 3 3 3 3 1 3 3 3 1 Power Factor 0.8 0.8 0.8 0.8 0.8 1.0 0.8 0.8 0.8 1.0 Hz 60 60 60 60 60 60 50 50 50 50 Amps Standby 313 342 626 683 723 867 325 356 614 850 Standby kW / kVA 208 (260) 208 (260) 208 (260) 208 (260) 208 (260) 208 (208) 181 (226) 181 (226) 181 (226) 181 (181) Prime kW / kVA 187 (233) 187 (233) 187 (233) 187 (233) 187 (233) 187 (187) 162 (202) 162 (202) 162 (202) 162 (162)

Stand-By ratings are continuous electrical service during the interruption of normal power. No overload capacity is specified at these ratings. Prime ratings available with variable loads are continuous, 10% overload capacity for one hour in twelve hours periods. Both ratings per BS 5514, DIN 6271, ISO-3046 Many industrial, commercial and residential voltages are available

ACUM210

ALTERNATOR SPECIFICATIONS
Type Rotor Insulation Temperature Rise Material Line-To-Line Harmonic Factor (Max) Telephone Interference Factor (Tif) Voltage Regulator Cooling Bearing Coupling Load Capacity (Standby) Overload Capacity (Prime) Voltage Regulation No Load To Full Load One Step Load Acceptance Per NFPA 110 1 % 100% Four pole, revolving field Class H 150C Standby Epoxy resin 5% 1% Solid State Self-ventilated and drip proof 1 each, pre-lubed Direct, Flexible Disc 100% 110%

Four pole, revolving field, direct coupled to engine flywheel, provides excellent alignment. Insulation is of class H, ready to be used on harsh environments where sea spray, sand and chemical corrosion are existing factors. Voltage regulator provides Volts/Hertz compensation to improve the motor starting capabilities, therefore support the engine handling transient loads. Dynamically balanced rotor, with damper winding, help dissipate transient voltage interference during load variations. The windings have a 2/3 pitch in order to reduce the harmonic content of voltage. Robust mechanical structure permits easy access to connections.

ENGINE SPECIFICATIONS
Manufacturer Model Bore Stroke Number Of Cylinders Piston Displacement Compression Ratio Combustion System Engine Type Aspiration Engine Crankcase Vent System Cylinder Crankshaft Material Governor Type Frequency Regulation No Load To Full Load Air Cleaner CUMMINS 6CTAA8.3-G1 4.49 in (114 mm) 5.32 in (135 mm) 6-Cylinder 505 in3 (8.3 L) 16.8:1 Bosch P3000 Direct Injection 4-Cycle; In-line Turbocharged and charge air cooled Closed Borable Forged Steel Mechanical 5% Dry Element Powered By:

Robust industrial grade CUMMINS diesel engine, for reliable endurance. Direct fuel injection system and swirl intake ports combine for a low fuel consumption and excellent transient response. Cylinder Head provides superior airflow through specially designed intake manifold ports, large valves and seats resulting in superior engine performance in torque reserve, fuel consumption and emissions. Extra strong engine block with provisions for overhaul. Dynamically Balanced Crankshaft, with induction-hardened journal surfaces significantly increases wear life.

Heavy-duty Cummins engines are known for their fuel efficiency, responsive transient performance and rugged reliability

STANDARD EQUIPMENT
ENGINE - Air Cleaner - Fuel Pump - Fuel Filter - Oil Pump - Full Flow Oil Filter - Jacket Water Pump - Thermostat and Housing - Exhaust Manifold Dry - Oil Cooler - Blower Fan & Fan Drive - Radiator - Unit Mounted - Electric Starting Motor 12v - Housing & Flywheel - Charging Alternator - 12v - Battery Kit & Battery Rack GENERATOR - Synchronous, Brush-less - Four Pole - Single Bearing - Direct Coupled With Flex - Class H Insulation - Drip-Proof Construction CONTROL PANEL - - Electric Hour Meter - Stop-Manual-Auto Pushbuttons - Standard Engine Control Monitoring - Automatic Shutdowns * High Water Temperature * Low Oil Pressure *Protective 12vdc Circuit Breaker -Display Lights For: * Water Temperature * Oil Pressure * Overcrank * Underspeed * Overspeed * Battery Charging GENERAL - Industrial Muffler -- Rain Cap - Integrated Fuel tank - In Frame Lifting Points - Acrylic Enamel Paint

ACUM210

INSTALLATION AND APPLICATION DATA


Type of Operation and Application 60 Hz 50 Hz Prime Standby Prime Standby 1800 285 (213) 248 (1710) 317 (237) 276 (1902) 245 (183) 213 (1470) 1500 272 (203) 237 (1632)

Item Rated Speed Engine Gross Engine Output BMEP Mean Piston Speed Ambient Air Temperature Engine Heat Reject to Coolant Cooling System Coolant Capacity Standard Thermostat Range Maximum Pressure Cap Maximum coolant friction Maximum fuel flow Fuel Type Fuel System Fuel Consumption @ 25% Power Fuel Consumption @ 50% Power Fuel Consumption @ 75% Power Fuel Consumption @ 100% Power Combustion Air Flow Air Intake Restriction clean filter Air Requirement Air Intake Restriction dirty filter Exhaust Temperature Maximun Allowable Back Pressure Maximum oil temperature Oil Pan Capacity Lubrication System Total Engine Oil Cap. w/filter Oil Filter Type Lube oil specifications grade Battery Charging Alternator Engine Electricals Baterry Charging Alternator Recommended Battery Cold Crank Starter Motor

Units rpm bhp (kWm) psi (kPa) Ft/s (m/s) F (C) BTU/min (kW) Gal (L) F (C) Psi (kpa) Psi (kpa) gal/h (L/h)

26.57 (8.1) 122 (50) 4250 (74) 4725 (83)

22.30 (6.8)

4090 (72)

4420 (78)

3.25 (12.3) 180-203 (82-95) 10 (69) 5 (35) 55 (208) Diesel #2 4(28)

gal/hr (L/hr) gal/hr (L/hr) gal/hr (L/hr) gal/hr (L/hr) ft3/min (L/s) In.H2O (kPa) In.H2O (kPa) F (C) In.H2O (kPa) F (C) gal (L) gal (L)

3.39 6.78 10.18 13.57 610 (289)

3.77 7.55 11.32 15.09 666 (314)

2.89 5.78 8.67 11.56 425 (200)

3.21 6.42 9.63 12.83 465 (220)

10(2.49) 25 (6.22) 886 (474) 920 (493) 1037 (553) 1059 (571)

3 (10.13) 250 (121) 5.0 (18.9) 6.3 (23.8) Cartridge SAE 15W - 40

Volts, Ground Rated amps CCA amps Volts, Ground

12V, negative 55 1200 / 0 F 18 C 12V, negative For 1800 RPM: 4% per 1000 ft (300 m) and 3.3% per 10F (6% per 10C) For 1500 RPM: 4% per 1000 ft (300 m) and 8.3% per 10F (15% per 10C)

Operation

Temperature and Altidtude Losses

ACUM 210

OPTIONAL EQUIPMENT
Cooling System Remote Radiator Jacket Water Heater Crankcase Oil Heater Fuel System Fuel/Water Separator Auxiliary Fuel Pump Sub-Base Fuel Tank Double Wall UL Listed Start System Battery Nicad Battery Warmer Plate Battery Charger Automatic Float Equalizing Trickle Switchgear Main Line Circuit Breaker Shunt trip Auxiliary switch Automatic Transfer Switch Paralleling Protective Relays Generator Permanent Magnet Excitation Space Heaters Temperature Rise Detectors Control Panel NFPA 110 Ready Remote Annunciation Panel Audible Alarm General Aluminum enclosure Sound attenuation kit Spring vibration isolators Interior lights AC or DC Trailer Export Packaging Special Testing Warranties ____ Year For Other Options Consult

DIMENSIONS AND WEIGHT


Units Length Width Height Weight In. (mm) In. (mm) In. (mm) Lbs (kg) Open Unit 105 (2667) 41.5 (1054) 57 (1448) 3654 (1657) Enclosed Unit 105 (2667) 41.5 (1054) 66 (1676) 3828 (1736) Sound Att. Unit 130 (3302) 41.5 (1054) 66 (1676) 3912 (1174)

General configuration for reference only, do not use these dimensions for installation purposes. Contact your local dealer for certified drawings.

All Specifications and Materials are subject to change without prior notice.

ARMSTRONG POWER SYSTEMS LLC Phone (305) 470-0058 Fax (305) 470-0068 Toll Free (800) 238-0732 th Address: 8254 NW 58 St, Miami Fl 33166 Email: sales@armstrongpower.com www.armstrongpower.com