, , , , . This document is the informational asset of Doosan Heavy Industries & Construction. Thus, unauthorized access, revision, distribution and copying of this document are strictly prohibited.
Index
Power Receiving Concept Power Receiving for Block Power system Block MV SWBD Scheme & Power distribution Power Receiving for Common Power system Common MV SWBD Scheme Common MV SWBD Power distribution Components of each Electrical System
- Gas Insulated Switchgear - Unit Auxiliary Tr - Isolated Phase Busbar - Generator Step-up Tr - UPS & Battery - MV Switch Board - LV Switch Board
Common
CB 4000A
CB 4000A (N.O)
MV SWBD 4.16KV
CB 1250A (N.O)
LV SWBD 480V
Normally UAT Incomer (4000A) & Bus section(4000A) CB will remain close to receive power at normal operation.
QOC Tie CB(1250A) and QCC Tie CB (4000A) will remain open for back-up stand-by. Once Block-1 power failure from grid, HSBT will close QCC Tie and open UAT incomer. Bus section CB will remain close. QOC Tie CB(1250A) will be an emergency backup from open cycle.
UAT Incomer
B/S
Power distribution
QCC Tie
QOC Tie
ST#4 18/13.8KV
MV SWBD 13.8KV
From Open Cycle SAT #3&4 13.8/4.16KV CB 4000A MV SWBD 4.16KV 1600A SAT#6 13.8/4.16KV
CB 1250A
Power Source
Back-Up Main Power Flow
B/S
IC-A IC-B
When black out condition, this SWBD receives power from open cycle. (Two Tie CB 1600A)
Once each block power fail, this SWBD gives power to each block 4.16KV unit SWBD.
IC-A
IC-B
Normally this SWBD Incomer CB (1250A) 1&2 receives power from 13.8KV SWBD via SAT 5&6. When emergency condition, this SWBD receives power from 4.16KV Station SWBD.
6
VOLTAGE TRANSFORMER
DISCONNECTOR
EARTHING SWITCH
CURRENT TRANSFORMER
CIRCUIT BREAKER
Flexible Braids
LV Side
Conservator Tank
Tap Changer
HV Side
Temperature gauges
MS 3000
Control Cabinet
Buchholz Relay 10
LV Side
Conservator Tank
Tap Changer
HV Side
Control Cabinet
Buchholz Relay
MV SWBD Components
Instrument Compartment
PT Compartment
Current Transformer
Earthing Switch
Breaker Compartment
12
LV SWBD Components
Voltage Transformer
Bus bar
Instrument Compartment
Current Transformer 13
Battery Bank
Utility Power
14
THE END
THANKS TO ALL
15