STORAGE TANKS CATHODIC PROTECTION


PREPERED AND PRESENTED BY M.Y.EL SHAZLY

TECOF

SACRIFICIAL ANODE SYSTEM


CURRENT

C A T H O D E

CURRENT

A N O D E

TECOF

IMPRESSED CURRENT SYSTEM


CURRENT

C A T H O D E

CURRENT

A N O D E

TECOF

INTERNAL & EXTERNAL PROTECTED AREA


INTERNAL PROTECTION INTERNAL PROTECTION

EXTERNAL PROTECTION EXTERNAL PROTECTION

INTERNAL PROTECTION

INTERNAL PROTECTION

PROTECTED AREA = AREA CONTACTING ELECTROLYTE (SOIL AND OR CONDUCTIVE LIQUID)

TANK INTERNAL CATHODIC PROTECTION


IMPRESSED CURRENT SYSTEM

h1
Transformer rectifier automatic control DC output volt/current Set point Ref. protection level Anode

A 000 Reference electrode

Protected area
shell wetted area bottom area

= bottom area + shell wetted area


= II x tank diameter x height II x (tank diameter) 2 4

Protection current

= protected area x current intencity

TECOF

TANK INTERNAL CATHODIC PROTECTION


SACRIFICIAL ANODE SYSTEM

Welded anodes

h1
Anode

Suspended anodes
h
2

Protected area
shell wetted area bottom area

= bottom area + shell wetted area


= II x tank diameter x height II x (tank diameter) 2 4

Protection current

= protected area x current intencity

TECOF

STORAGE TANKS EXTERNAL CATHODIC PROTECTION


UNDER BASE ANODE INSTALLATION RODE ANODE TYPE
-950 mv -850 mv 50 cm

Rod anodes

TECOF

STORAGE TANKS EXTERNAL CATHODIC PROTECTION


UNDER BASE ANODE TYPE INSTALLATION

-900 mv -850 mv

50 cm

RIBBON ANODE

TECOF

STORAGE TANKS EXTERNAL CATHODIC PROTECTION


DISTREBUTED ANODE INESTALLATION
-850 mv -850 mv

5 -10 m

Rod anode vertical or horizontal

5
Min. potential point

-1

RIM POTENTIAL = 1100 TO 1200

BS STANDERED OR

TECOF

ADD 1mv per one foot of tank diameter to the min. protection level (-850 mv)

STORAGE TANKS EXTERNAL CATHODIC PROTECTION


DEEP WELL GROUND BED INESTALLATION

Tank-1

Tank-2

Tank-3

Tank-4

Deep well ground bed

Tank Farm
Tank 1 Tank 2 Tank 3 Tank 4

Deep well GB

Tank 5

Tank 6

Tank 7

Tank 7

TECOF

STORAGE TANKS EXTERNAL CATHODIC PROTECTION


REMOTE GROUND BED INESTALLATION
-2500 mv -850 mv -450 mv

Remote GB

TANK FARM Tank 1 Tank 2 Tank 3

Tank 4

Tank 5

Tank 6

Tank 7

Tank 8

Tank 9

REMOTE GB

TECOF

CURRENT REQUIREMENT
1 - SURFACE AREA TO BE PROTECTED
EXTERNAL = BOTTOM AREA (BARE)

INTERNAL = BASE AREA + WETTED SHELL AREA (BARE)


IF COATED A COATING DEFFECT PERCENTAGE MUST BE APPLAYED

TECOF

CURRENT REQUIREMENT
2 CURRENT INTENSITY
INTERNAL: FRESH WATER = 20 ma/m2 SALT WATER = 100 ma/m2 EXTERNAL: DEPEND ON SOIL RESISTIVITY RANGES FROM 5 TO 0.5 ma/m2
TECOF

CURRENT REQUIREMENT
3 CURRENT CALCULATION =
SURFACE AREA TO BE PROTECTED X CURRENT INTENCITY 1- COATING DEFFECT PERCENTAGE TO BE TAKEN INTO CONSEDIRATION 2- IF THE TANK IS USED TO STORE WATER, THIS MEENS THAT SHELL WETTED AREA WILL CHANGE WITH HIGHT, HEIGHER CURRENT VALUE MUST BE TAKEN IN SIZING

TECOF

ELECTRICAL EQUIVALENT CIRCUIT

CURRENT = VOLTAGE DIVIDED BY RESISTANCE OHMS LOW EQUIVALENT CIRCUIT RESISTANCE = R1+R2+R3+R4 WHERE: R1 = NEGATIVE CABLE RESISTANCE ohm R2 = TANK STEEL RESISTANCE ohm R3 = GROUND BED RESISTANCE ohm R4 = POSITIVE CABLE RESISTANCE ohm

R2

R1

CURRENT V OUTPUT

CURRENT = PROTECTION CURRENT DEMAND in ampere VOLTAGE = DRIVING POTENTIAL in volt

R3

R4

TECOF

SAMPLES OF TANK CORROSION CELLS


WELD CORROSION BATCH CORROSION + OLD METAL NEW METAL OLD METAL

+ -

RING BEAM CORROSION

ANNUAL PLAT WELD CORROSION

Tank bottom

CORROSION AREA

Concrete ring beam

CP current

Bottom pla

tes
5 deg.

DEBARY CORROSION PRODUCTS