SHS2 Main features

SF6-insulated Switch Disconnector - Isolator

Suitable for metal-enclosed secondary distribution switchgear


Stainless steel enclosure 3 positions: LINE - OPEN - EARTH

Earthing switch with making capacity


Separate operation slots for Switch-disconnector and Earthing Switch

Characteristics Main Data


Rated voltage Power frequency withstand voltage (50-60 Hz/1 min) (*) Impulse withstand voltage (*) kV kV kVp 24 50 (60) 125 (145)

Rated frequency
Rated Normal current (t.a. 40C) Short-time current - 1s Making capacity Gas absolute pressure (20 C) Distance between phases Electrical life (**) Mechanical endurance

Hz
A kA kA kPa mm Class E3 Class E1

50/60
400/630 12.5/16/20/25 31.5/40/50/62.5 125 230 (line) (earth)

Class M1 (**)

(*) withstand voltage between phase and earth and between phases (withstand voltage between open contacts) (**) According to IEC 60265-1, IEC 60129

SHS2 Basic dimensions (to fit 500mm/375mm width panels)


Caption:

495 (panels width 500) 371,5 (panels width 375)

Insolators; Enclosure Operating mechanism Rupture disk

4 3

SHS2 Three positions


Caption 1.Switching shaft 2.Fixed contact 3.Moving contact 4.Earthing contact

Open

Line
2 1

Earth

SHS2 Stainless steel enclosure


EARTHED metallic segregation between busbar and feeder compartments

Maximum safety during maintenance and operations in the cable or fuse compartment even with busbars energized Reduced risk of short circuit between phases or between the two insulators of the same phase

SHS2 Operative mechanical version


T1 - T1M On exceeding dead centre Stored energy Independent operation (from operator) Dependent operation (from operator) Switch disconnector + Earthing switch Isolator + Earthing switch Spaced earthing switch only Motorized operative mechanism Opening coil x -x T2-T2M -x x T3-V1 ---T4 x -x

--

--

--

x
--x --

x
---x

-x ----

--x ---

SHS2 Front plate


Caption: 1. Switch disconnector slot 2. Earthing switch slot 3. Interlock lever 4. Mechanical position indicator 5. Voltage indicator 6. Key-locks

6 3

6
2

SHS2 Available key-locks


SHS2 equipped with T1 e T2 operative mechanism SHS2/T1 - SHS2/T1/N - SHS2/T1M - SHS2/T1M/N - SHS2/T2 - SHS2/T2/N - SHS2/T2F - SHS2/T2F/N Line operation 1 Free-key for Switch disconnector in open position 1 Free-key for Switch disconnector in close position 1 Free-key for Switch disconnector in close position 1 Free-key for Switch disconnector in open position 2 Free-keys for Switch disconnector in open position 2 Free-keys for Switch disconnector in close position Earth Operation 1 Free-key for Earthing switch in open position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in open position 2 Free-keys for Earthing switch in open position 2 Free-keys for Earthing switch in close position

SHS2 equipped with T3 operative mechanism SHS2/I - SHS2/I/N - SHS2/IF SHS2/IB 1 Free-key for Isolator in close position 1 Free-key for Isolator in open position 1 Free-key for Isolator in open position 1 Free-key for Isolator in open position 1 Free-key for Isolator in open position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in close position 2 Free-keys for Earthing switch in close position 2 Free-keys for Earthing switch in close position 1 Free-key for Isolator in close position 1 Free-key for Isolator in open position 1 Free-key for Isolator in close position SHS2 equipped with T4 operative mechanism 1 Free-key for Isolator in open position SHS2/ES 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in open position 1 Free-key for Isolator in close position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in close position 1 Free-key for Earthing switch in open position 1 Free-key for Isolator in close position 1 Free-key for Earthing switch in close position 2 Free-keys for Earthing switch in close position 2 Free-keys for Earthing switch in close position

SHS2 Accessories

Fuse Holder

Spaced Earthing Switch

Line and Earth key locks Auxiliary contacts (2NA+2NC for each position) (1) Voltage indicators (3) Frame with isolators or isolators with capacitive dividers (4) Opening coil (24 48 110 220 Vdc/ac) (2) Door lock Motor operation (24 Vcc 48-110-220Vdc/Vac) for spring operating mechanism) Fuse adaptors (for fuse length e=192 mm and e=292mm) Spaced earthing switch (making capacity 2,5kA)

(1) On T2 (stored energy) operative mechanism when the opening coil is required for switch disconnector in closed position a maximum of 1NO+1NC auxiliary contacts are available (2) Available only on T2 operative mechanism (3) Require accessory (4)

SHS2 Accessories
Caption: 1. Line key locks 2. Earth key locks 3. Auxiliary contacts 5 3 4 1 5

4. Opening coil
5. Voltage indicators

2 3

SHS2 For circuit-breaker unit completion


1.

HD4/R: Circuit breaker gas insulated;

Lateral operation mechanism 230 mm pole distance

Protection relay on board:


PR 521 Self-supplied (50-51-51N) REF 601 (50-51-50N-51N)

2.

VD4/R: Circuit breaker vacuum insulated

SHS2 For panel solutions equivalent to UniMix type


SHS2/T1 SHS2/T1/N SHS2/T2 SH2/T2/N SHS2/T1M SHS2/T1M/N SHS2/T2MF SHS2/T2MF/N

SHS2/T2M SHS2/T2M/N

SHS2/T2F SHS2/T2F/N

SHS2/I SHS2/I/N

Width 500 and 375 mm

UNIMIX P3

Width 500 and 375 mm

UNIMIX P2

Width 500 and 375 mm

UNIMIX ASR

SHS2/IB

SHS2/IF

UNIMIX M
Width 500 mm

UNIMIX P1F
Width 750 mm

UNIMIX A
Width 500 mm

SHS2/ES

ABB Group April 3, 2013 | Slide 14