IEC 61850 & UCA 2.0 The two different approaches for Substation Automation By : Kuldeep Tickoo / Siemens India.
Energy Automation
Page 2
Energy Automation
Page 3
IEC 61850 & UCA 2.0 The two different approaches for Substation Automation By : Kuldeep Tickoo / Siemens India.
Energy Automation
Page 4
Energy Automation
Page 5
Energy Automation
Page 6
Electric Power Research Institute (EPRI) launched a concept in 1990 known as the Utility Communication Architecture or UCA. The goal behind UCA was to identify a suite of existing communication protocols that could be easily mixed and matched, provide the foundation for the functionality required to solve the utility enterprise communication issues, and be extensible for the future. After some initial revisions, the results of the project have been known as UCA 2.0. UCA 2.0 is described in a technical report TR 1550 of the IEEE [2].
The basis and the way of standardizing communications in IEC 61850 are entirely new. IEC 61850 was developed from IEC 60870-5-x and UCA 2.0.
Comprehensive EPRI project UCA 2.0 IEC 61850
The goal of this standard IEC 61850 Communication networks and systems in substations is to provide interoperability between the IEDs from different suppliers or, more precisely, between functions to be performed in a substation but residing in equipment (physical devices) from different suppliers. Interchangeability is outside the scope of this standard, but the objective of interchangeability will be supported following this standard. Interoperability has the following levels for devices from different suppliers: (1) The devices shall be connectable to a common bus with a common protocol (syntax) (2) The devices shall understand the information provided by other devices (semantics)
Energy Automation
(3) The devices shall perform together a common or joint function if applicable
Page 8
Defines structure for protection and control System Communication configuration between bay devices Standardised language for describing substation Standard communication with TCP - IP Fault records in Comtrade format
IEC 61850
Energy Automation
Page 9
Separation of:
(e.g. Protection)
IEC 61850:
Data Model
Application
Service
Services, Rules
(e.g. MMS/TCP/IP/Ethernet)
Communication
Mapping
Energy Automation
Page 10
Input Data
Basic Function
Energy Automation
Page 11
A device sends information by Multicasting. Only devices which are subscribers receive this message. In the example, Receiver Z receives the message. Receiver Y is not a subscriber.
GOOSE message
Ethernet
Energy Automation
Page 12
Normal message
Energy Automation
Page 13
Energy Automation
Page 14
Conclusions
No. 1 with Energy Automation
UCA2.0 is only an IEEE technical report TR 1550 - not a standard IEC 61850 is not backward compatible with UCA2.0 If a utility installs a UCA2.0 system now and upgrades it to IEC 61850 later, the conversion would be time consuming and costly IEC 61850 specifies system and project management, but UCA2.0 does not IEC 61850 specifies quality assurance, environmental conditions etc, but UCA2.0 does not IEC 61850 provides engineering support through a substation configuration language, but UCA2.0 does not International agreement: only one standard - IEC 61850 Standards