Experimental Setup
Base unit components include: 1. Air distribution chamber. 2. A tank with heaters to simulate cooling loads of 0.5, 1.0 and 1.5kW. 3. A makeup tank with gauge mark and float operated control valve. 4. A centrifugal fan with intake damper to give 0.06kg s-1 max. air flow. 5. A water collecting basin. 6. An electrical panel
Note Use distilled water to fill the makeup tank . Monitor and record the amount of water evaporated during all of the test operations of the cooling tower. Check wet bulb thermocouple reservoir for water. Add if necessary. This can be done by measuring the time needs to spend by added amount of water to the make-up tank. After the system reach to study sate, Record all temperatures, dry and wet bulb temperatures of the air and water temperature of all sections, mass flow-rate of ware and air.
Mass Balance and Enthalpy Balance on Cooling Tower *Please see page 12 equations (1,2,&3)
Take mass balance over a differential section (see the fig.)
mw - mw1 = ma (Y - Y1' )
dmw = ma dY
Water Inlet
(1) (2)
T2 H2 mw
t2 h2 ma
Air outlet
*Mass velocity of dry air remain constant through the cooling tower Take enthalpy balance over the same differential section
dz z 1
(3)
*Because the latent heat of water is a big value, so a small amount of water evaporation will produce large cooling effect. Therefor we can assume the mass velocity of the water falling down through the tower is constant with out large consequences error Please see equation (4) on page 12
1
Water Outlet T1 H1 mw t1 h1 ma Air Inlet
mw (H - H1' ) = ma (h1' - h)
(4)
(5)
(6)
Eq (6) represent Air Bulk Operating Line by plotting air enthalpies versus water temperatures.
Enthalpy of Air
mw Cpw ma
h2
h1
T1
T2
Water Temperature
Where there is no resistance to heat flow in the interface between the saturated air film and water. In other words, the interface temperature can be assumed to be equal to the bulk water temperature (Merkel assumption) T(wart temperature) ti (interface temperature)
By plotting the enthalpies of the saturated airwater vapor mixture (film) and water bulk temperatures will produce a curve, please see the Figure. This carve represent Saturated Air Operating line or can be called Water Operating line
The relation between the temperature and enthalpy of the saturated air
H2 Enthalpy
This curve applies to the air film surrounding the water It called Water Operating Line And limited for hot and cold water temp (T2 and T1)
H3 h2 H1 h3
h1 T1 T3 T2 Water Temperature
Air Operating Line or Tower Operating Line Represent Air condition through the column
(5)
(7)
Kya dh = dz ( H i - h) ma
h2
(8)
h1
K ya dh = ( H i - h) ma
dz =
o
K y az ma
(9)
h2 h1
ky a dh = ( H i - h) ma
dz =
o
ky az ma
Merkels Equation
T2
g1 = H1 - h1 g 2 = H 2 - h2 g m = H 3 - h3 Dhm = f g m
KaV mw n = b[ ] mw ma
The cooling tower effectiveness .. is defined as the ratio of the actual energy transfer to the maximum possible energy transfer
h2 - h1 e= H 2 - h1
Murphree gas phase stage efficiency
Yas Y2 Y1 tas t2 t1 Air Temps
Y2 - Y1 EMG = Yas - Y1