Escolar Documentos
Profissional Documentos
Cultura Documentos
Authored by James M. Fisher, Ph.D., P.E. Perry S. Green, Ph.D. Joseph J. Pote, P.E.
Presentation by: James M. Fisher, Ph. D., P. E. Vice President Computerized Structural Design Milwaukee, WI
1
Technical Digest 11
Design Methodology
The first consideration relative to the design of the structure is to determine if rigid frame action is required. For single story structures the optimum framing system generally consists of braced frames in both directions, and the use of a roof diaphragm system to transfer wind and seismic loads to the vertical bracing elements.
Design Methodology
The specifying professional and the joist manufacturer must communicate design data and information to each other. The specifying professional must specify the necessary loading and stiffness data to the joist manufacturer. The specifying professional must indicate the type of joist to column connections so that the joist manufacturer can provide the joists with the geometry that meets the design intent. Dialog must occur between all involved parties prior to final pricing and design.
8
Design Methodology
The joist manufacturer must design the joists in conformance with the SJI Specifications and other contract requirements specified by the specifying professional.
Analysis Requirements
Forces and moments in single story joist rigid frames are determined in a manner similar to other Ordinary Moment Frames (OMF). The first step is to perform a preliminary analysis. In general, it is suggested that the OMF be considered as a pinned based frame to eliminate moment resisting foundations; however, for drift control partially restrained or fixed bases can be considered.
10
Analysis Requirements
After selecting trial member sizes for the columns and joists, a computer analysis is performed to determine forces, moments, and deflections (both first-order and second-order) for the load combinations prescribed by the Applicable Building Code. Because a second-order analysis is a non-linear problem, the analysis must be performed for each required load combination.
11
Frame Model
Model for IBC or ASCE Load Combinations
12
Analysis
Trial joist stiffness can be obtained from the SJI equations for the approximate moment of inertia for a joist or a Joist Girder. The SJI equation for a Joist Girder equals 0.018NPLd (LRFD), and 0.027NPLd (ASD) where: N = number of panel points P = panel point load (kips) at factored load level for LRFD, and at nominal load level for ASD L = girder length (ft.) d = girder depth (inches)
13
Analysis
The SJI equation for the approximate moment of inertia for a joist equals 26.767(WLL)(L3)(10-6) for both LRFD and ASD. where:
WLL = The RED figure in the K-, LH-, and DLH-Series Load Tables L = (Span 0.33) in feet for K-Series joists L = (Clear span + 0.67) in feet for LH- and DLH-Series joists
14
Analysis
Angle Size Unbraced Length feet L=4 L=5 L=6 L=7 Area in.2
2L6 x 6 x 1
2L6 x 6 x 7/8
939
828
911
809
879
781
842
749
22.0
19.5
2L6 x 6 x 3/4
2L2.5 x 2.5 x 3/16
705
49
698
48
678
41
650
34
16.9
1.80
15
Frame Model
Model for AISC-Strong Beam, Weak Column
16
OMF Analysis
17
Pseudo Columns
18
Typical Connections
19
Basic Connection
20
Eccentricity Effect
21
Added Reinforcing
22
23
Plate Connection-Sidewall
24
Plate Connection-Interior
25
26
Imin = 6790 in.4 for the exterior girders and 4570 in.4 for the interior girder (analysis requirements). Minimum width of top chord = 7.0 in. (weld requirements).
27
28
BC Force (kips)
Remarks
29
30
31
32
Bracing
33
Examples 1 and 2
34
Examples 1 and 2
35
Example 1
The building is located in Charleston, South Carolina. The building code to be used is 2006 International Building Code (IBC 2006). The precast concrete shear walls at the north and south ends of the building are non-load bearing shear walls, and are used to resist the forces between the first interior rigid frame and the end wall.
36
Example 1
Loading requirements are specified as:
Roof Loads: Dead Load: 1 psf Membrane 2 psf Deck 2 psf Insulation 3 psf Joists and Bridging 2 psf Girder 10 psf Total
37
Example 1
Collateral Load: 3 psf Sprinkler 2 psf Mechanical & Lighting 5 psf Total Live Load: 20 psf Reducible per Code (12 psf on Joist Girders) Ground Snow Load = 5 psf Roof Snow Load = 5 psf (ASCE 7, Section 7.3, low slope roof criteria)
38
Example 2
Wind Load = 120 MPH Exposure C Seismic Load: Charleston, South Carolina Serviceability Requirement:
Maximum drift = H/100 (10 year wind)
39
Example 2: Jackson, MS
Wind Base Shear (120 mph)
22.9 kips per frame line (Factored by 1.6)
40
41
42
43
44
Appendix A
Appendix A contains a complete design of the Joist Girders for Example 1
46
Acknowledgement
The authors of Technical Digest 11 would like to thank:
The Engineering Practice Committee and the Research Committee of the Steel Joist Institute for their review and contributions to the writing of this document. John A. Rolfes, S.E., P.E. Vice President of Computerized Structural Design for his assistance in the preparation of the digest, and James O. Malley, S.E. Senior Principal, Degenkolb Engineers, for his insightful review of the digest.
47
Thank you
48