Sheathed cables
clipped direct to
or lying on a non-
metallic surface




3







Reference to Table















Methods of Installation of Cables
Installation Method

Number


Description


Installation Method




Appropriate
Reference for
determining
Current-carrying
Capacity
Open and Clipped Direct
Sheathed cables
clipped direct to
or lying on a non-
metallic surface




1







Reference to Table















In Conduit
Single core non
sheathed cables
in metallic or non-
metallic conduit
on a wall or
ceiling
2





Reference to Table











Installation Method

Number


Description


Installation Method




Appropriate
Reference for
determining
Current-carrying
Capacity
In Trunking
Cables in trunking
on a wall or
suspended in air





8







Reference to Table







Cables in flush
floor trunking







9








Reference to Table

















Single core cables
in skirting
trunking





10







Reference to Table















Methods of Installation of Cables
Installation Method

Number


Description


Installation Method




Appropriate
Reference for
determining
Current-carrying
Capacity
On Trays
Sheathed cables
on a perforated
cable tray,
bunched and
unenclosed. A
perforated cable
tray is considered
as a tray in which
the holes occupy
at least 30% of
the surface area.
11










Reference to Table





















In Free Air
Sheathed single
core cables in
free air (any
supporting metal
work under the
cables occupying
less than 10% of
the plan area) :
2 or 3 cables
vertically one
above the other,
distance between
cables equal to
the overall
diameter (De);
distance from the
wall not less than
0.5 (De)





12

















Reference to Table






























Methods of Installation of Cables
Installation Method

Number


Description


Installation Method




Appropriate
Reference for
determining
Current-carrying
Capacity
In Free Air
Sheathed
Multicores cables
in free air
distance between
wall and cable
surface not less
than 0.3 De (any
supporting
metalwork
occupying less
than 10% of the
plan area)





13











Reference to Table


















Methods of Installation of Cables
Nom. Cross
Sectional Area
for Cu.
Cu.
Conductor
Current
Rating
Voltage Drop
Cu. Conductor
Voltage Drop
Al. Conductor
Equivalent
Current Rating
of Al.
Conductor
Nom. Cross
Sectional
Area for Al.
mm
2
(A) mV/A/m mV/A/m (A) mm
2

1.5 18 25 11.82 28 6
2.5 25 15 11.82 28 6
4 33 9.5 7.91 39 10
6 43 6.4 4.2 57 16
10 59 3.8 4.2 57 16
16 79 2.4 2.7 79 25
25 104 1.5 1.35 123 35
35 129 1.1 1.35 123 50
50 167 0.84 0.94 159 70
70 214 0.6 0.58 226 120
95 261 0.47 0.48 261 150
120 303 0.4 0.41 299 185
150 349 0.34 0.35 354 240
185 400 0.31 0.31 410 300
240 472 0.27 0.28 472 400
300 545 0.25 0.26 546 500
400 634 0.24 0.24 626 630
500 723 0.23 0.23 709 800
630 826 0.22 0.22 823 1000
The continuos current carrying capacities are based on the following condition :
a) Ambient temperature 30oC
b) Maximum continuos loading temperature of conductor 70oC
c) Clipped direct 3 or 4 cable, 3 phase a.c
Cu and Al Equivalent Size Comparison
Nom. Cross
Sectional Area
for Cu.
Cu. Conductor
Current Rating
Voltage Drop
Cu. Conductor
Voltage Drop
Al. Conductor
Equivalent
Current Rating
of Al.
Conductor
Nom. Cross
Sectional
Area for Al.
mm
2
(A) mV/A/m mV/A/m (A) mm
2

10 73 4 4.2 76 16
16 94 2.5 2.7 90 25
25 124 1.65 1.45 136 50
35 154 1.15 0.97 174 70
50 187 0.87 0.72 211 95
70 238 0.6 0.58 245 120
95 289 0.45 0.47 283 150
120 335 0.37 0.39 323 185
150 386 0.3 0.31 382 240
185 441 0.26 0.26 440 300
240 520 0.21 0.22 517 400
300 599 0.185 0.19 605 500
400 673 0.165 0.175 691 630
Cu and Al Equivalent Size Comparison
CU/XLPE/SWA/PVC/AL/XLPE/SCT/PE
The continuos current carrying capacities are based on the following condition :
a) Ambient temperature 30oC
b) Maximum continuos loading temperature of conductor 70oC
c) Clipped direct 3 or 4 cable, 3 phase a.c
Cu and Al Equivalent Size Comparison
XLPE/PVC
The continuos current carrying capacities are based on the following condition :
a) Ambient temperature 30 deg.C
b) Maximum continuos loading temperature of conductor 90 deg.C
c) Clipped direct 3 or 4 cable, 3 phase a.c
Nom. Cross
Sectional Area
for Cu.
Cu. Conductor
Current Rating
Voltage Drop
Cu. Conductor
Voltage Drop
Al. Conductor
Equivalent
Current Rating
of Al.
Conductor
Nom. Cross
Sectional
Area for Al.
mm
2
(A) mV/A/m mV/A/m (A) mm
2

10 74 4 4.2 80 16
16 99 2.5 2.7 97 25
25 130 1.6 1.45 149 50
35 161 1.15 0.98 189 70
50 209 0.87 0.73 234 95
70 268 0.61 0.59 273 120
95 326 0.45 0.47 314 150
120 379 0.37 0.39 366 185
150 436 0.31 0.32 438 240
185 500 0.26 0.27 507 300
240 590 0.22 0.23 594 400
300 681 0.195 0.2 692 500
400 793 0.175 0.185 791 630
500 904 0.16 0.17 911 800
630 1033 0.15 0.16 1072 1000
800 1179 0.145 0.15 1217 1200
Current-carrying Capacity for Single Core
Copper Conductor, Non-armoured or without
Sheath to BS6004 & BS6346
Conductor
Cross
Sectional
Area
Current Carrying Capacity
Method of Installation
Enclosed in
Conduit in
Thermally
Insulated Wall
etc.
Enclosed in
Conduit on
Wall or
Trunking etc.
Clipped Direct
On a
Perforated
Cable Tray
Horizontal or
Vertical
In Free Air
Horizontal
Spaced
Vertical
Flat
Spaced
Trefoil
2
cables,
single
phase
a.c or
d.c
3 or 4
cables,
three
phase
2
cables,
single
phase
a.c or
d.c
3 or 4
cables,
three
phase
2 cables,
single
phase a.c
or d.c flat
touching
3 or 4
cables,
three
phase a.c
flat &
touching
@ trefoil
2 cables,
single
phase a.c
or d.c flat
touching
3 or 4
cables,
three
phase a.c
flat &
touching
@ trefoil
2 cables,
single phase
a.c or d.c or
3 cables
three phase
a.c
2 cables,
single
phase a.c
or d.c or 3
cables
three
phase a.c
3
cables,
trefoil
three
phase
a.c
mm
2
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1.25 13 12 16 14 19 17 - - - - -
1.5 14.5 13.5 17.5 15.5 20 18 - - - - -
2.5 19.5 18 24 21 27 25 - - - - -
4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 56 76 68 87 79 - - - - -
25 80 73 101 89 114 104 126 112 146 130 110
35 99 89 125 110 141 129 156 141 181 162 137
50 119 108 151 134 182 167 191 172 219 197 167
70 151 136 192 171 234 214 246 223 281 254 216
Current-carrying Capacity for Single Core
Copper Conductor, Non-armoured or without
Sheath to BS6004 & BS6346
Conductor
Cross
Sectional
Area
Current Carrying Capacity
Method of Installation
Enclosed in
Conduit in
Thermally
Insulated
Wall etc.
Enclosed in
Conduit on
Wall or
Trunking etc.
Clipped Direct
On a Perforated
Cable Tray
Horizontal or
Vertical
In Free Air
Horizontal
Spaced
Vertical
Flat
Spaced
Trefoil
2
cables
,
single
phase
a.c or
d.c
3 or 4
cables,
three
phase
2 cables,
single
phase a.c
or d.c
3 or 4
cables,
three
phase
2 cables,
single
phase a.c
or d.c flat
touching
3 or 4
cables,
three
phase a.c
flat &
touching
@ trefoil
2 cables,
single
phase a.c
or d.c flat
touching
3 or 4
cables,
three
phase a.c
flat &
touching
@ trefoil
2 cables,
single phase
a.c or d.c or
3 cables
three phase
a.c
2 cables,
single
phase a.c
or d.c or 3
cables
three
phase a.c
3 cables,
trefoil
three
phase a.c
mm
2
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
95 182 164 232 207 284 261 300 273 341 311 264
120 210 188 269 239 330 303 349 318 396 362 308
150 240 216 300 262 381 349 404 369 456 419 356
185 273 245 341 296 436 400 463 424 521 480 409
240 320 286 400 346 515 472 549 504 615 569 485
300 367 328 458 394 594 545 635 584 709 659 561
400 - - 546 467 694 634 732 679 852 795 656
500 - - 626 533 792 723 835 778 982 920 749
630 - - 720 611 904 826 953 892 1138 1070 855
800 - - - - 1030 943 1086 1020 1265 1188 971
1000 - - - - 1154 1058 1216 1149 1420 1337 1079
Current-carrying Capacity for Multicore
Copper Conductor, Non-armoured to BS6004
& BS6346
Conductor
Cross
Sectional
Area
Current Carrying Capacity
Method of Installation
Enclosed in
Conduit in
Thermally
Insulated Wall etc.
Enclosed in Conduit on
Wall or Trunking etc.
Clipped Direct
On a Perforated
Cable Tray
Horizontal or Vertical
1 two-
cores
cable,
single
phase
a.c or
d.c
1 three-
core cable
or four-
core
cable,
three
phase a.c
1 two-cores
cable,
single
phase a.c
or d.c
1 three-
core cable
or four-
core
cable, three
phase a.c
1 two-cores
cable,
single
phase a.c
or d.c
1 three-
core cable
or four-
core
cable,
three
phase a.c
1 two-
cores
cable,
single
phase
a.c or d.c
1 three-
core cable
or four-
core
cable, three
phase a.c
mm
2
(A) (A) (A) (A) (A) (A) (A) (A)
1.5 14 13 16.5 15 19.5 17.5 22 18.5
2.5 18.5 17.5 23 20 27 24 30 25
4 25 23 30 27 36 32 40 34
6 32 29 38 34 46 41 51 43
10 43 39 52 46 63 57 70 60
16 57 52 69 62 85 76 94 80
25 75 68 90 80 112 96 119 101
35 92 83 111 99 138 119 148 126
50 110 99 133 118 168 144 180 153
70 139 125 168 149 213 184 232 196
95 167 150 201 179 258 223 282 238
120 192 172 232 206 299 259 328 276
150 219 196 258 225 344 299 378 319
185 248 223 294 255 392 341 434 364
240 291 261 344 297 461 403 514 430
300 334 298 394 339 530 464 593 497
400 - - 470 402 634 557 715 597
Current-carrying Capacity for Single Core
Copper Conductor, Armoured to BS6346
Conductor
Cross
Sectional
Area
Current-Carrying Capacity
Method of Installation (in free air)
Clipped Direct
On a Perforated Cable
Tray Horizontal or
Vertical
2 cables, single
phase a.c
2 cables, single
phase d.c
3 or 4 cables, three
phase a.c
2 cables,
single phase
a.c or d.c
flat &
touching
3 or 4
cables,
three phase
a.c, flat &
touching
2 cables,
single phase
a.c or d.c
flat &
touching
3 or 4
cables,
three phase
a.c, flat &
touching
Horizontal
Spaced
Vertical
Flat
Spaced
Horizont
al
Spaced
Vertical
Flat
Spaced
Horizon
tal
Spaced
Vertical
Flat
Spaced
3 cables
Trefoil
mm
2
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
50 193 179 205 189 229 217 229 216 230 212 181
70 245 225 259 238 287 272 294 279 286 263 231
95 296 269 313 285 349 332 357 340 338 313 280
120 342 309 360 327 401 383 415 396 385 357 324
150 395 354 413 373 456 436 479 461 438 407 373
185 447 399 469 422 511 489 548 525 490 456 425
240 525 465 550 492 593 568 648 622 566 528 501
300 594 515 624 547 668 640 748 719 616 578 567
400 687 575 723 618 737 707 885 851 674 632 657
500 763 622 805 673 810 777 1035 997 721 676 731
630 843 669 891 728 893 856 1218 1174 771 723 809
800 919 710 976 777 943 905 1441 1390 824 772 866
1000 975 737 1041 808 1008 967 1685 1627 872 816 945
Current-carrying Capacity for Multicore
Copper Conductor, Armoured to BS6346
Conductor Cross
Sectional Area
Current-Carrying Capacity
Method of Installation (in free air)
Clipped Direct
On a Perforated Cable Tray
Horizontal or Vertical or in free air
1 two-cores cable,
single phase a.c or
d.c
1 three-core cable
or four-core
cable, three
phase a.c
1 two-cores cable,
single phase a.c or
d.c
1 three-core cable
or four-core
cable, three
phase a.c
mm
2
(A) (A) (A) (A)
1.5 21 18 22 19
2.5 28 25 31 26
4 38 33 41 35
6 49 42 53 45
10 67 58 72 62
16 89 77 97 83
25 118 102 128 110
35 145 125 157 135
50 175 151 190 163
70 222 192 241 207
95 269 231 291 251
120 310 267 336 290
150 356 306 386 332
185 405 348 439 378
240 476 409 516 445
300 547 469 592 410
400 621 540 683 590
Current-carrying Capacity for Aluminum
Conductor
Nominal
Sectional
Area (mm
2
)
Continuous Current Rating (Unit Amperes)
Short
Circuit
Current
Rating
for 1
sec.
In Air at 40
o
C On Ground at 25
o
C
Single
Conductor 3
cables S=2d
Twin
Conductor
Three or
Four
Conductors
Single
Conductor
3 cables
S=2d
Twin
Conductor
Three or
Four
Conduct
ors
4 - 29 24 - 38 32 305A
6 - 36 31 - 47 41 405
10 - 49 41 - 63 53 760
16 - 66 55 - 82 69 1.22 kA
25 - 86 72 - 105 89 1.9
35 - 105 90 - 130 105 2.66
50 150 125 105 150 150 125 3.8
70 185 170 140 185 190 155 5.32
95 220 205 165 215 225 185 7.22
120 265 230 195 250 260 215 9.12
150 285 270 235 280 285 240 11.4
185 350 305 255 320 325 270 14.1
240 405 360 295 365 380 320 18.2
300 460 420 355 420 430 355 22.8
400 570 - - 495 - - 25.8
500 650 - - 550 - - 32.6
630 750 - - 640 - - 40.8
800 890 - - 725 - - 50.3
1000 1015 - - 815 - - 65.3
Single conductor : Single point
bonded
Short Circuit Ratings
Short Circuit Rating (A) Copper Conductor Aluminum Conductor
Up to and including 300mm
2
115 X (S/t) 76 X (S/t)
Greater than 300mm
2
103 X (S/t) 68 X (S/t)
t : Short circuit duration time in second
S : Cross sectional area in mm
2

Conditions : Max. permissable continuous operating temperature 70

deg.C
Max. permissable temperature at short-circuit 160 deg.C
Air Temperature
(
o
C)
25 30 35 40 45
Rating factor (max.
conductor
temperature 70
o
C)
1.22 1.15 1.08 1.00 0.91
Rating Factor for Variation in Ambient
Temperature
Ground
Temperature (
o
C)
10 15 20 25 30
Rating factor (max.
conductor
temperature 70
o
C)
1.15 1.11 1.05 1.00 0.94
Rating Factor for Variation in Ground
Temperature (Direct Laid on the Ground)
Rating Factors for Depth Laying for Cables
Laid Direct on the Ground
Depth of Laying
(meter)
600/1000V Cables
Up to 50 mm
2
70 mm2 to 300 mm
2
Above 300 mm
2

0.5 1.03 1.04 1.06
0.6 1.02 1.02 1.03
0.8 1.00 1.00 1.00
1 0.98 0.97 0.98
1.25 0.97 0.96 0.95
1.5 0.96 0.94 0.93
1.75 0.95 0.93 0.91
2 0.94 0.92 0.90
2.5 0.93 0.91 0.89
3.0 and above 0.92 0.89 0.87
HANDLING AND INSTALLATION OF CABLE

1.Minimum bending radius and permissable pulling tension
- to prevent damage on electrical and physical properties of the cable













Lifting by crane Drum rolling direction Do not lay on flanges
Lifting drum by forklift correctly
Drums secure adequately during transportation
HANDLING AND INSTALLATION OF CABLE
DO NOT attempt coiling on the ground
On the ground cable can be FLAKED in a figure of eight formation
HANDLING AND INSTALLATION OF CABLE