Ovation SIS Hardware

Shirish Ratnaparkhi
December 2014

EMERSON Process Management


Power and Water Solutions

Copyrighted Material / Duplication Prohibited

Objectives
Upon completion of this module you will be able to
Design Ovation SIS Hardware layouts

Define Ovation SIS Power Requirements

Define SISNet Repeater fiber-optic ring layout

Create a New Logic Solver with Developer Studio

Add a New Logic Solver with Developer Studio

Assign, Commission and Load a Logic Solver with Developer Studio

Define the SLS 1508 and SISNet Repeater LED indicators

Use Ovation diagnostics to view SISNetwork nodes and subsystems

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-2

Ovation SIS Hardware Components


System Power Supply

SIS 1508 Logic Solvers

Communication Processor SIS Terminal Blocks

Dual Right Extender

The SIS 1508 Logic Solvers could be four simplex or two redundant pairs.
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-3

Ovation SIS Hardware Components

System Power Supply Ovation Dual Power Supply 12/24VDC.


Communication Processor Ovation controller provides Primary and
Secondary Ethernet connections to the Ovation Control Network. Ethernet
communications is for configuration and monitoring only, not for SISrelated functions.

Logic Solvers Contains logic solving capability. Logic Solvers run the
SIS modules the user configures.
Terminal Blocks Field device connections to Logic Solver I/O channels.
Dual Right Extender It is used to terminate the 2 channel peer-to-peer
communications for the Logic Solvers in the example above. The
Power/Controller 2-Wide carrier has the peer-to-peer communication
termination built in.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-4

Ovation SLS 1508 Logic Solver


The Ovation SLS 1508 Logic Solver is packaged in a 2-wide I/O footprint. SIS terminal
blocks, situated anywhere on I/O backplanes, are placed starting with the odd numbered
slots. Simplex requires two slots and Redundant requires four slots on the I/O carrier.
24VDC power for the I/O and CPU is derived from a dedicated connector; not bussed
field power. Controller or Bussed power failure has no effect on Logic Solvers.

Item

Specification

Input Power

24 VDC 20%, 1.0 A plus field power (5.0 A total)


Note: It is recommended that the SLS, Ovation controller and I/O use
separate power supplies.

Field Power

4 A maximum (actual value depends upon channel and field device type)

Isolation

Each channel is optically isolated from the system and factory tested to
1500 VDC. No channel-to-channel isolation.

LocalBus
Current

None

Mounting

In SIS (yellow) terminal blocks in odd numbered slots (1, 3, 5, 7) on the


8-wide carrier. Simplex SLSs take 2 slots and redundant SLSs take 4
slots.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-5

Ovation SLS 1508 Logic Solver


Note: 24VDC is available on screw terminals C and A after plugging connector into the
Logic Solver. Do not daisy chain power between Logic Solvers.
Connections on Printed Wire Board
D C B A

Top View
Power Connector

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-6

Ovation SLS 1508 Logic Solver


16 channels of I/O per Logic Solver consists of a mix of:
HART Analog Input
Analog Input
HART two-state Output
Digital Input 12VDC dry contact
Digital Output 24 VDC High Side
Line fault detection on I/O
Separate I/O processor
Two Main Processors
50mS Module Execution
SOE timestamp at module execution
Sixteen additional Boolean values published
Peer-to-Peer on every scan

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1-7

Logic Solver Internal Architecture

MP 2 error-checks data, sends


data to MP 1 which also error
checks data.

MP 2 publishes data to SISnet


and reads the data back.

MP 1 reads the data from


SISnet.

MP 2 and MP 1 use the data


from SISnet, as will any other
logic solvers connected to
SISnet.

Railbus

MP 1

Peer-to-Peer
SISnet

B
Diagnostics

I/O CPU reads input data and


adds CRC and sends to MP 2.

I/O CPU and Circuits

A
MP 2

Terminal Block

Actuator
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Sensor
Copyrighted Material / Duplication Prohibited

1-8

Logic Solver Internal Architecture


Railbus

MP 2 and MP 1 run the logic


software synchronously, with
certain tasks assigned to only
one processor of the pair.
MP 2 and MP 1 run their
application logic, using
extensive comparison and error
checking to ensure that the
correct output values are set.

If an error is detected then it


will be flagged and all of the
I/O circuits in the logic solver
will be switched off as this is
the only safe course of action.

A
MP 2

Terminal Block

Actuator
EMERSON Process Management
Power and Water Solutions

Peer-to-Peer
SISnet

Diagnostics

MP 1
I/O CPU and Circuits

Course OV 236 Rev 2 01/02/2010

Sensor
Copyrighted Material / Duplication Prohibited

1-9

Logic Solver Internal Architecture


Railbus

MP 1

Peer-to-Peer
SISnet

B
Diagnostics

If the I/O CPU detects an error,


such as a short or open circuit
in the field wiring, an error will
be flagged. However, the I/O
diagnostics will not trigger a
module shutdown until the
output is required to be
de-energized.

I/O CPU and Circuits

A
MP 2

Terminal Block

Actuator
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Sensor
Copyrighted Material / Duplication Prohibited

1 - 10

Ovation SLS 1508 Redundant Logic Solver

Dedicated Redundancy Link between Logic Solver pairs

Separate power per Logic Solver

Both Logic Solvers use same input data for checking

Solvers are synchronized with each other

Redundant peer-to-peer Link

I/O published locally on peer-to-peer


every scan

Redundant partner is not required for


SIL 3 applications

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 11

Ovation SLS 1508 Redundant Logic Solver


In some cases additional availability is required and , in such cases, a redundant logic
solver may be installed. Both logic solvers take their input data, and send their output
data, through a single set of terminals that is wired to the field devices.
In a redundant architecture the two logic solvers work in parallel it is not a master/slave
arrangement. Both logic solvers read the same input data and write the same outputs all
of the time. The exact methodology is proprietary and under patent.
Active Logic Solver
One of the logic solvers is designated the active logic solver; this is the one of the pair
that makes data available to the Railbus. Both logic solvers write this data to the field
devices.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 12

Redundant Logic Solver Internal Architecture


Shown below is a Block diagram indicating the interconnectivity between Redundant
Logic Solvers.
Railbus

MP 1

Diagnostics

I/O CPU and Circuits


EMERSON Process Management
Power and Water Solutions

Diagnostics

Redundant
Terminal Block

SISNet
B

MP 2

Actuator

SISNet
B

Redundancy link

I/O CPU and Circuits

MP 1

MP 2

Sensor

Synchronization link
Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 13

Ovation SLS 1508 Redundant Logic Solver


Communications with SISnet
Both logic solvers publish all their data onto the SISnet all the time. They also listen for
all data on the SISnet. This allows the logic solvers to monitor their own capability to do
so and also that of their redundant partner.
Switchovers and Diagnostics
Should either logic solver fail, there will be no bump in the signal as the other solver
assumes complete control. This approach of two logic solvers working parallel gives a
significant advantage in that, should one fail, the other does not have to detect the fault
and assume control. It simply continues to work exactly as it was before.
Diagnostics run within all logic solvers all of the time, with up to twenty diagnostic
cycles per second. Some diagnostics are by reference and some are by comparison.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 14

SIS Termination Blocks


The SLS provides 16 channels of flexible I/O. Therefore, each channel can be configured
as a combination of Analog Input (HART), Analog Output (HART) two-state, Digital
Input 12VDC dry contact, or Digital Output 24VDC High-side.
Quick release tabs

A
B
C
Simplex terminal block 2 I/O slots
EMERSON Process Management
Power and Water Solutions

A
B
C
Redundant terminal block 4 I/O slots
Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 15

SIS Termination Blocks Field Connections

Row A AI, AO, DI, DO +(positive) field device connections up to 16 channels.


Row B AI, AO, and DI (negative) field device connections up to 16 channels.
Row C DO (negative) field device connections up to 16 channels.

A
B
C

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 16

Digital Input 12 VDC Dry Contact


Note: Refer : Installing Ovation Safety
Instrumented System.

EMERSON Process Management


Power and Water Solutions

Digital Input Channel Specifications


Item

Specification

Number of channels

16

Isolation

Each channel is optically isolated


from the system and factory tested to
1500 VDC. No channel-to-channel
isolation.

Detection level for ON

2mA

Detection level for


OFF

1.65 mA

Input impedance

1790

Input compatibility

Inputs compatible with: NAMUR


sensors (12 V), Dry contact, Dry
contact with end of line resistance

Line fault detection


short circuit (optional)

100 for guaranteed short circuit


detection
> 6 mA (simplex)
> 11 mA (redundant)

Line fault detection


open circuit (optional)

> 40 k for guaranteed open loop


detection
0.35 mA

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 17

Digital Input 12 VDC Dry Contact


The Digital Input channels have line fault detection to detect open or short circuits in
field wiring. To use this capability you must:
Enable line fault detection on a channel-by-channel basis when you configure the
channels.
Connect the dry contact to a 12K external resistor in parallel (for open circuit
detection) and a 2.4K resistor in series (for short circuit detection).
Note1: Line fault detection is built into
NAMUR sensors. Do not use external
resistors with NAMUR sensors; however,
you must enable line fault detection in your
configuration when using NAMUR sensors.
Note2: Emersons End of Line Resistance
Module (KJ2231X1-EC1) provides this
function. The module connects to the Digital
Input channel and to a field contact.
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 18

Digital Output 24VDC


High Side

Digital Output channel specifications


Item
Number of channels

16

Isolation

Each channel is optically isolated


from the system and factory tested to
1500 VDC. No channel-to-channel
isolation.

Output voltage

Field power minus 2 V

Field power

0.5 A continuous per channel; 4.0 A


max per card

Output loading

56 to 3500

Off-state leakage

Open loop test ON 7.8 mA


Open loop test OFF 4.5 A typical;
10 A max.

3.3 K simplex &


2.7 K redundant

RC Compensator

0.47 f simplex &


0.22 f redundant

*Refer to the Installation Notes for information on pulse testing.


EMERSON Process Management
Power and Water Solutions

Specification

Note: Optional pulse test will apply


24 VDC pulse on line for 1.0 mS
every 50 mS.*
Short circuit protection

Output current limited to 2.0 A typical

Line fault detection


short circuit

< 5 for > 1 sec with +24 VDC field


power.*

Line fault detection


open circuit (with +24
VCD field power)

> 25 k for open loop detection.


< 3.5 k for no open loop detection.*

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 19

Digital Output 24VDC High Side


When driving inductive loads greater than or equal to 0.8 Henry in simplex or 0.3 Henry
in redundant, an RC compensator may be required. Size the RC compensator at 3.3K
and 0.47 f for simplex and 2.7K and 0.22f for redundant.
Pulse testing is recommended; however, it can be disabled for field devices such as solid
state relays that cannot support it. With redundant SLSs, pulse testing requires partner
synchronization and stops if the redundant partner becomes unavailable.
Note: Emersons SLS RC Compensator Module (KJ2231X1-ED1) provides this function.
The module connects to the Digital Output Channel and the field load. Labeled
connections for Simplex and Redundant Logic Solvers.
Digital Out with R-C Snubber
3.3 k simplex and 2.7 k redundant
RC Compensator
0.47 f simplex and 0.22 f redundant
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 20

Analog Input 4-20ma With HART


Analog Input channel
specifications (w/HART)

Note: Refer : Installing Ovation Safety


Instrumented System.

EMERSON Process Management


Power and Water Solutions

Item

Specification

Number of channels

16

Isolation

Each channel is optically isolated


from the system and factory tested to
1500 VDC. No channel-to-channel
isolation.

Nominal signal range


(span)

4 to 20 mA

Full signal range

1 to 24 mA

Field circuit power per


channel

24 mA

2-wire transmitter
power

15.0 V min terminal-to-terminal @ 20


mA; current limited to 24 mA max

Safety/diagnostic
accuracy

2.0% of span

Resolution

16 bits

Filtering

2-pole filter, corner frequency


5.68 Hz: -3 db at 5.68 Hz, -20.0 db at
40 Hz (half the sample rate)

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 21

HART Two-State Output


Note: Refer : Installing Ovation Safety
Instrumented System.
HART Two-State Output
Channel Specifications
Item

EMERSON Process Management


Power and Water Solutions

Specification

Number of channels

16

Isolation

Each channel is optically isolated


from the system and factory tested to
1500 VDC. No channel-to-channel
isolation.

Nominal signal range


(span)

ON state 20 mA
OFF state 0 or 4 mA (configurable)

Full signal range

0 to 24 mA

Safety/diagnostic
accuracy

5% of span

Resolution

12 bits

Compliance voltage

20 mA into 600 load

Open-loop detection

< 1.0 mA when the output drifts


15% out of the configured value

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 22

One-wide Extender Cable Carrier


White BNC Connector

Black BNC Connector


D-Shell Connector

D-Shell Connector

White BNC Connector


D-Shell Connector
D-Shell Connector

External 12VDC

Black BNC Connector

Connection
Left cable carrier
EMERSON Process Management
Power and Water Solutions

Right cable carrier


Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 23

One-wide Extender Cable Carrier


Local bus and peer-to-peer bus extender cables are used to extend railbus power and peerto-peer signals when I/O carriers are installed on separate DIN rails. One railbus extender
cable is used for a standard installation. Dual railbus extender cables can be used for high
availability applications.
White BNC connector Connects A peer-to-peer coax cable to additional I/O
carriers with SLSs or termination on last right extender carrier.
Black BNC connector Connects B peer-to-peer coax cable to additional I/O
carriers with SLSs or termination on last right extender carrier.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 24

One-wide Extender Cable Carrier

D-Shell Connectors For a standard installation, the extender cable is used


between the top D-Shell connectors of the right and left extender carriers. A second
extender cable is used between the bottom D-Shell connectors of the right and left
extender carriers for high availability systems.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 25

Dual Cable Extenders

Peer B peer-to-peer
(black strain relief)

Dual extender cable

Peer A peer-to-peer
(white strain relief)

RG62A/U Coax

T
T

120 ohm terminator


120 ohm terminator

A maximum of 32 Logic Solvers per Ovation controller.


EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 26

Dual Cable Extenders


A dual cable extender provides railbus and 12VDC power extension between two
horizontal carriers. Functionally, a dual cable extender replaces the existing Local bus
cable extender and can also be used for the new SIS system.
A dual cable extender provides two BNC connections for peer-to-peer communications.
Peer-to-peer extender cables extend the peer-to-peer bus between SLSs on different
carriers. The 2-channel peer-to-peer bus must be terminated at both ends. Terminated onewide carriers terminate the peer-to-peer bus at the final dual right extender. The other end
is terminated internally on the two-wide power controller carrier.
There are two cable extenders; the Dual Right Extender and the Dual Left Extender. The
left extender is only needed when extending between two or more I/O carriers.
Note: The dual right extender must be installed and terminated even if you are using only
one 8-wide I/O carrier.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 27

SISNet Repeaters
SISNet repeaters provide fiber-optic communications between Logic Solvers attached to
different controllers.

SISNet Carrier
EMERSON Process Management
Power and Water Solutions

SISNet Repeaters
Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 28

SISNet Repeaters

SISNet Repeater Carrier Provides pass through connections for railbus signals
and the +12VDC power required for traditional I/O cards. It provides peer-to-peer
signal connection from the SISNet Repeater to the rest of the system and a
communication signal connection between the two SISNet Repeaters.

SISNet Repeaters Provides fiber-optic communications between Logic Solvers


attached to different controllers. The repeaters are attached to the SISNet Repeater
Carrier.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 29

SISNet Repeaters

Top view
Connections on
Printed Wire Board

Bottom view
RxD
TxD

Test port
for factory
use only

Power Connector

Note: 24VDC is available on screw terminals C and A after plugging into the repeater.
Do not daisy chain power between repeaters.
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 30

SISNet Repeater Specifications


Item

Specification

Port type

ST female

Cable type

Multimode 62.5 /125 m; ST type or Multimode 50 /125 m; ST type

Output power

<-12dBm

Link budget

Multimode 62.5 /125 m max attenuation 11 dB


Multimode 50 /125 m max attenuation 8 dB
Wavelength 1300 nm

Link distance (max)

2 km one way TxD to RxD


Refer to Example Fiber-Optic Power Loss Calculation for additional information

Topology

Physical ring: RxD connects to TxD of predecessor and TxD connects to RxD of successor.

Test port type

For factory use only.

Mounting

2-wide SISNet Repeater carrier.


Left carrier position is secondary SISNet Repeater, right carrier position is primary SISNet Repeater.

Item

EMERSON Process Management


Power and Water Solutions

Specification

Input

24 VDC 300 mA (max)

Connector type

4-position screw terminal

Wire type

Solid or Stranded

Wire gauge

12 AWG maximum
Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 31

SISNet Repeaters LED Indicators


Correct Operating
Condition

LED
Power
(green)
Fault (red)

Local Peer
Tx (yellow)

Local Peer
Rx (yellow)

ON

Fault
Indication
s

Corrective
Action

Probable Cause

OFF

Power not supplied to unit

Check power supply


and connections.

ON

Internal fault

Contact tech support

FLASHING

Maintenance required

Contact tech support

ON Normal operations. SISNet repeater


receiving global data from other SISNet
repeaters and transmitting it to the local peerto-peer bus.

FLASHING
(local Peer Tx
only)

The SISNet repeater is not receiving its own


transmissions while still receiving the
transmissions of local SISs.

Contact tech support

OFF Normal operations. SISNet repeater


receiving no global data from other SISNet
repeaters. It is receiving its own status
transmissions.

FLASHING
(both local Peer
Tx and Rx)

Peer-to-peer bus extender cables disconnected,


bus not terminated or terminated with wrong
resistance.

Check peer-to-peer
cables and termination

ON Normal operations. SISNet repeater


receiving transmissions from local SLSs.

FLASHING
(local Peer Rx
only)

SISNet repeater not receiving local SLS


transmissions and not receiving its own status
transmissions.

Check peer-to-peer bus


termination. Contact
tech support

1. Peer-to-peer bus extender cables


disconnected, bus not terminated or terminated
with wrong resistance.

1. Check peer-to-peer
cables and termination.

2. More than 5% of received messages have


errors.

2. Check peer-to-peer
bus termination.
Contact tech support.

OFF

OFF Normal operations. SISNet repeater is


receiving no transmission from local SLSs.
Receiving its own status transmissions.

EMERSON Process Management


Power and Water Solutions

FLASHING
(both local Peer
Rx and Tx)

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 32

SISNet Repeaters LED Indicators


LED

Remote Peer
Tx (yellow)

Correct Operating
Condition

ON Normal operations. SLS transmitting


local and remote global messages on the fiberoptic ring.

Fault
Indication
s

Corrective
Action

Probable Cause
1. Hardware error.

1. Contact tech
support.

2. Break in fiber-optic ring.

2. Check that SISNet


repeater is receiving
remote global data and
its own global data is
making it around the
ring.

1. Fiber-optic cable is disconnected, broken or


crossed.

1. Check fiber-optic
cable connections:
primary to primary,
secondary to
secondary.

2. More than 5% of received messages have


errors.

2. Check remote peer


predecessor for
transmit error.
Contact tech support.

FLASHING

OFF Normal operations. No global data to


transmit.

Remote Peer
Rx (yellow)

ON Normal operations. SISNet repeater is


receiving global data.
OFF Normal operations. No global data
being received by this SSINet repeater.

EMERSON Process Management


Power and Water Solutions

FLASHING

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 33

SISNet Repeaters
24VDC

24VDC

Remote Peer Tx
Remote Peer Rx

Remote Peer Tx
Remote Peer Rx

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 34

SISNet Repeaters Fiber-Optic Rings


SISNet Repeaters connected to one Ovation controller communicate with SISNet
Repeaters connected to a different controller over a fiber-optic ring. A local SISNet
Repeater collects locally-generated global messages into a single message and sends it to
the SISNet Repeater in the ring. Immediately upon receipt of a message, the receiving
SISNet Repeater forwards the message to the next SISNet Repeater in the ring. A global
message is forwarded around the ring once. The A SISNet Repeaters form one fiber-optic
ring and B form another ring.
The fiber-optic ring is a multimode fiber cable, maximum distance between SISNet
Repeaters is 2km.
Each SISNet Repeater requires a separate 24 VDC supply.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 35

SISNet Repeaters Fiber-Optic Rings


CAB 1

Ring A

TX

Ring B

TX

RCV

RCV
TX

RCV

TX

RCV

CAB 2

RCV

CAB 4

TX
TX

CAB 3

TX

RCV
EMERSON Process Management
Power and Water Solutions

RCV

TX

RCV

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 36

SISNet Repeaters Fiber-Optic Rings


Fiber-Optic Ring Connection Recommendations
Wire the two fiber-optic rings in the opposite direction. Do it this way for
maximum availability.
The example above displays four separate cabinets with SISNet Repeaters.

Ring A is wired from CAB1 to CAB2 to CAB3 to CAB4 to CAB1, completing the
fiber-optic ring.

Ring B is wired just opposite from CAB1 to CAB4 to CAB3 to CAB2 to CAB1,
completing the fiber-optic ring.

Scenario
Assume CAB3 looses all power and the SISNet Repeaters are down. Wiring the fiberoptics in opposite directions give the availability of the other CABs to communicate to
each other across the fiber-optics. If CAB2 sends data to CAB1 or CAB4 it has a path
using RING B.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 37

SISNet Distance Extender


SISNet Distance Extenders convert multimode fiber-optic signals to single mode
fiber-optic signals to allow SISNet Repeaters to communicate over greater distances. The
remote peer ring can be extended by an additional 60Km when single mode fiber-optic
cable is used. Power rating is 24Vdc @ 250ma.

Front View
EMERSON Process Management
Power and Water Solutions

Side View
Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 38

SISNet Distance Extenders


LED indicators on the SISNet Distance Extenders

LED

Correct
Condition

Fault
Indicator

PWR

ON

OFF

Power is not
supplied to Unit

Provide Power

SM
(Single-Mode)

ON

OFF

No single-mode
carrier detected

Restore connection to the


predecessor SISNet Distance
Extenders

MM
(Multi-Mode)

ON

OFF

No multi-mode
carrier detected

Restore connection to
predecessor SISNet Repeaters
multi-mode TxD

EMERSON Process Management


Power and Water Solutions

Probable
Cause

Course OV 236 Rev 2 01/02/2010

Corrective Action

Copyrighted Material / Duplication Prohibited

1 - 39

SISNet Repeaters and Distance Extenders


SISNet, all Nodes are remote. Node refers to SISNet Repeaters and Extenders in this
example.

Multi-Mode
Conversion Cable
ST to SC
EMERSON Process Management
Power and Water Solutions

Single-Mode up to 60 Km
Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 40

SISNet Repeaters and Distance Extenders


The example above shows a remote peer ring in which all nodes are remote. Again, node
refers to a SISNet Repeater pair and SISNet Distance Extender pair. This remote peer
ring uses a counter-rotation topology in which the left SISNet Repeaters are connected
clockwise and the right SISNet Repeaters are connected counterclockwise.
Multi-Mode Fiber Optic Conversion Cable The conversion cable has an ST style
connector on the end connected to the SISNet Repeaters and SC style connector on
the end that connects to the Distance Extenders for both TxD and RxD.
Single-Mode Fiber Optic Cable The Single-Mode fiber cable has an LC style
connector on both ends of the cable that plug into the Distance Extenders for both
TxD and RxD.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 41

SIS IO Allocation
The classification of IOs:
Hardwired / Soft signals
Analog / Digital
Inputs / Outputs
Control / Data / Alarm /
Safety
From Process / System
generated
IOs as per Logic
1. The IOs listed in IO
List must match to the
IOs indicated in the
logic in any format.

EMERSON Process Management


Power and Water Solutions

2. The entire logic should


be suitably divided into
SIFs
3. The SIFs must be
allocated to the
modules of logic
solvers.
4. This must be done in a
view to maintain
required risk reduction
to be provided by the
SIF.
Rules of the game
. The maximum current
given by DO channel is
0.5 A
Course OV 236 Rev 2 01/02/2010

The total output


current by a Logic
Solver is 4A max
Secure parameters per
SLS are 16 Max
Max 8 SLS can
publish globally
No double browsing
of inputs
Avoid passing
through multiple logic
solvers to reach to DO
Consider scan time
and free memory
specifications

Copyrighted Material / Duplication Prohibited

1 - 42

Integrated Yet Separate


Railbus

Power

Peer-to-Peer A

Peer-to-Peer B

Shown above are the I/O carrier traces used for integration yet separation.
EMERSON Process Management
Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 43

Integrated Yet Separate

Power 12VDC from Ovation System Supply is sued by SDS and NOT used by
any SLSs or SISNet Repeaters.

Railbus Communication lines used by SDS for Primary and Secondary Ethernet
connections to the Ovation LAN through router. Ethernet communications are for
configuration downloads and monitoring only; not safety-related functions.

Peer-to-Peer A 1 channel of SLS to SLS communication.

Peer-to-Peer B 1 channel of SLS to SLS communication.

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 44

Ovation SIS Architecture


Operator Station

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

DB Server

Copyrighted Material / Duplication Prohibited

1 - 45

Traffic on the networks


load,
download,
firmware
upgrade,
secure
write

all points updates,


alarming all traffic
related to points
representation

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 46

Marine Facilities Architecture


DB SVR-DROP208

Primary
Primary

Backup
Backup

OPR Stn.
DROP243
Root
S/w

FAN out
s/w

R
T
R
A

#P2
(ESD8)
SDS11
#P2 (ESD9)SDS12

RT
RB

SISLAN-9 &
10

#P2 (F&G-

4)

SDS13

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

SIS
Drop62/16
2

DCS
Drop57 &
58

Ovation
Lan
SIS Lan

Copyrighted Material / Duplication Prohibited

1 - 47

Ovation SIS Network configuration

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 48

Summary
You should now be able to
Design Ovation SIS Hardware layouts

Define Ovation SIS Power Requirements

Define SISNet Repeater fiber-optic ring layout

Create a New Logic Solver with Ovation Developer Studio

Add a New Logic Solver with Ovation Developer Studio

Assign, Commission and Download a Logic Solver with Ovation Developer Studio

Define the SLS1508 and SISNet Repeater LED indicators

Use Ovation diagnostics to view SISNetwork nodes and subsystems

EMERSON Process Management


Power and Water Solutions

Course OV 236 Rev 2 01/02/2010

Copyrighted Material / Duplication Prohibited

1 - 49