WELCOME TO ALL
TANTRANSCO OFFICIALS
9/5/15
9/5/15
Application:
9/5/15
DC Floating System
In Generation and Transmission substations the
9/5/15
9/5/15
X k
LOAD
BATTERY
CHARGER
X k
9/5/15
Y k
Battery
Charger
Load
X k
X k
Equivalent CKT
Y k
LOAD
Battery
X k
Charger
X k
9/5/15
Load
Charger
X k
Y k
Equivalent CKT
X k
Load
Battery
Charger
Y k
9/5/15
X k
Principle of Operation
Injects low frequency coded pulses into the DCDB
main bus.
Injected signal is traced using receiver unit.
Once there is a ground fault, the injected signals will
get a closed loop to the transmitter ground through
fault ground
The systematic approach of noting where pulses
have been detected, then moving down the feeder up
to the point where pulses are not detected, pinpoints
the ground fault location.
Taurus Confidential Document
9/5/15
Transmitter Unit
15 sq.mm
sensor CT
Receiver Unit
50 sq.mm sensor CT
9/5/15
Earthing Cable
Connection Diagram
Batter
y
Bank
Negative
Bus
Connection
Positive Bus
Connection
Station
Ground
Charge
r
Taurus DC
Transmitter
Unit
Taurus Confidential Document
Fault
Indicatio
n
Taurus DC
Receiver
Unit
Faul
t
9/5/15
Relay Panel
No Fault
Indicatio
n
Demo Pic
9/5/15
Demo Pic
9/5/15
Demo Pic
9/5/15
USP/Product Highlights
Online fault finding
Automatic Capacitance Balancing
Multiple fault detection
Detection of point of mixing in dual Battery system
Noise and harmonics suppression
Exactly pin points the fault
Long duration, service free rechargeable battery
Additional filters in Receiver Unit for AC Noise Suppression for
9/5/15
Specifications
Resistance Range: Up to 400K Ohms
Suitable for DC floating system from 48 to 300V DC
Sensitivity < 1mA
Output Voltage: Auto selectable
Power Supply: Built in Rechargeable Battery
Sensor probes: 2 nos. of 15 & 50 sg. mm
Fault distance: Up to 3KM.
Input signal: LF/LV Pulse
9/5/15
Users
NTPC
State Generating companies
Private Generating Companies
POWERGRID
State Transmission Companies
private Transmission Companies
Captive Power Plants
Process Industries
Mining Industries
Railways
Taurus Confidential Document
9/5/15
Case Study
9/5/15
Case Study - 1
Customer: Rourkela Steel Plant.
Customer Problem:
Problem in 220V system, with voltage conditions as
SOURCE
Positive to
Ground
Negative
to Ground
Positive to
Negative
220
220
9/5/15
Fault Tracing
With our kit, it was found that feeder no.M9 was
Positive to
Ground
Negative
to Ground
Positive to
Negative
110
110
220
9/5/15
Case Study - 2
Customer: JSPL.
Demo Place: JSPL, Angul.
Customer System Status:
SOURCE
Positive to
Ground
Negative
to Ground
Positive to
Negative
1
2
130
130
100
100
230
230
9/5/15
Case Study - 3
Customer: EMCO ENERGY LTD.
Demo Place: 600MW Thermal Power Plant, Warora.
Positive to
Ground
Negative
to Ground
Positive to
Negative
220
220
9/5/15
9/5/15
9/5/15
Case Study - 4
Customer CESC Ltd.
Demo Place- 750MW BBGS, Kolkata.
Equipment was tested on Unit-3 220V DCDB.
SOURCE
Positive to
Ground
Negative
to Ground
Positive to
Negative
DCDB
Unit#3
239
240
9/5/15
9/5/15
SOURCE
Positive to
Ground
Negative
to Ground
Positive to
Negative
DCDB
Unit#3
124
116
240
9/5/15