DC Earth Fault Locator

Application:

To Locate Earth Faults / Earth leakages in floating DC system of a power station.

Taurus Confidential Document

9/5/15

DC Floating System
In Generation and Transmission substations the

entire system of the DC Source along with connecting


cables, battery charger and control equipment forms
DC floating system i.e. at no point it is electrically
connected to earth.

Taurus Confidential Document

9/5/15

Problems with Earth fault on a


DC Floating System

In case of a earth fault either in positive or negative

due to a cable damage or insulation failure the entire


control system gets electrically connected to earth
and no more remains a floating system
Further, a fault happening to this earthed system in
the opposite polarity results in overloading of DC
source, which results in cable burning and disruption
of power to the control equipment and also
malfunctioning of DC System may occur.

Taurus Confidential Document

9/5/15

Healthy DC System single line Diagram

X k
LOAD

BATTERY

CHARGER

X k

Taurus Confidential Document

9/5/15

DC System with Positive fault

Y k

Battery

Charger

Load

X k
X k

Equivalent CKT
Y k
LOAD

Battery

X k

Charger
X k

Taurus Confidential Document

9/5/15

DC System with Negative fault


X k
Battery

Load

Charger
X k

Y k

Equivalent CKT
X k
Load

Battery

Charger
Y k

Taurus Confidential Document

9/5/15

X k

Principle of Operation
Injects low frequency coded pulses into the DCDB

main bus.
Injected signal is traced using receiver unit.
Once there is a ground fault, the injected signals will
get a closed loop to the transmitter ground through
fault ground
The systematic approach of noting where pulses
have been detected, then moving down the feeder up
to the point where pulses are not detected, pinpoints
the ground fault location.
Taurus Confidential Document

9/5/15

DC Earth Fault Locator along with accessories

Transmitter Unit

15 sq.mm
sensor CT

Receiver Unit

50 sq.mm sensor CT

Taurus Confidential Document

Two core connecting cable

DCDB Connecting Cable

9/5/15

Earthing Cable

Connection Diagram
Batter
y
Bank

Negative
Bus
Connection
Positive Bus
Connection
Station
Ground

Charge
r

Taurus DC
Transmitter
Unit
Taurus Confidential Document

Fault
Indicatio
n

Taurus DC
Receiver
Unit

Faul
t
9/5/15

Relay Panel

No Fault
Indicatio
n

Demo Pic

Taurus Confidential Document

9/5/15

Demo Pic

Taurus Confidential Document

9/5/15

Demo Pic

Taurus Confidential Document

9/5/15

USP/Product Highlights
Online fault finding
Automatic Capacitance Balancing
Multiple fault detection
Detection of point of mixing in dual Battery system
Noise and harmonics suppression
Exactly pin points the fault
Long duration, service free rechargeable battery
Additional filters in Receiver Unit for AC Noise Suppression for

trouble free operation in Generating Station


Complies & certified as per IEC 61000-4-2, IEC 61000-4-3, IEC
61000-4-8, IEC 60068-2-6, IEC 60068-2-27, IEC 60068-2-78
IP67 Protection (Pelican casing)

Taurus Confidential Document

9/5/15

Specifications
Resistance Range: Up to 400K Ohms
Suitable for DC floating system from 48 to 300V DC
Sensitivity < 1mA
Output Voltage: Auto selectable
Power Supply: Built in Rechargeable Battery
Sensor probes: 2 nos. of 15 & 50 sg. mm
Fault distance: Up to 3KM.
Input signal: LF/LV Pulse

Taurus Confidential Document

9/5/15

Users
NTPC
State Generating companies
Private Generating Companies
POWERGRID
State Transmission Companies
private Transmission Companies
Captive Power Plants
Process Industries
Mining Industries
Railways
Taurus Confidential Document

9/5/15

Case Study

Taurus Confidential Document

9/5/15

Case Study - 1
Customer: Rourkela Steel Plant.
Customer Problem:
Problem in 220V system, with voltage conditions as
SOURCE

Positive to
Ground

Negative
to Ground

Positive to
Negative

220

220

Taurus Confidential Document

9/5/15

Fault Tracing
With our kit, it was found that feeder no.M9 was

having earth fault. Further traced in sub feeder we


found Fault in Relay panel of bay three.
But after all these exercises we found no
improvement in the voltage.
Once again we started with the DCDB and feeder No
M10 was showing faulty. After isolating the same
system voltage got balanced.
SOURCE

Positive to
Ground

Negative
to Ground

Positive to
Negative

110

110

220

Taurus Confidential Document

9/5/15

Case Study - 2
Customer: JSPL.
Demo Place: JSPL, Angul.
Customer System Status:
SOURCE

Positive to
Ground

Negative
to Ground

Positive to
Negative

1
2

130
130

100
100

230
230

After testing each feeders in both the sources below mentioned

feeders found to be faulty.


S-1=2F-A, 5R-C,5R-D and 1R-D.
S-2=2F-A,5R-C,5R-D and 1R-E.
Customer preferred to switch off the feeders due to lack of
coordination with other Team.
After Switching them OFF system voltage got balanced.
Taurus Confidential Document

9/5/15

Case Study - 3
Customer: EMCO ENERGY LTD.
Demo Place: 600MW Thermal Power Plant, Warora.

Customer System Status:


SOURCE

Positive to
Ground

Negative
to Ground

Positive to
Negative

220

220

Taurus Confidential Document

9/5/15

Positive Dead Fault


After testing each feeder for fault, its finally found in

feeder No. 2.4F which was feeding 6.6KV Control


Panel.
Feeder C1A of 6.6KV Control Panel found to be
faulty.
Tracing further through inside circuitry found
insulation damage on the wire connected between
Relay and CB.
After improving its insulation with help of a
insulation Tape system voltage got balanced.
Taurus Confidential Document

9/5/15

Taurus Confidential Document

9/5/15

Case Study - 4
Customer CESC Ltd.
Demo Place- 750MW BBGS, Kolkata.
Equipment was tested on Unit-3 220V DCDB.

SOURCE

Positive to
Ground

Negative
to Ground

Positive to
Negative

DCDB
Unit#3

239

240

Taurus Confidential Document

9/5/15

Negative Dead Fault


Each feeder was tested for earth fault and fault found

in feeder Nos 14F-B & 14F-D.


Both the above feeders were feeding unit#3 6.6KV
Bus Transfer Panel.
And further traced to a ABB make SUE 3000 HMI
Unit (A monitoring system).
Visibly able to identify the carbon deposition on the
front door display unit (power circuitry).
After replacing it with a new one , system voltage got
improved.
Taurus Confidential Document

9/5/15

System Voltage after Fault rectification


Unit is replaced with a new one and observed the

improved voltage level.

SOURCE

Positive to
Ground

Negative
to Ground

Positive to
Negative

DCDB
Unit#3

124

116

240

Taurus Confidential Document

9/5/15

Taurus Confidential Document

9/5/15