Escolar Documentos
Profissional Documentos
Cultura Documentos
Transformer
IEC-60076-3
Losses on the
transformer
Why using laminated core:
The core is laminated to reduce no load losses.
The eddy current losses due to eddy current
circulation in the core is proportional to the square
of the thickness of the core. If the thickness is
reduce, the eddy current loss and heating of core
is also reduced. The surface of the laminated core
is providing with cooling of insulating varnish or
insulating oxide layer to layer to prevent eddy
current. Burrs and sharp edges shall be avoided,
the core bolts should be fully insulated to prevent
continuous path to circulating current and heating
due to hysteresis loss.
density and
to reduce hysteresis loss and eddy current loss.
No load loss having two component
1. Active or working iron loss component, Iw.= Io Cos
2. Magnetizing iron loss component, Im= Io
Magnetizing Current = Io = Iw2 + Im2
The no load loss= Vo x Io x Cos
Sine
Measurement of No load
loss and No load Current
This test is a routine test of the transformer during FAT.
The no load loss Po and no load current Io are determined
at rated voltage and at rated frequency. The test is
normally carried out at different voltage levels usually from
90% to 110% at 5% intervals. Some times it is from 85% to
120% according to the requirement of the specification.
The voltage shall be applied either from High Voltage (HV)
side of the transformer or from the Low Voltage (LV)side of
the transformer keeping other side open condition.
Suppose, the transformer HV/LV voltage is 132/12 kV and
if applied at HV side, it need 132kV +20% source
transformer to perform at the above mentioned voltage
levels.
Measurement of No load
loss and No load Current
Hence, normally all transformer manufacturers
are doing the no load loss by exciting LV side of
the transformer. Rated excitation is required
either exciting from HV side or LV side with the
respective rated voltage of the winding.
Following losses will be occurred at no load
condition of the transformer.
Iron loss or core loss
Dielectric loss in the insulation
load loss caused by the no load current.
The last two losses are very small and hence,
generally ignored.
Measurement of No load
loss and No load Current
During the no load loss measurement, the applied
voltage wave from
some what differ from the
sinusoidal form. This is due to the harmonics in the
magnetizing current which caused additional voltage
drop in the impedance of the applied voltage. Hence
during this loss measurement, an average type volt
meter ( Mean Value Volt meter) is referred in the VT
secondary for the applied voltage as required the %
of excitation and taken as U. At the same time, a
volt meter responsive to the r.m.s value of the
applied voltage shall be connected in parallel with
the mean value voltmeter and taken as U. The
reading of the mean value and r.m.s voltmeters are
different. The test voltage wave shape is satisfactory
if, the reading of U and U are equal or with in the
3% range.
Measurement of No load
loss and No load Current
A wave form correction factor shall be
applied to the measured loss as per the
below formula for getting actual loss at
sinusoidal wave form of the applied voltage.
Po = Pm (1+d)
Where d= U-U
( usually negative
value )
U
Where Po = corrected loss, Pm= Measured
loss,
U= mean value Voltmeter reading
and U= r.m.s Voltmeter reading.
Measurement of No load
loss and No load Current
The frequency of the applied voltage shall be at the rated
frequency of 50Hz. If the frequency is differ from the rated
value and is with in the IEC tolerance of 3% (48.5 to 51.5
Hz) a frequency correction factor also required to the
applied voltage. Consider the test frequency is 49Hz and
51 HZ. The corresponding correction in the applied voltage
will be 49 X V and 51 X V respectively, since the
50
50
core is designed for the rated frequency of 50Hz. If less
frequency from rated, the excitation of the core will be
more than rated excitation and vice versa.
Measurement of No load
loss and No load Current
Measurement of No load
loss and No load Current
For loss measurement watt meters are using to
measure the loss and now a days Power Analyzer
is using in place of watt meters. Two connection
methods are using in three phase transformer for
loss measurement.
Two watt meter method
Three wattmeter method
Generally three wattmeter method are using
and is more accurate than using two watt meters.
Two watt meter method
Equipments required:
Source Transformer with suitable voltage
regulating system
Measurement of No load
loss
CTs 3 nos (suitable to required rating of voltage
and current)
VTS - 2 Nos line to line (suitable to required rating
of voltage)
Frequency meter.
Average type volt meter
R.m.s type Voltmeter (V1,V2&V3)
3 Ammeters with suitable range (A1,A2 &A3 )
2 Watt meters with low power factor (W1& W2)
or
Power analyzer.
Measurement of No load
loss
Three watt meter method
Equipments required:
Source Transformer with suitable voltage
regulating system
CTs 3 nos (suitable to required rating
of voltage and current)
VTS - 3 Nos Phase to Earth (suitable to
required rating of voltage)
Measurement of No load
loss and No load Current
Frequency meter.
Average type volt meter
R.m.s type Voltmeter
3 Ammeters with suitable range (A1,A2 &A3
)
3 Watt meters with low power factor
(W1, W2 &W3)
or
Power analyzer.
Measurement of No load
loss and No load Current
Measurement of No load
loss and No load Current
With the above test conditions, the voltage shall be raised
up to the saturation level and slowly reduced to the
minimum possible value and repeated two three times for
demagnetizing the core. After demagnetization, the
voltage shall be applied to the required levels and take all
readings in all levels.
Calculations
Total measured loss =Po= W1+W2
or W1+W2+W3
Corrected loss =Pm= Po X wave form correction factor X
frequency correction factor, if required.
Magnetizing Current (average)=Io= A1+A2+A3/3
Applied Voltage (average) =Vo = V1+V2+V3/3
or
Direct readings in the Power Analyzer.
Measurement of No load
loss and No load Current
Wattmeter constant and Multiplication Factor
Wattmeter constant : Voltage selection in WM x Current selection in WM x
power factor
(WK)
Tolerance of losses
The no load loss is always in the core when a transformer is
energized at no load condition and hence no load loss of a
transformer is a permanent losses of the transformer. The
penalty of the excess no load loss than the specified limit is
more than that of load loss since load loss is varying
according to the load.
As per IEC
Losses has no positive tolerance and is specified the
maximum value. That means, the measured value should
not be more than the specified value.
Total losses has a positive tolerance of 10% is allowed
Component losses has a positive tolerance of 15% is
allowed provided that the tolerance for the total losses is
not exceeded.
Penalty of losses
Penalty for excess loss as per DEWA
specification
For no load loss: 36,000.0 Dhs/kW within 5% in
excess of guarantee values and 72,000.0 Dhs/kW
above 5% in excess of guarantee values.