Lesson Content
Describe the acceptable methods for
determining the maximum demand on an
installations consumers mains.
Calculate the maximum demand for the
consumer's mains for given installations up to
400 A per phase.
What is Maximum
MD
Demand?
Is the Maximum continuous current that flows in a
circuit for a period of 15 minutes or longer
AS/NZS 3000
1.6.3
Why not just put a cable size in, that will handle the
current rating for the maximum current rating of the
appliance?
AS/NZS 3000
Table C4
MD can be determined
by:
AS/NZS 3000
2.2.2.
Calculation
Assessment
Measurement
Limitation
MD of Mains &
Submains
AS/NZS 3000
Clause 2.2.2 (d)
m
u
MD of Mains & Submains
m
i
in
m
2
10+10+16+16+3
By
Calculation
a
16mm2 ify
m
2=
c 36
m Amps
84 Amps
e
6
p
1
MD =
?f
s
2
s
2.5mm
o
10mm2
e e
i
t
i iz
r
20 metres tho le s
46 metres
a u ca b
y s
l
p in
p
10A
10A 16A 16A
32A
u
a
s mL1 L2
t
P1
P2
Stove
s
o
M
Domestic House
So how do we calculate
MD?
Domestic Table C1
Non-domestic Table C2
Non- domestic Energy Demand
Table C3
= 3 points
Note e
Note d
2 x 2.6 metres track
light =
5 points per 10
track = points
Not regarded as
Lighting
Fixed Space
Heating
Load Group D
Calculations
A house consists of the
following:
Assume to be <150W
3000 W
230V
Ai
Ai
D
Ai
Ai
Aii
Aii
33 + (3 x 3) = 42P
3P
3 x 2 x 2 = 12P
12P
13.04A
Calculations
A house consists of the
following:
36 light fittings, 3 consisting of 3 lamp combinations
3 bathroom exhaust fans
2 x 750W heat lamp, fan, light combinations
3 x 2metre track lights
12 wall lights around the veranda
6 x 100W bollard lights on driveway
6 x 400W metal halide flood lights for pool
42P
3P
12P
12P
69P
1 20 =
21 40 =
41 60 =
61 69 =
Ai
Ai
D
Ai
Ai
Aii
Aii
33 + (3 x 3) = 42P
3P
3 x 2 x 2 = 12P
12P
13.04A
3A
2A
2A
2A
9A + 13.04A =
22.04A
3 Light Calculations
Broken up evenly
36 light fittings
3
A B
12 Fittings / 3A 3A
C
3A
NOT
36 light fittings = 3A + 2A = 5A
3
A B C
1.6 1.6 1.6
Calculations
A house consists of the
Broken up evenly over 3 Phases
following:
36 light fittings, 3 consisting of 3 lamp combinations
3 bathroom exhaust fans
Divide by 3
2 x 750W heat lamp, fan, light combinations
3 x 2metre track lights
12 wall lights around the veranda
6 x 100W bollard lights on driveway
6 x 400W metal halide flood lights for pool
14P
1P
4P
4P
23P
Ai
Ai
D
Ai
Ai
Aii
Aii
11 + (1 x 3) = 14P
1P
1 x 2 x 2 = 4P
4P
4.35A
1 20 = 3A
21 23 = 2A
5A + 4.35A =
9.35A /
Power Points
Load Group Bi
Double Power Points
36 Double Power Points
6 Single power points
Notes
h
36 x 2 =72P
6P
1 20 =
78P
21 40=
41 60 =
61 78 =
10A
5A
5A
5A
25A
Power Points
Load Group Bi
Notes
h
36 x 2 =72P
6P
AND
Other Direct Wired
Equipment that is <10A
Air conditioners
Cook tops
Water heaters
78P
1 20 =
21 40=
41 60 =
61 78 =
10A
5A
5A
5A
25A
Power Points
NOT
Calculations
A house consists of the
following:
20 Double power points
8 Single power points
8A swimming pool pump
34 x 15A power points
12A Air-conditioner supplied via a 15A power point
14A Pool heater direct wired
Bi
Bi
Bi
Bii
D
G
20 x 2 = 40P
8P
1P
10A
-
Calculations
A house consists of the
following:
20 Double power points
8 Single power points
8A swimming pool pump
3 x 15A power points
12A Air-conditioner supplied via a 15A power point
14A Pool heater direct wired
40P
8P
1P
49P
Bi
Bi
Bi
Bii
D
G
1 20 = 10A
21 40 = 5A
41 49 = 5A
20A + 10A =
30A
20 x 2 = 40P
8P
1P
10A
-
Load Group C
Cook tops
Wall ovens
Washing machines
Clothes driers
Load Group D
15 litre heater
with a 2.4kW element
2400/15 =
160 W/L
8 W/L
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
22 x Double 10 A socket outlets
1 x 10kW range
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
22 x Double 10 A socket outlets
1 x 10kW range
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS
7A
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
44 + 4 = 48P 10 + 5 + 5 =
22 x Double 10 A socket outlets 44P
1 x 10kW range
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS
7A
20A
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
22 x Double 10 A socket outlets
1 x 10kW range (10000/230) x 0.5 =
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS
7A
20A
21.7A
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
22 x Double 10 A socket outlets
1 x 10kW range
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS
13 x 0.75 =
7A
20A
21.7A
9.75A
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
22 x Double 10 A socket outlets
1 x 10kW range
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS 4600/230 =
7A
20A
21.7A
9.75A
20A
Maximum Demand
Ai
Bi
Bi
C
D
F
2 x 60 W exhaust fans
4 x Single 10 A socket outlets
22 x Double 10 A socket outlets
1 x 10kW range
1 x Permanently connected air conditioner (full load current of 13 A)
1 x 4.6 kW continuous HWS
7A
20A
21.7A
9.75A
20A
78.45A
Uneven 3 Loads
Not all single phase loads will break up evenly over
three phases
But the phases must not be unbalanced by more than
25A
NSW S&IR
Clause 1.10.3
3 Maximum Demand
Ai A 30 x
Ai B 18 x Lights
Aii C 6 x 400W mercury vapour flood lights
Bi A 15 x Double power points (p/p)
Bi B 10 x Single p/p & 15 x Double p/p
Bii C 3 x 15A Single p/p
C A 1 x 4.1kW wall oven
C B 1 x 4.6kW cook top
F C 1 x 3.6kW heat pump HWS
A
D B
C
3 Maximum Demand
Ai A 30 x
Ai B 18 x Lights
5A
3A
18P
7.83A
30P
10+30P
10+5A =
15A
20A
10+5A =
10A
(4100230)x0.5 =
8.91A
10A
(4600230)x0.5 =
15.65A
3600230 =
6.17A
6.17A
6.17A
Multiple Domestic
Submains to individual units
Unit 1
MSB
Unit 2
Unit 3
Columns 3, 4 or 5
Column 2
Questions to be
Asked?
How
How
6 Units
3
18 Units
3
66 Units
3
Maximum Demand
A house consists of the
following:
Ai 26 x Light points
26 + 4 = 30P
4.9A
10A + 5A + 5A = 20A
3A + 2A = 5A
52 + 5 = 57P
10A
(5600W/230V)x0.5
C 1 x 5.6kW wall oven / cook top
(3600W/230V)x0.75
D 1 x 3.6kW air conditioner
12.2A
10.4A
11.7A
74.2A
Multiple Domestic
9 Units consists of the
following:
9 Units
3
= 3 Units / Phase
Use Colum 3
Ai 26 x Light points
6A
10A
15A
35.2A
6A x 3 = 18A
109A
Multiple Domestic
30 Units consists of the
30following:
Units
3
Ai 26 x Light points
10A
2.8A x 10 = 28A
117A
6A x 10 = 60A
275A
Multiple Domestic
66 Units consists of the
66following:
Units
3
Ai 26 x Light points
0.5A x 22 = 11A
10A
2.8A x 22 = 61.6A
258A
100A + (0.8A x 22) =118A
550A
A
5 Units
Col 3
B
5 Units
Col 3
C
6 Units
Col 4
Multiple Domestic
16 Units consists of the
following:
5 Units / A & B
Ai
26 x Light points
Bi
Bi
Use Colum 3
6A
10A + (5A x 5) =
35A
10A
15A
58.7A
52.2A
(2400230V) x 5 =
176.9A
Multiple Domestic
16 Units consists of the
following:
6 Units / C
Ai
26 x Light points
Bi
Bi
Use Colum 4
5A + (0.25A x 6) =
6.5A
15A + (3.75A x 6) = 37.5A
10A
2.8A x 6 =
(3600230) x 0.75 x 6
16.8A
70.4A
6A x 6 =
36A
177.2A
A
5 Units
Col 3
176.6A
B
5 Units
Col 3
176.6A
C
6 Units
Col 4
177.2A
Communal Load
Loads that are used by all the unit dwellers
Driveway/ parking lighting
Stairwell lighting
Power points for cleaners
Lifts
Swimming pool pumps
Multiple Domestic
16 Units have a communal load consists of
the following:
H 20 x 80 W bollard Lights
14.78A
H 30 x light points
I
15A
7.8A
15A
12A
15 x 1.25 =
18.75A
83.33A
Table C2 Colum
2 circuits could also be divided across
These
Socket outlets
In a FactoryOn each
19 x 750W = 15.25kW
15250 230 = 66.3 Amps
19 x 100W = 2.9kW
2900 230 =12.6 Amps
Socket outlets
5 x 10A 3 outlets
Treat as B(i)
1000W + 4 x 750W =
Per Phase
4kW
4000 230 = 17.4
Amps
2 x 32A 3 outlets
5 x 20A 3 outlets
Per Phase
75% x 32A
32A + 24A +
75% x 20A x 5
131Amps
75A =
Motors
In
Factories
2 x 30A 3 motors
3 x 15A 1 motors
1 per phase
22.5A +
22.5A = 75 Amps
Welders
3
AS/NZS 3000
C2.5.2.2 (b)
x 20A 3 Welders
W1
W2
Only 2 welders on
each phase
W3
20A + 20A = 40 Amps
Per Phase
Table C3
Light/Power = 50 VA/m2
Reverse cycle AC =
63.750kVA
3 x 400
25 VA/m2
75 VA/m2 x 850 63.750kVA
=
92
Amps/Phase