Escolar Documentos
Profissional Documentos
Cultura Documentos
Architecture
Mark II
1973
2181
Gas Turbine
Discrete Solid-state
for Sequencing. IC's
& Microprocessor for
Control
Single
Meters, PBs,
Switches, Solid-state
Annuniciator
Mark IV
Mark V
Mark VI
1982
1991
1997
1080
3411
915
Gas Turbine
Gas / Steam
Turbine / BOP
Complete
Upgradable CPUs.
Microprocessor
Distributed
VME Backplane.
Based. 8086/80286. Processors 186/196. Distributed
Proprietary Backplane Proprietary Backplane Controllers
Single / Triple
Single / Triple
Single / Triple
Black & White
PC. Initially
Monitor with
Proprietary. Later
Windows PC with
Membrane PBs
Windows, Cimplicity Cimplicity GUI
Modbus & Ethernet
Serial & Proprietary TCP-IP GSM
Mark VI e
2004
Governor / BOP
Upgradable CPUs.
cPCI Backplane.
Networked I/O.
Local/Remote
Single / Dual / Triple
Windows PC with
Cimplicity GUI
Modbus, Ethernet
Modbus, Ethernet
Hardwired
Hardwired
GSM, OPC, DNP 3.0 GSM, OPC, DNP 3.0
10MB Ethernet, Peer- 100MB Ethernet,
to-Peer
Peer-to-Peer
Networks
NA
NA
NA
Arcnet
Communications
Communications
Maintenance Analog Cablibration, Analog Cablibration,
Software Calibration, Software Calibration,
Interface
Pots, Timers
Pots, Timers
Software Calibration Software Calibration Windows Based
Windows Based
Overview
Common items in any Mark VIe Control
System
HMI
Viewer
IO Net
PD
H
IO Pack
Controller
Terminal Board
UD
H
HMI
Server
The Controllers
The Software
The Networks
Communications
Controller Enclosure
6 Slot CPCI
Backplane for power only
CPCI Power Supply
+-12, +5 +3.3 VDC
Optional 2nd Power
Supply
Controller
CPCI form factor for
mounting in rack
Operating System is QnX
Permanent storage is
Compact Flash
Up to 3 RJ-45 IO Net
connections
There are 3main
controllers:
> UCCA
> UCCC
> UCSA
IO Packs
1 Generic Processor
Board
1 PACK specific A/D
board
-30 Deg C. to +60 Deg
C.
IR Port
2 IONet Ethernet RJ45
IONet Switches
Switch Types
N-TRON 500 Series
508TX 8 10/100 BaseTX RJ-45 Ports
516TX 16 10/100 BaseTX RJ-45 Ports
509FX 8 10/100 BaseTX RJ-45 Ports
1
100 BaseFX Fiber Port
517FX 16 10/100 BaseTX RJ-45 Ports
1
100 BaseFX Fiber Port
Features
Operating Temp: -40 to 85C
Operating Humidity: 10 to 95% Non-Condensing
Shock: 200g @ 10ms
Vibration / Seismic: 50g, 5-200Hz, Tri-axial
MTBF: > 2M hours
Auto-sensing 10/100 Base TX, Duplex, and MDIX
Up to 2.6Gb/s, High Speed Backplane
Steel Enclosure, Prevents EFI and RFI
DIN-Rail or Rack Mounted
Redundant Power Inputs 10-30Vdc,
- 200ma (w/o fiber) 400ma (w fiber) at 24Vdc
Bi-color LEDs for Link, Speed, Activity, and Duplex Status
Emissions and Safety Approvals
FCC Part 15 Class A
UL Listed (US & Canada)
Class 1, Div 2, Groups A, B, C, D, T4A
CE: EN55011, EN61000-6-2 and 6-4
EN61000-4-2,3,4,5,6,11, EN61010-1 Class III,
Pollution Degree 2
UDH Communicator
Processor selected to send EGD data and
Alarm
Data over the UDH
All controllers receive EGD Data from the
UDH
In the event that a controller can not receive
UDH EGD Data, the controller will request the
data over the IONet from the UDH
communicator
Redundancy
4 different levels
Field Devices (Simplex, Dual, TMR)
Controllers (Simplex, Dual, TMR)
IO Network (Single, Dual, Triple)
IO Pack (Single, Dual, Triple)
Voting
Voting is separated into 2 different categories
> Inputs
> Outputs
Inputs voted in Software (SIFT)
> 2 out of 3 for logics
> Median Select for analogs
> Voting Disagreement Detector (Voter Mismatch)
Output Processing
TMR system outputs voted in Hardware at
the TB.
For Dual System or Simplex system
outputs are set by the Designated
Controller
Mark VIe
Flexible redundancy
High bandwidth I/O network;
time synchronized to Sec
High accuracy across broad
temperature range
Architecture provides clean
upgrade path