Instrumentation
Process Control
Prepared By: Engr. Alexis John M. Rubio
Industrial
and
LEARNING OBJECTIVES
At the end of the class the students can be able to:
Introduction
Process Control
Process control is the automatic control of an
output variable by sensing the amplitude of the
output parameter from the process and comparing
it to the desired or set level and feeding an error
signal back to control an input variable.
Process Control
Process Control
Example
Instrument Parameters
The accuracy of an instrument or device is the
difference between the indicated value and the actual
value. Accuracy is determined by comparing an
indicated reading to that of a known standard.
Accuracy depends on linearity, hysteresis, offset, drift,
and sensitivity. The resulting discrepancy is stated as a
deviation from the true value, and is normally
specified as a percentage of
full-scale reading or
deflection (%FSD).
Accuracy can also be expressed as the percentage of
span, percentage of reading, or an absolute value.
Instrument Parameters
The range of an instrument specifies the lowest and
highest readings it can measure, i.e., a thermometer
whose scale goes from -40C to 100C has a range
from -40C to 100C.
The span of an instrument is its range from the
minimum
to
maximum
scale
value,
i.e.,
a
thermometer whose scale goes from -40C to 100C
has a span of 140C. When the accuracy is expressed
as the percentage of span, it is the deviation from
true expressed as a percentage of the span.
Reading accuracy is the deviation from true at the
point the reading is being taken and is expressed as
Instrument Parameters
Example:
1. A pressure gauge ranges from 0 to 50 psi, the worstcase spread in readings is 4.35 psi. What is the
%FSD accuracy?
2. If the deviation of 4.35 psi in the first problem is was
measured at 28.5 psi, what is the reading accuracy?
3. In the data sheet of a scale capable of weighing up to
200 lb, the accuracy is given as 2.5 percent of a
reading. What is the deviation at the 50 and 100 lb
readings, and what is the %FSD accuracy?
Instrument Parameters
The absolute accuracy of an instrument is the
deviation from true as a number not as a percentage,
i.e., if a voltmeter has an absolute accuracy of 3 V
in the 100-volt range, the deviation is 3 V at all the
scale readings, e.g., 10 3 V, 70 3 V and so on.
Precision refers to the limits within which a signal
can be read and may be somewhat subjective.
The total accuracy of the system is statistically the
root mean square (rms) of the accuracy of each
element.
Instrument Parameters
Instrument Parameters
Hysteresis is the difference in readings obtained when
an instrument approaches a signal from opposite
directions,
Resolution is the smallest amount of a variable that an
instrument can resolve, i.e., the smallest change in a
variable to which the instrument will respond.
Repeatability is a measure of the closeness of
agreement between a number of readings (10 to12)
taken consecutively of a variable, before the variable
has time to change. The average reading is calculated
and the spread in the value of the readings taken.
Instrument Parameters
Linearity is a measure of the proportionality between
the actual value of a variable being measured and
the output of the instrument over its operating
range.
Example
In a temperature measuring system, the transfer
function is 3.2 mV/k 2.1%, and the accuracy of the
transmitter is 1.7%. What is the system accuracy?
What is the non-linearity of the given pressure
gauge below?
Example
What is the hysteresis in terms of %FSD of the given
pressure gauge sensor?
Seatwork
1. A pressure sensor has a span of 25 to 150 psi.
Specify the error when measuring 107 psi, if the
accuracy of the gauge is (a) 1.5% of span, (b) 2%
FSD, and (c) 1.3% of reading.
2. A pressure sensor has an accuracy of 2.2% of
reading, and a transfer function of 27 mV/kPa. If the
output of the sensor is 231 mV, then what is the
range of pressures that could give this reading?
3. What is the sensitivity of an instrument whose
output is 17.5 mV for an input change of 7C?
Seatwork
4. A pressure sensor has a range of 30 to 125 kPa and
the absolute accuracy is 2 kPa. What is its percent
full-scale and span accuracy?
5. A flow sensor has a range of 0 to 25 m/s and a FSD
accuracy of 4.5 percent. What is the absolute
accuracy?
6. A temperature instrument has a range -20F to
500F. What is the error at 220F? Assume the
accuracy is (a) 7 percent of FSD and (b) 7 percent
of span.
Seatwork
7. What is the hysteresis of the pressure sensor as a
percentage of FSD?