PROTECTION OF AC MACHINES
AGAINST INTERNAL FAULTS
Document By
SANTOSH BHARADWAJ REDDY
Email: help@matlabcodes.com
Engineeringpapers.blogspot.com
More Papers and Presentations available on abov
TR 1
DIFFERENTIAL RELAY
IpTAPErqoutie50cmdn2-lTAIp
Differential Protection
T.AILPErqoutiepcmdnIRT.A
Differential Protection
G1
I2
Id
100
100
NORMAL LOAD
500
500
THROUGH FAULT
(500%)
500
300
200
INTERNAL FAULT
(200%)
100
80
20
INTERNAL FAULT
(20%)
NOTE :
1.
THROUGH FAULT CONDITION HAS TO BE DETECTED BY
NORMAL O/C RELAY (SINCE FAULT CURRENT IS
HIGHER THAN 100%)
2.
SATABILITY OF
DIFFERENTIAL RELAY
CIRCULATING CURRENT
(HIGH IMPEDANCE)
PERCENTAGE BIASED
(LOW IMPEDANCE)
CIRCULATING CURRENT
HIGH IMPEDANCE DIFFERENTIAL RELAY
I1 - I2
RELAY OPERATING
CURRENT
TRIP
SETTING
IN TERMS OF
CT PRIMARY
(20% OF In)
CIRCULATING CURRENT
HIGH IMPEDANCE DIFFERENTIAL RELAY
Id
Is =20%
0.5
1.0
1.5
2.0
2.5
CIRCULATING CURRENT
HIGH IMPEDANCE DIFFERENTIAL RELAY
DISADVANTAGES :
DUE TO CT CHARACTERISTICS MISMATCH,
RELAY CAN DETECT A CONDITION WHERE
I1-I2 EXCEEDS SET VALUE
A)
B)
C)
CIRCULATING CURRENT
(HIGH IMPEDENCE) DIFFERANTIAL RELAY
ADD A
STABILISING RESISTOR
TO IMPROVE
PERFORMANCE
CIRCULATING CURRENT
HIGH IMPEDANCE DIFFERENTIAL RELAY
STABILISING RESISTOR
WILL IMPROVE PERFORMANCE OF RELAY
FOR CT CHARACTERISTICS MISMATCH
- TO CERTAIN LIMITS
BUT RELAY HAS BECOME INSENSITIVE
DUE TO ADDITION OF RESISTOR.
RELAY MAY NOT TRIP FOR A REAL
INTERNAL FAULT.
BIASED DIFFERENTIAL
I1 - I2
RELAY OPERATING
CURRENT
(I1+I2)/2
RELAY RESTRAINING
CURRENT
TRIP SETTING =
(BIAS %)
(I1- I2)
(I1 +I2)/2
BIASED DIFFERENTIAL
INTERNAL FAULT
EXTERNAL FAULT
BIAS PERCENTAGE
( I1-I2)
DIFFERENCE
CURRENT
RELAY OPERATES
%Id
MIN I1-I2
SLOPE
I1+I2
2
SUM CURRENT
DUAL SLOPE ?
DIFFERENTIAL RELAYS
INTERPOSING CTs
IN TRANSFORMER DIFFERENTIAL RELAYS
FOLOWING COMPENSATIONS WILL BE
REQUIRED FOR:
A)
B)
DIFFERENTIAL RELAYS
INTERPOSING CTs
INELECTROMECHANICAL / SOLIDSTATE RELAYS
INTERPOSING CTs ARE USED FOR PROVIDING
THE MAGNITUDE AND VECTOR COMPENSATION
IN NUMERICAL RELAYS THE SOFTWARE INSIDE
INSIDE THE RELAY TAKES CARE OF THESE
COMPENSATION
1. YY0
B
2. YY6
B
Y
R
3. YD1
4. YD11
WHY REF ?
1.
2.
3.
4.
5.
6.
7.
8.
PERCENTAGE BIASED
DUAL SLOPE
DISPLAYS OF Id
VECTOR/AMPLITUDE
COMPENSATION
(W/O ICTs)
2ND HARMONIC RESTRAINT
5TH HARMONIC RESTRAINT
WAVE FORM CAPTURE
INBUILT REF