Escolar Documentos
Profissional Documentos
Cultura Documentos
1
Basic Requirements.
Before we install or modify a circuit, we must make
sure
1. That we calculate the total current that the circuit will
need to carry in relation to the power of the connected
load.
2. That we use the correct specification & rating of
protective device suitable for that load / current.
3. That we use a cable large enough so that it will always be
protected by the fuse or circuit breaker (MCB) from
damage due to over-current, taking into account any
correction factors applicable.
4. That earth loop impedance (Zs) is not excessive, so as to
achieve the required disconnection time for the circuit.
5. That volt drop for the circuit is within the tolerances
allowed.
2
Step 1
Calculate Design Current (Ib).
V I
V = Supply voltage (volts)
V
3
Calculate Design Current (Ib).
230V
= 17.4A
4
Calculate Design Current (Ib).
Wattage Voltage Ib
500w 230
2.25kW 240
1700w 233
9.5kW 238
1750w 110
5
Calculate Design Current (Ib)
Solution.
Wattage Voltage Ib
500w 230 2.17A
2.25kW 240 9.38A
1700w 233 7.3A
9.5kW 238 39.92
1750w 110 15.91
5.2kW 230 22.61
6
Step 2 Selection of Protective
Device Rating (In).
In Ib
It I n
In simple terms, this states that the rating of the
cable (It) must be greater than or equal to the
current rating of the protective device common
sense, otherwise the cable could become the fuse!
10
Select Cable Size for Current
Carrying Capacity (It).
Assuming we are using PVC flat (T&E) type cable, the tabulated
current carrying capacity (It) for different sizes of cable can be
found in table 7.1 (ii) / pg. 69 of the On-Site-Guide (OSG). For
other types of cable, refer to Appendix F.
Decide which rating / size of cable you would use for the
protective devices chosen earlier, based upon the rule It In
and assuming the cable is clipped direct (installation reference
method C). We will discuss the other installation methods later.
Example:
Wattage Voltage Ib Type In It / size
5.2kW 230 22.61A C MCB 32A 37A / 4.00mm2
11
Select Cable Size for Current
Carrying Capacity (It).
Decide which rating / size of cable you would use for the protective
devices chosen earlier, based upon the rule It In and assuming the
cable is clipped direct (installation reference method C). We will
discuss the other installation methods later.
Wattage Voltage Ib Type In It / size
500w 230 2.17A BS 3036 5A
2.25kW 240 9.38A BS 1361 10A
1700w 233 7.3A BS 88 10A
9.5kW 238 39.92 B MCB 40A
1750w 110 15.91 BS 3036 20A
12 5.2kW 230 22.61 C MCB 32A 37A / 4.00mm2
Select Cable Size for Current
Carrying Capacity (It) Solution.
Decide which rating / size of cable you would use for the protective
devices chosen earlier, based upon the rule It In and assuming the
cable is clipped direct (installation reference method C). We will
discuss the other installation methods later.
Wattage Voltage Ib Type In It / size
500w 230 2.17A BS 3036 5A 16A / 1.00mm2
Clipped
direct or
embedded in plaster.
15
Installation Method B.
Runin conduit or
trunking.
16
Installation Methods
100, 101 & 102.
Method 102
In contact with
thermal insulation.
Method 100
17
Installation Method 103.
To be avoided, as the
thermal effect can halve
the current carrying
capacity compared to a
cable clipped direct
(method C).
18
Effects of Thermal Insulation.
It can be seen from OSG table 7.1 (ii) that the cable size may
need to be increased for our circuits if the cable is not
clipped direct (installation method C).
Recalculate the cable size for the following methods.
21 3/13/17
Voltage Drop.
Fused time
B 16A MCB
control.
or 15A fuse.
Lighting circuit 3%
6.9 volts for a 230v supply.
Equal to 223v minimum at load terminals.
Other circuits 5%
11.5 volts for a 230v supply.
Equal to 218.5v minimum at load terminals.
24 3/13/17
OSG: Appendix F pg. 145
Voltage drop = 18 x 13 x 19
= 4.47 V
1000
Is this a pass?
26
The End.
27
How long can circuits be before Zs
& volt drop become too high?
28 3/13/17
How long can circuits be before Zs
& volt drop become too high?
29 3/13/17
Worked examples using table 7.1
for Standard Circuits.
What is the cable size / maximum length to be
used?
1. Ring circuit, 30A BS 3036 re-wireable fuse, installation
method C, TN-S system with RCD.
_______________ or _________________
2. Outdoor lighting circuit, 6A type B MCB, installation
method 101, TN-C-S system without RCD.
_______________ or _________________
3. Immersion heater, 15A BS 1361 cartridge fuse,
installation method 102, TT system.
_______________ or _________________
30
OSG: Appendix F pg. 145 -
Correction Factors.
We have already seen from OSG table 7.1(ii) - pg.
69, that if a cable is surrounded by thermal
insulation along its whole length (method 103) it
halves the current carrying capacity of the cable
compared to clipped direct (method C). This
represents a derating factor.
Other correction factors can be applied using the
formula -
It In
Correction factors
31
OSG: Appendix F pg. 145 -
Correction Factors.
Ca ambient temperature F1
Ci thermal insulation F2
Cg grouping F3
Where more than one correction factor applies, they must be multiplied.
32
Some Example of Applying
Correction Factors.
If our immersion heater circuit was protected by a
15A rewireable fuse to BS 3036 and the circuit
cable was bunched with 3 other circuits in PVC
trunking (method B table 7.1(ii) pg. 69).
It In It 15
Correction factors 0.725 x 0.70
34
The End.
Any questions?
35