Capacity Building programme on

New Techniques and Strategies in


Prevention and Management of Industrial
Disasters

Standard Codes followed in Hazardous


Industries
LPG Storage and Handling installations

Presentation by

C. Vijay Kumar,
Senior Manager (LPG-Engg), IOCL, Karnataka
APPLICABLE STANDARDS & STATUTORY
REGULATIONS
1.0 STATIC AND MOBILE PRESSURE VESSELS(UNFIRED)
RULES:1981
TO REGULATE THE CONSTRUCTION, FITMENT,LOADING
TRANSPORT AND INSPECTION OF UNFIRED VESSELS IN
SERVICE OF COMPRESSED GAS(LPG) WITH CAPACITY
EXCEEDING 1000 LTR.
PESO (CCOE) LICENSE FOR BULK STORAGE
2.0 GAS CYLINDER RULES: 1981
TO REGULATE POSSESSION, DELIVERY, STORAGE, HANDLING
AND EXAMINATION/TESTING OF CYLINDERS LIMITED UPTO
CAPACITY 1000 L.
PRIOR APPROVAL FROM CCOE BEFORE CONSTRUCTING ANY
NEW FACILITIES OR ALTERING THE EXISTING FACILITIES FOR
FILLING CYLINDERS AND STORAGE AREA
PESO LICENSE FOR FILLLING OF CYLINDERS
PESO LICENSE FOR STORAGE OF FILLED CYLINDERS
APPLICABLE STANDARDS & STATUTORY
REGULATIONS
3.0 FACTORIES ACT: 1948
APPROVAL FOR DRAWINGS FOR CONSTRUCTION OF FACTORY/
INSTALLATION BY DIRECTOR, DEPARTMENT OF FACTORIES &
BOILERS.
ADHERENCE TO FACTORIES ACT 1948 AND STATE FACTORIES
RULES
WRITTEN SAFETY POLICY WRT HEALTH AND SAFETY OF
WORKMEN
MAINTENANCE OF UPDATED ONSITE MANAGEMENT PLAN

4.0 WEIGHTS AND MEASURES RULES:1987


WEIGHTS AND MEASURE CERTIFICATE FOR WEIGH BRIDGE,
FILLING MACHINES AND CHECK SCALE
PERMISSIBLE ERRORS ON NET QUANTITIES DECLARED BY
WEIGHT OR BY VOLUME AS PER ACT
APPLICABLE STANDARDS & STATUTORY
REGULATIONS

5.0 ENVIRONMENTAL REGULATIONS


CONSENT OF STATE POLLUTION CONTROL BOARD FOR
DISCHARGE OF SEWAGE OR EFFLUENTS INTO A STREAM OR
ON LAND

CONSENT OF STATE POLLUTION BOARD FOR DISCHARGE OR


EMISSION OF AIR POLLUTANTS FOR OPERATION OF DG SET
& FIRE ENGINES

6.0 INDIAN ELECTRICITY RULES - 1956

7.0 THE MOTOR VEHICLES ACT - 1988.


APPLICABLE OISD STANDARDS &
GUIDELINES
OISD STD 144 LIQUEFIED PETROLEUM GAS (LPG)
INSTALLATIONS
OISD GDN 169 OISD GUIDELINES ON SMALL LPG BOTTLING
PLANTS (DESIGN & FIRE PROTECTION FACILITIES)
OISD STD 150 DESIGN AND SAFETY REQUIREMENTS FOR
LIQUEFIED PETROLEUM GAS MOUNDED STORAGE FACILITY
OISD STD 105 WORK PERMIT SYSTEM
OISD STD 128 INSPECTION OF UNFIRED PRESSURE VESSELS
OISD STD 132 INSPECTION OF PRESSURE RELIEVING
DEVICES
OISD STD 137 INSPECTION OF ELECTRICAL EQUIPMENT
OISD STD 154 SAFETY ASPECTS IN FUNCTIONAL TRAINING
OISD STANDARD 144
Minimum safety requirements on design, layout,
storage, loading / unloading, operation, inspection
& maintenance, fire protection, emergency planning
and safety audit systems of LPG Installations.

Not applicable to bottling plants having a bulk LPG


storage capacity not exceeding 300 MT (above
ground) or 450 MT in case of mounded or in
combination of above ground and mounded with
total bottling quantity not exceeding 35MT per shift
of eight hours. Such small bottling plants are
covered under OISD GDN 169.
Installation layout & design consideration
Storage & Handling of Bulk LPG
Bottling operations
Maintenance and inspection
Safety
a) Fire Protection Facilities
b) Gas Monitoring System
c) Emergency Management Plan
d) Safety Audit
TABLE I
OISD 144- INTER DISTANCES FOR LPG FACILITIES
1 2 3 4 5 6 7
1. LPG STORAGE VESSELS * T-II 30 30 30 15 60
2. BOUNDARY/PROPERTY LINE/ T-II -- 30 30 30 30 --
GROUP OF BLDGS NOT ASSO-
CIATED WITH LPG PLANT
3. SHED-LPG 30 30 15 30 30 15 60
4. TW/TT GANTRY-LPG 30 30 30 50 50 30 60
5. LPG/OTHER RAIL SPURS 30 30 30 50 50 30 60
6. PUMP HOUSE/COMPRESSOR 15 30 15 30 30 -- 60
HOUSE(LPG)
7. FIRE PH 60 ** 60 60 60 60 --

Notes : ALL DISTANCES ARE IN METRES


** ANY DISTANCE FOR OPERATIONAL CONVENIENCE
* OF SUM OF DIA OF ADJACENT VESSELS
OISD 144 -TABLE II
DIST BETWEEN LPG STORAGE VESSELS &
BOUNDARY LINE/GROUP OF BUILDINGS NOT
ASSOCIATED WITH THE PLANT

CAPACITY OF EACH VESSEL DISTANCE


(CU. MT OF WATER) (M)

10-20 15
21-40 20
41-350 30
351-450 40
451-750 60
751-3800 90
> 3800 120
OISD 144
PLANT LAYOUT
1.0 LOCATION AND SAFETY DISTANCES OF FACILITIES

1.1 LOCATION

ACCESS FOR MOBILE FIRE FIGHTING EQUIPMENTS


AVAILABILITY OF SPACE FOR FUTURE EXPANSION
LONGITUDINAL AXIS OF BULLETS NOT POINTED
TOWARDS VESSELS, VITAL PROCESS EQUIPMENTS
BUILDINGS AND FACILITIES
STORAGE VESSELS LAID OUT IN A SINGLE ROW
BULLETS AND SPHERES NOT GROUPED TOGETHER
STORAGE VESSELS NOT LOCATED ONE ABOVE THE
OTHER
OISD 144
PLANT LAYOUT
2.0 LPG BOTTLING FACILITIES
SEPARATE SHEDS FOR -
EMPTY CYLINDER STORAGE CUM FILLING SHED
FILLED CYLINDER STORAGE
ESCAPE ROUTES IDENTIFIED IN LPG SHEDS

3.0 PROTECTION OF FACILITIES


PROVISION OF ROADS AROUND FACILITIES FOR
ACCESSIBILITY OF FIRE FIGHTING OPERATION
EMERGENCY ESCAPE EXIT WITH PROPER GATE
LPG LORRY PARKING AREA(BULK/PACKED) WITH PROPER
HYDRANTCOVERAGE
OISD 144
PLANT LAYOUT
4.0 LPG STORAGE FACILITIES
PROVISION OF KERB WALL AROUND STORAGE VESSELS
PROVISION OF SPILLAGE SUMP WITH MIN DISTANCE NOT MORE
THAN DIA OF THE NEAREST VESSEL OR 15M WHICHEVER IS HIGHER
AREA UNDER SPHERE IS HAVING CONCRETE PAVEMENT WITH
PROPER SLOPE TO SHALLOW SUMP
GROUPING OF THE VESSEL NOT EXCEEDING 6 NO.S IN EACH GROUP
TOP SURFACE OF ALL VESSELS IN ONE GROUP ON THE SAME PLANE

5.0 LPG BULK HANDLING FACILITIES


MIN TURNING RADIUS FOR TT SHOULD BE 20M
MAX NO. OF TANK LORRY BAYS IN A GROUP NOT TO EXCEED 8 NOS.
SEPARATION BETWEEN TWO SETS OF BAYS MIN 50M
PROVISION FOR ISLAND FOR PROTECTION OF PIPE LINE
PIPELINE SYSTEM WITH THERMO SAFETY VALVES ROVs AND EFCVs
TO BE PROVIDED
OISD 144
STORAGE VESSEL DESIGN CRITERIA
STORAGE VESSELS
DESIGN CODES - ASME SEC. VIII or IS-2825 or PD- 5500
APPROVED BY PESO
MATERIAL-SA537 Gr.1 OR SA 516 Gr. 70
DESIGN TEMPERATURE- -27DEG TO +55DEG
DESIGN PRESSURE: 14.5 Kg/SQCM AT 55 DEG CELCIUS.
CORROSSION ALLOWANCE: 1.5MM
RADIOGRAPHY FULL
STRESS RELIEVING 100% IRRESEPCTIVE OF THICKNESS
WIND PRESSURE AS PER IS 875
EARTH QUAKE PRESSURE AS PER IS:1893
HYDRO TEST PRESSURE AS PER DESIGN CODE
OISD 144
FIRE PROTECTION FACILITIES
SPRINKLER SYSTEM -
Automatic fire protection (Fixed) medium velocity sprinkler system -
heat detection through quartzoid bulbs

In LPG storage area, detectors shall be provided encircling each


vessel, equi-spaced.

Minimum 2 nos. detectors shall be provided at the top of the vessel


and one near the liquid line ROV to take care of failure of flanges.

Upon actuation there shall be alarm in control panel, LPG pumps


and compressors would trip, ROVs on LPG supply and return lines
would trip and the deluge valves on fire water sprinkler system will
get actuated.
OISD 144
FIRE PROTECTION FACILITIES
DESIGN CRITERIA

ALL LPG STORAGE VESSELS, CYLINDER STORAGE/


FILLLING SHEDS, REPAIR SHEDS, LPG PHs, BULK LORRY
AND TANK WAGON GANTRIES SHALL BE COVERED BY
MEDIUM VELOCITY SPRAY SYSTEM

DETECTION OF FIRE FOR AUTOMATIC ACTUATION OF


MV SPRAY SYSTEM SHALL BE PROVIDED AT ALL CRITICAL
LOCATIONS LIKE LPG BULK STORAGE, TANK TRUCK/TANK
WAGON GANTRY,NEAR CAROUSAL, LPG PUMP/COMPRESSOR
HOUSE, EVACUATION, VALVE CHANGE AREAS
OISD 144
FIRE PROTECTION FACILITIES
FIRE WATER STORAGE

EFFECTIVE WATER STORAGE CAPACITY IS NOT LESS THAN 4 HRS


AGGREGATE WORKING CAPACITY OF MAIN FIRE WATER PUMP

MIN 2 STORAGE TANKS ARE PROVIDED IF STEEL TANKS ARE


PROVIDED

FIRE WATER PUMPS TO MEET INSTALLED RATE OF FLOW AND


HEAD SHALL BE CENTRIFUGAL TYPE DIESEL ENGINE DRIVEN

THERE SHALL BE A JOCKEY PUMP NOT LESS THAN 10M3/HR PER


100 HYDRANT POINTS WHICH MAINTAINS THE SYSTEM PRESSURE
AT 7KG/CM2 BY STARTING AND STOPPING AUTOMATCALLY BASED
ON THE SYSTEM PRESSURE
OISD 144
FIRE PROTECTION FACILITIES
AT LEAST ONE STANDBY FIRE WATER PUMP SHALL BE
PROVIDED UPTO 2 NOS OF MAIN PUMPS.
FOR MAIN PUMPS 3 AND MORE, MINIMUM TWO STANDBY
PUMPS OF THE SAME CAPACITY AS THE MAIN PUMPS SHALL BE
PROVIDED.
FIRE HYDRANT NETWORK
FIRE WATER RING MAIN LAID ABOVE GROUND
FIRE WATER RING MAIN LAID UNDERGROUND IF ANY ,
CONFORMS TO THE FOLLOWING:
- RING MAIN LAID 1 MTR BELOW GROUND
- IN ROAD CROSSING, RING MAIN LAID 1.2 MTR BELOW
GROUND
FIRE WATER RING MAIN KEPT PRESSURISED MIN. 7KG/CM2
FIRE WATER MONITOR PROVIDED WITH INDEPENDENT ISOLATION
VALVE
BETWEEN HYDRANT POINTS HOSE BOXES ARE KEPT WITH 2 NOS
HOSES AND A NOZZLE
OISD 144
FIRE PROTECTION FACILITIES

FIRST AID PORTABLE FIRE FIGHTING EQUIPMENTS

FIRE EXTINGUISHERS SHALL BE PROVIDED AT VARIOUS


LOCATIONS AS UNDER:

AREA PORTABLE FIRE EXTINGUISHER


LPG STORAGE VESSEL 2 NO.S 10KG DCP
LPG CYL SHED 2 NO.s 10KG DCP PER 200 SQM AREA
LPG PUMP HOUSES 2 NO.S 10KG DCP PER 50SQM
TT LOADING/UNLOADING 1 NO. 10KG DCP PER BAY
TW LOADING/UNLOADING 1 NO. 10KG DCP FOR EVERY 15/20
MTRS OF GANTRY
OTHER PUMP HOUSES 2 NO.S 10KG DCP
OISD 144
FIRE PROTECTION FACILITIES
FIRST AID PORTABLE FIRE FIGHTING EQUIPMENTS

AREA NO. OF FIRE EXTINGUISHER


MCC/DG ROOM/HT ROOM ATLEAST 2 NO.S 4.5KG
CO2 EXTINGUISHERS IN
EACH ROOM
100% SPARE CARTRIDGES
50% MIN SPARE DCP BAGS AS PER FIRE EXTINGHUISHER
CAPACITY
MOBILE FIRE FIGHTING EQUIPMENT
1 NO. 75 KG DCP IN FILLING SHED , LPG STORAGE VESSELS,
LPG PUMP HOUSE AREA, TANK TRUCK LOADING/UNLOADING
GANTRY AREA, TANK WAGON LOADING/UNLOADING GANTRY
AREA
OISD 144
FIRE PROTECTION FACILITIES
HOSES NOZZLES AND ACCESSORIES
50% SPARE SHALL BE STORED IN THE LPG PLANT
2 NO.S NOZZLES SPARE OF EACH KIND

FIRE ALARM SYSTEM


SUFFICIENT NO. OF MANUAL CALL POINTS
TWO ELECTRICALLY OPERATED FIRE SIREN WITH 1 KM AND 3 KM RADIUS
COVERING THE ENTIRE PLANT AND SORROUNDING PLACES
MANUALLY OPERATED SIREN AT STRATEGIC PLACES

COMMUNICATION SYSTEM
AVAILABILITY OF EFFECTIVE COMMUNICATION
COMMUNICATION SYSTEM LIKE TELEPHONE, PA/PAGING IN
HAZARDOUS AREA TO BE FLAMEPROOF / INTRINSICALLY SAFE
OISD 144
GAS MONITORING SYSTEM
The Gas Monitoring system - early warning for gas
concentration below the LEL (lower explosive limit).

The detectors for the gas monitoring system strategically


located at all facilities close to potential source of leakage.

The detection control equipment provided in the control


room for continuous monitoring even during power failure.

The control equipment to generate at least two alarms at


different levels of concentration of gas below LEL.
OISD 144
GAS MONITORING SYSTEM
Appropriate annunciation system shall be available to
ensure that all the alarms generated, both, audio and visual
are reported to the plant personnel, who are authorized to
take corrective action. Depending on the manning practice
of the plant, the alarms both, audio and visual can be
repeated at additional location to ensure corrective action is
taken.
The height of the detector should not be more than 0.3 M
from the mounting level.
The detectors should be located at least 0.3 mtrs. away
from the potential source of leakage
The gas monitoring system shall be kept in good operating
condition all the time.
OISD 144
GAS MONITORING SYSTEM
The minimum detectors are given below:
Storage vessels (above ground) 1 No. top and 1 No. near

bottom ROV.
LPG pump house 1 No. in pump house and 1 No. in
manifold.
Filled cylinder shed - 2 No.

Valve change shed 1 No.

Empty-cum-filling shed 2 Nos. near carousel, 1 No. near

evacuation unit tank, 1 No. weight correction unit.


TLD one at each manifold and at ends.

Tank wagon gantry 1 no. for every two bays or 30 m

whichever is less at bottom. Additionally, some detectors at


selected locations shall be provided at the top of platform.
OISD 144
EMERGENCY MANAGEMENT SYSTEM
GUIDELINES FOR EMERGENCY PREVENTION -
Sound engineering practice in the design, fabrication,

installation and maintenance of facilities.


Careful selection and correct use of equipment.

Observance of safety and security regulations.

Proper and constant training and guidance to all

personnel on product knowledge and maintenance


practices.
Good House-keeping.

Constant supervision and alertness


OISD 144
EMERGENCY MANAGEMENT SYSTEM
Instructions to both corporation and contractors
employee identifying the action to be taken by each
one in an emergency.
Availability of fire fighting organization plan including
plan for holidays and off shifts
Availability of approved onsite disaster management
plan(DMP)
Mock fire drills to be conducted in coordination local
administration, Police authorities, Fire Brigade, hospital
authorities, home guards, neighbouring industries
Offsite DMP will be formulated by District
Administration
OISD 144
EMERGENCY MANAGEMENT SYSTEM
SOURCE OF LPG LEAKAGES -
Through water drain valve while draining.

Leaking sample valve.

Breakage of glass on Sight Flow Indicator on the

pipeline.
Opening of pop-off valve, gland/packing etc.

Leakage through LPG compressor/pump.

Leakage due to bursting/ rupture of hose or through

swivel joints of body arms.


Leakage from the filling guns.

Escape of liquid/ vapour LPG during maintenance/

repairs.
OISD 144
SAFETY AUDIT
A structured and systematic safety audit of
any plant / facility to be done
Check lists should cover all the operational
areas, major equipments, operating/
maintenance procedures, safety practices,
fire prevention/ protection systems etc.
OISD 144
SAFETY AUDIT
Daily safety audit of LPG Installation by Safety
Officer reviewed by PM on daily basis.
Monthly safety audit by Plant Manager
Electrical audit by Internal & External Auditors
annually
Detailed safety audit by Multi disciplinary team
annually with members from region / HQ
Maintenance & Inspection audit annually
Surprise audit by Regional Safety Team
External safety audit by OISD scheduled as well
as surprise
OISD 144
SAFETY AUDIT
The safety audit will cover the following points
Safety Organisation

Security System

Fire prevention/ protection system

Preparedness to handle any emergency --Disaster

control plan and mock drills.


Skill level and training needs for HRD.

Operating manual/ instructions, display of Do's/

Don'ts etc.
OISD 144
OPERATING PRACTICES
1.0 STORAGE AND HANDLING OF BULK
UNLOADING OF BULK LPG TANK TRUCKS/ TANK
WAGONS UNLOADING OF BULK TTs & TWs TO BE
CARRIED OUT ONLY AT LOCATIONS APPROVED BY
PESO

SAFETY PRECAUTIONS
ELECTRICAL EQUIPMENTS/ LIGHTING FLAME PROOF

VAPOUR VENTLINE FOR INDUIVIDUAL BAY AT 1.5M

HEIGHT ABOVE THE EAVES OF THE SHED


FIRE EXTINGUISHERS SHALL BE POSITIONED AS AN

IMMEDIATE AID FOR FIRE FIGHTING - 1 NO 10 KG


DCP EXTINGUISHER PER BAY
OISD 144
OPERATING PRACTICES
CHECKS TO BE CARRIED OUT FOR EACH TT BEFORE
UNLOADING
VALID LICENSE FROM PESO, NAGPUR
2 NO.S 10KG DCP FIRE EXTINGUISHERS
QUICK CLOSING MANIFOLD VALVE WITH LEVER
INDICATING CLOSE/OPEN STATUS
MASTER CUT OFF SWITCH FOR SWITCHING OFF
ENGINE IS PROVIDED
AVAILABILITY OF TREM CARD, ROUTE MAP,
INSTRUCTION BOOKLET, RTO PERMIT
OISD 144
OPERATING PRACTICES
LPG CYLINDER STORAGE
STACKING
VERTICAL WITH VALVE IN UPRIGHT POSITION
HEIGHT SHOULD NOT EXCEED 2 STACKS
DIFFERENT TYPE AND CAPACITY TO BE STACKE SEPARATELY (SEPARATE
STACKING OF OMC CYLINDERS COMPANY WISE)

STACKING PATTERN
SMALL LOTS OF 4 ROWS AND 25 CYL LENGTH WITH MAX 2 STACKS
HIGH
MIN ACCESS PATH OF 1M ON BOTH SIDES OF STACK 2M ACCESS AFTER
5 LOTS
AFTER EACH LENGTH OF 25 CYLINDERS, PASSAGE OF 2M CYLINDER
STORAGE SPACE TO BE MARKED AND PAINTED ON FLOORING
DEMARCATED
MINIMUM DISTANCE OF 15M FROM CYLINDER LOADING
MIN DISTANCE OF 10M FROM FILLING POINT
OISD 144
MAINTENANCE & INSPECTION
INSPECTION/ TEST CERTIFICATE AT THE TIME OF ORIGINAL FABRICATION
SHOULD BE AVAILABLE AND SUBSEQUENT INSPECTION / HYDRAULIC TEST
CARRIED OUT AS PER SMPV RULES 1981 AND RECORDS MAINTAINED.
GUIDELINES OF OISD STANDARD-128 TO BE FOLLOWED FOR DETAILED
INSPECTION OF PRESSURE VESSELS.
ANNUAL INSPECTION AND TESTING OF SAFETY VALVES CARRIED OUT AT
PROPER SET PRESSURE AND RECORDS MAINTAINED.
ALL INSTRUMENTS, LEVEL INDICATORS, PRESSURE AND TEMPERATURE
GAUGES, ROVS ARE MAINTAINED IN WORKING CONDITION AND DAILY
SCHEDULED CHECKS, PERIODIC CALIBRATION AND PREVENTING
MAINTENANCE SCHEDULE
RELIEF VALVES - ISOLATION VALVES LOCKED IN OPEN CONDITION
EARTHING SHOULD HAVE CONTINUITY AND CONDITION OF EARTH PIT TO
BE CHECKED AND RESISTANCE MEASURED
OISD 144
MAINTENANCE & INSPECTION
INSTRUMENTATION
TEMP INDICATING DEVICES TO BE CHECKED, CALIBRATED ONCE
IN 6 MONTHS USING STD GAUGE
LEVEL GAUGE SHALLBE CHECKED DAILY FOR PROPER
FUNCTIONING
ZERO LEVEL CHECK AND CALIBRATION TO BE CARRIED OUT
MONTHLY
PRESSURE GAUGES TO BE CHECKED DAILY FOR CORRECT
FUNCTIONING AND CALIBRATED ONCE IN 6 MONTHS USING STD.
GAUGE
FLOW MEASURING DEVICES TO BE CHECKED DAILY AND
CALIBRATED ONCE IN A MONTH

INSPECTION OF LOADING/UNLOADING HOSES


UNLOADING ARMS ARE PREFERABLE TO HOSES
HOSES TO BE STORED PROPERLY WITH ENDS CLOSED BLINDS
NO HOSE HAVING KINKS OR CRACKS
SECURITY
ENTRANCE TO AUTHORISED PERSONNEL ONLY WITH
IDENTIFICATION WITH PHOTO ID CARDS
FRISKING OF ALL PERSONAL DONE BEFORE ENTRANCE
PHYSICALLY AS WELL AS HAND HELD METAL DETECTORS.
FURTHER THE PERSON HAS TO PASS THROUGH DOOR FRAME
METAL DETECTORS
VISITORS ALLOWED INSIDE ONLY AFTER AUTHORISATION BY
PLANT MANAGER / AUTHORISED OFFICER
MONITORING OF MOVEMENT OF VISITORS AND LOGGING THEM
OUT AFTER EXIT.
VISITORS FACE CAPTURED USING A WEB CAMERA
VEHICLES ENTERING ARE CHECKED FOR PRESENCE OF BOMBS,
ETC., PHYSICALLY AS WELL AS UNDER BODY MIRRORS
NO INFLAMMABLE OBJECT ALLOWED INSIDE
VISITORS VEHICLE CHECKED THOROUGHLY DICKIE, BONNET AND
UNDER BODY
ADEQUATE SECURITY PERSONNEL FOR ROUND THE CLOCK FOR
PETROLING AND SECURITY OF INSTALLATION
SECURITY TOWERS FOR MONITORING OUTSIDE AREAS
CO-ORDINATION WITH LOCAL POLICE AND INTELLIGENCE BUREAU
FOR SUSPICIOUS PERSONS AND MOVEMENT
TRAINING
SAFETY EDUCATION AND TRAINING RECEIVES GREAT ATTENTION
A VARIETY OF TRAINING COURSES ARE CONDUCTED INTENDED
TO DEVELOP THE SKILLS AND SAFETY CONSCIOUSNESS OF
EMPLOYEES.
TRAINING IS GIVEN TO IOCL EMPLOYEES, HANDLING & HOUSE
KEEPING CONTRACT LABOUR, TRUCK CREW AND SECURITY AS PER
THE SYLLABUS GIVEN IN OISD 154.
TRAINING ALSO GIVEN DURING MONTHLY FIRE DRILL AND HALF
YEARLY FIRE DRILL INVOLVING OUTSIDE AGENCIES.
FIRST AID TRAINING IS GIVEN TO EMPLOYEES WITH THE
ASSISTANCE OF OUTSIDE AGENCIES LIKE ST. JOHNS, ETC.,
TRAINING IS GIVEN AS PER MV RULE 9 TO TRUCK CREW WITH
THE HELP OF INHOUSE PERSONNEL AND OUTSIDE AGENCIES.
TRAINING DATA AND QUALITY REVIEWED BY HIGHER
MANAGEMENT
REFRESHER COURSES ARE GIVEN PERIODICALLY AS SPECIFIED
OISD 154 / INTERNAL COMPANY REGULATIONS.