Oil Gun
Deflectors
Burner Installation
S/heater II
modules
Gas Turbine
Diffuser
Supports
Burner
Throat
Burner Frontplate
General Layout
Auxiliary Fans
Comp. Skid
12.5’
8 7
Main
11’
6 5 Valve
10’ Rack
4 3 Side
9‘
2 1
Burner Set-up
Flame scanners
- 1 IR flame scanner (oil)
- 1 UV flame scanner (gas)
Limit switch
(signals if oil gun is
coupled)
Cooling/sealing lines
Sub Valve Rack
Steam purge line
Gas line
Oil line
Compressor skid
- 2 compressors (piston type)
CO2 room
- (1 bottle)
Power Installed - 45 kW
Voltage - 400V,
3PH
Pressure Switches Rack
Oil operation:
USAGE OF AUXILIARY AIR:
PSL - Start of 1 fan
-Stabilization air for gas burners PSLL - DB trip (2 of 3)
-Atomizing/stabilization air for oil burners
-Combustion/cooling air for igniters
Gas Operation:
-Cooling/sealing for flame scanners, sight glasses PSL - Start of 1 fan
-Sealing air for burner bushings PSLL - DB trip (2 of 3)
Instrument Air Compressor
Silence
Buzzer Start
Gas Oil Alarm
Reset Stop
Acknowledge
Lamp test
Emergency Selector Switch
Pushbutton BMS or DCS
Auxiliary Fan Panel / Burner Selector Switches
Stand-by
Failure Back-up Running
Off Auto Manual
( 8 selector switches)
Changeover of Auxiliary Fans
GAS OPERATION
Butterfly valve
Pressure Switch LL
(2 X 3) - DB Trip
(Setting = 6.5 bars)
Instrument Air
Compressors
Design
Design press
press= =10
10bars
bars
Effective
Effective pressure
press – 9.8
= 7.5= –7.59.8 barsbars
Air flow
Voltage = =400V,50Hz,3ph
2 kg/s
Power = 4 KW
AUXILIARY AIR & INSTRUMENT AIR SUPPLY
Pressure Switch HH
Pressure Switch (2 X 3) – DB Trip
LL (2 X 3) – DB Trip (Setting = 8 bars)
(Setting = 7 bars)
Gas Supply
Supply press
= 25 bars
Net Heating Value Pressure reducing station Main gas vent valve Control Valve
= 31.67 – 38.8 (Maintains = 9 bars) (Vented gas seal) (Press range = 0.25–7 bars)
MJ/Nm3
Max gas flow
= 4.3 Nm3/s
GAS FEED LINE
Gas feed line
Burner
Solenoid vent valves
(one on each side)
Igniter
Individual block
solenoid valves Ignition gas feed line
Pressure switch L
(Setting = 0.3 bar)
(stops steam purge)
Supply press = 2.5 – 5 bars
D/strm CV = 1 bar
Temp. = 180 deg C
Flow = 0.01 kg/s
IR UV
Igniter
Flame Scanners
PRESSURE SWITCHES RACK
XXQFA50
CP050 Aux. air press low (gas) 47 mbar 30 mbar Start of back up fan Alarm
XXQFA50
CP060/07
0/080 Aux. air press low-low (gas) 47 mbar 25 mbar? 2V3 Burner trip
XXEKG10
CP141/14
2/143 Gas supply press low-low 9 bar 7 bar 2V3 Burner trip
XXEKG10
CP145/14
6/147 Burner gas press high-high 0.25 – 7 bar 8 bar 2V3 Burner trip
XXEKD10
CP141/14
2/143 Oil supply press low-low 12 bar 9 bar 2V3 Burner trip
XXEKD10
CP145/14
6/147 Burner oil press high-high 0.13 – 4 bar 6 bar 2V3 Burner trip
XXQHA50
CP180 Purge steam press low 0.7 bar 0.3 bar Stop the oil gun purge Alarm
XXQFA10
CP170 Comp. 1 press low/high 8 bar 7.8? / 9.9 bar? Start/stop of comp. 1
XXQFA10
CP180 Comp sel. switch low/high 8 bar 7.5 / 8.8 bar Interval start of comp.
XXQFA10
CP160 Comp. 2 press low/high 8 bar 7.5? / 9.2 bar? Start/stop of comp. 2
XXQFA10 Standby compressor will
CP130/14 start ( certain time delay)
0/150 Instrument air press low-low 8 bar 6.5 bar 2V3 Burner trip
OM SCREEN
HRSG Protection
42 mbars
Indicates green if Remote is HBK10 - Warning
selected at BMS local panel. CP001 48 mbars
-DD close (11 & 12)
- GT Trip (21,22,23)
Indicates green if aux air press > min, no flame, fuel
valves close prior to GT Start-up. GT start permissive.
SF Prot OFF
XXLBA10CT001/002/003
HP STM T S/HTR OUTL > MAX3
T > 580 deg. C (2X3)
Time Delay=180 secs Auxiliary
Fans
HRSG Parameters with Duct Burners
Based on Design Data
Parameters Unfired condition Fired condition
• Start can only take place if at least 7 burners are selected and ready
for operation (not under maintenance).
• Successful operation only takes place if at least 7 burners were ignited
within 3 minutes. If not, burners will trip.
• Burners will start sequentially starting from burner 1 – 8. If one burner
will trip, it will continue to start other burners. If two, all burners will trip.
* Two auxiliary fans for oil are operated during purging. After steam
purge and steam valve is closed, one fan is switched off.
Manual Oil Gun Purge
• After a GT/HRSG trip, oil gun steam purge is interlocked
(solenoid valve closed). The oil guns for each burner
should be purged manually.
Thank You