Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 2
All Seasons

°CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
1. Introduction

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Course schedule
Day 1 Day 2
9:00-10:00 9:00-10:00

10:00-11:00 10:00-11:00

11:00-12:00 11:00-12:00

12:00-13:00 12:00-13:00

13:00-14:00 13:00-14:00

14:00-15:00 14:00-15:00

15:00-16:00 15:00-16:00

16:00-17:00

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 4


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Safety: Emergency cases


1. Always contact Daikin staff (or FQS secretaries phone:
extension 8444)

2. The emergency phone n° is 8000 (guardhouse) or the quick-


dial number on the Avaya telephones.

3. All Daikin Europe instructors are qualified for first aid help.

4. In case of fire alarm, follow the evacuation procedure

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 5


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Safety: Evacuation procedure


1. Use the staircases on the exit or emergency exit side of the
building
2. Do not use the elevator
3. Follow the (emergency) exit signs
4. Move towards the meeting point in front of the building

5. Check for missing colleagues and report to the Daikin instructor

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 6


TOP SECRET
SECRET
INTERNAL USE ONLY

Main <- Staircases -> Emergency PUBLIC

Meeting point direction

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 7


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Safety: Trainee qualification Certified


electrician

1. We assume that all trainees are qualified to work with


electricity.

2. Should this not be the case, then you have to inform the
instructor. He/she will only allow you to watch the exercises.

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 8


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Safety: Electrical work


1. Electrical connections can only be made on installations that
are not switched on.

2. Only the instructor is allowed to switch on the power after


verification of the electrical connections made by the trainees.

3. Do not execute given exercises if you doubt the safety of your


handling.

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 9


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Electrical safety in Practice 1 and 2

Power supply through building-independent power


modules with:

Power indication lamps per phase


Emergency stop button

8 x 230 V single phase sockets

2 x 400 V 3-phase sockets


All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 10
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Safety: Use of the emergency stop


1. Each emergency stop switches off ALL
power modules in the Practice room.

2. Re-armament is only possible by the


instructor on the main board.

3. Deliberate use will not be tolerated.

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 11


TOP SECRET
Basic direction of the new Altherma LT manuals SECRET
INTERNAL USE ONLY
PUBLIC

Architects, Installer Installer


Affiliate Consultant Installer Commiss. End- Servic
Sales engineering hydraulic refrigeran
s s electrics engineer user e
bureau s t

PRE-SALES
PLANNING -
ENGINEERING
INSTALLATION
COMMISSIONING
USE
MAINTENANCE
SERVICE

Installation manual Operation manual


All necessary instructions for a licensed installer All basic instructions for the end-user
to properly install the unit to operate the system
when he/she is on site through the controller

Installer reference guide User reference guide


This guide is for the installer’s reference, This guide is for the user’s reference,
containing all installation instructions containing more information about
+ additional information: advanced usage and configuration
technical data, application examples, preparation work,
Use of the controller, maintenance, …

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 12


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 13
All Seasons

°CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
2. System build up

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

2. System build-up: content


1. Indoor unit

2. Outdoor unit

3. Combinations

4. Accessories/options

5. Basic system drawing

6. Typical application

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 15


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

2.1. Indoor unit: wall hung


 New CA range
• Compatible only with latest models:
• Outdoor GBS: *CA
• Outdoor GQI: *CA / BA

Line up: Line up:


H/O Reversible
• EHBH04CA3V • EHBX04CA3V
• EHBH08CA3V • EHBX08CA3V
• EHBH08C9W • EHBX08C9W

• EHBH16CA3V • EHBX16CA3V
• EHBH16CA9W • EHBX16CA9W

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 16


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

2.1. Indoor unit: integrated (tank included)


 New CA range
• Compatible only with latest models:
• Outdoor GBS: *CA
• Outdoor GQI: *CA / BA

Line up: Line up:


H/O Reversible
• EHVH04S18CA3V • EHVX04S18CA3V
• EHVH08S18CA3V • EHVX08S18CA3V
• EHVH08S26CA9W • EHVX08S26CA9W

• EHVH16S18CA3V • EHVX16S18CA3V
• EHVH16S26CA9W • EHVX16S26CA9W

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 17


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

2.2. Outdoor unit: GBS (small)


 New CA range
 New 4kW capacity class
• No 7kW capacity class
• No more ERHQ

Line up:
• ERLQ004CAV3
004 = 4kW
006 = 6kW
• ERLQ006CAV3
008 = 8kW • ERLQ008CAV3

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 18


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

2.2. Outdoor unit: GQI (big)


• Existing BA & CA range
• ERHQ & ERLQ

Line up:
• ERHQ011BAV3 • ERLQ011CAV3
• ERHQ014BAV3 • ERLQ014CAV3
• ERHQ016BAV3 • ERLQ016CAV3

• ERHQ011BAW1 • ERLQ011CAW1
• ERHQ014BAW1 • ERLQ014CAW1
• ERHQ016BAW1 • ERLQ016CAW1

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 19


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

2.2. Outdoor unit: GQI (big)

E R L/H Q 0-- BA V3
Voltage supply
Single phase 230V

Minor change
Capacity class heating

Refrigerant R410
L: Ambient zone 2 (cold climate)
H: Ambient zone 3 (mild climate)
Outdoor unit

European model

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 20


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3. Combination – wall hung indoor unit

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 21


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3. Combination – integrated indoor unit

All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 22


TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


1. EKDP008CA drainpan (GBS OU)

2. EKDPH008CA drainpan heater (GBS OU)

3. EKFT008CA U-beams for mounting (GBS only)

4. EKHBPHTH16A (for ERH)

5. EKDK04* (for ERHQ)

6. EK016SNC snow hood (for ERLQ GQI)

7. KRP58M51 demand pcb (for ERLQ)


All Seasons °CLIMATE COMFORT V. Eylenbosch 30 March 2018 23
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


EKDP008CA DRAINPAN (only for GBS OU)

• New GBS CA has free hanging coil.


• If required, you can mount a drain pan for outdoor unit
• Collect water from defrost cycle and drain via central hole to
remote
• Consists of drainpan and U-beams

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 24
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


EKDPH008CA drainpan heater (GBS OU)
• Drain pan heater for drain pan EKDP008CA
• Recommended when a drain pan is used in cold regions
• 90W & controlled by OU (faston terminal on pcb)

EKFT008CA U-beams (GBS only)


• U-beams for mounting outdoor unit without drainpan
• Height 25cm

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 25
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


EKHBPHTH16A bottom plate heater (for ERHQ)

• Bottom plate heater for ERHQ* units


• Controlled by indoor unit (settings)
• EKRP1HBAA is also required (for control signal)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 26
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


EKDK04* drain plug (for ERHQ only, ERLQ has standard BPH for GBS)

• Drain plug/stop kit


• To guide the condensate through one hole in the bottom plate
• Not allowed to use if bottom plate heater installed

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 27
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


EK016SNC snow hood (for ERLQ GQI)

• Snow cover 60

• For low ambient/heavy snowfall 10

70

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 28
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: outdoor unit


KRP58M51 demand pcb (for ERLQ GQI)

• Limit rated power consumption


• (100/80/70/60/40%)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 29
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


1. EKRSCA1 ambient sensor for outside (IU)
2. EKRSCA1 ambient sensor for outside (IU)
3. KRCS01-1 ambient sensor for inside (IU)
4. EKPCCAB1 PC cable (IU)
5. EKRUCAL1&2 user interface (IU)
6. EKHBDPCA2 indoor drainpan (Wall hung reversible IU)
7. EKRTWA wired remocon (IU)
8. EKRTR1 wireless remocon (IU)
9. EKRTETS external sensor (IU – with EKRTR1)
10. EKRP1HBAA option pcb (IU)
11. EKRP1AHTA optional demand pcb (IU & GBS only)
12. EKSOLHWAV1 (solar kit only for wall hung units)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 30
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKRSCA1 ambient sensor for outside (connect to IU)
• Temperature measurement remotely from outdoor unit
(ambient temp)
• Connected to indoor unit (but installed outdoors)
Ideal place to put the ambient
sensor: on the north side,
protected from rain, sun and
wind.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 31
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKRSCA1 ambient sensor for outside (connect to IU)
• Temperature measurement remotely from outdoor unit
(ambient temp)
• Connected to indoor unit (but installed outdoors)

KRCS01-1 ambient sensor for inside (connect to IU)


• Temperature measurement remotely from user interface (room
temp)
• Connected to indoor unit
• Can only be used in case unit control method = room
thermostat
Only one of two sensor can be used!
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 32
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.6. [A.2.2] System Layout Options


A.2.2 Options
1 DHW operation
3 DHW tank heater
4 Contact type main
 Set [A.2.2.B]: External sensor 5 Contact type add
6 Digital I/O pcb
 Not installed (sensor of user interface is used to measure 7 Demand pcb
8 External kWh meter 1
indoor temp, sensor of outdoor unit for ambient temp) 9 External kWh meter 2
A External DHW pump
 (1) Outdoor sensor B External sensor

 (2) Room sensor


• Offset can be set (refer to [A.3.2.3] UI sensor, [A.3.2.3] ext.
Sensor for room temp, [A.6.5] Ext. Sensor for ambient temp.

!!! External sensor is still used for all operation logic (except
for protection functions)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 33
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit

Preliminary
EKPCCAB1 PC cable (IU)

• PC cable: connection between indoor unit and a PC.

• Possiblity to:
• Up & download settings (also schedule timers)
• Upload language files

• Software will be made available on extranet:


www.daikineurope.com – manuals – software
(language files already available)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 34
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKRUCAL1&2 user interface (connected to IU)
• EKRUCAL1 is standard delivered with the unit:
• Additional user interface can be connected:
• To have both:
• Control close to the indoor unit
• Room thermostat functionality in the principal space to be heated
• To have an interface containing other languages:
• EKRUCAL1 (delivered with unit)
contains the 6 common languages: English, German, French, Dutch, Italian,
Spanish.
• EKRUCAL2 (to be ordered separately)
contains other languages: English, Swedish, Norwegian, Czech, Turkish,
Portuguese.
• Second user interface can be used to
• send version 2 languages to the one standard delivered with the unit
• CLIMATE
All Seasons °
sendCOMFORT
prepared settings (all, also including schedule timers etc)
V. Eylenbosch 30 March 2018 35
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKHBDPCA2 indoor drainpan (Wall hung reversible IU)
• To collect drainwater during cooling operation

EKRTWA wired remocon (IU)


• Wired room thermostat (same as previous series)

EKRTR1 wireless remocon (IU)


• Wireless room thermostat (same as previous series)

EKRTETS external sensor (IU – with EKRTR1)


• External sensor for room thermostat
• For UFH or other room location
• Similar to KRCS1-01 but this one can only be used on EKRUCAL
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 36
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKRP1HBAA Digital I/O pcb
(connect to IU)
• Alarm output
• Space heating/cooling On/OFF
output (for HPC)
• Changeover to external heat source
(if bivalent system)
• If ERHQ OU: control signal for
bottom plate heater kit
EKBPHTH16A (for GQI)
• Can be integral part of solar kit
EKSOLHW (only for wall hung units).
In this case, pcb is delivered with
solar kit.
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 37
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKRP1AHTA optional demand pcb (IU & GBS only)

• Power consumption limitation with 4 digital inputs.


• Only for GBS (contains already simple demand setting)
• Not for GQI. For GQI, use KRP58.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 38
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: indoor unit


EKSOLHWAV1
(!solar kit only for wall hung units!)

• Option kit for solar (incl. EKRP1HBAA)

• For EKHWS/EKHWE units

• No solar available for integrated


model!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 39
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: tank
EKHWS tank

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 40
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. Accessories/options: tank
EKHWE tank

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 41
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5. Basic system drawings (wall hung)

Hydro Box

Outdoor unit Back up heater


Refrigerant

Plate heat exchanger

Space heating

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 42
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC
5. Basic system drawings (wall hung)
Altherma system with hot water tank (in hot water mode)

Outdoor unit Back up heater (off)


Refrigerant

Plate heat exchanger


Hot water tank

Max
80°C
3 way valve Space heating
Booster heater Delivered with
EKHWS-B / EKHWE-A

Max
55°C

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 43
TOP SECRET
SECRET
INTERNAL USE ONLY

5. Basic system drawings (wall hung) PUBLIC

Altherma system with hot water tank & cooling (cooling mode)

Outdoor unit
Back up heater (off)
Refrigerant
Plate heat exchanger

Hot water tank

Max
80°C FCU for cooling

Booster heater
2 way valve
3 way valve

Space heating

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 44
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC
5. Basic system drawings (wall hung)
Altherma system with hot water tank & solar + cooling (in cooling mode)

Outdoor unit
Back up heater (off)
Refrigerant
Plate heat exchanger

Hot water tank


Solar pump
Max station (field)
80°C FCU for cooling

Solar kit
2 way valve

3 way
valve
Space heating

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 45
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5. Basic system drawings (integrated)


Integrated tank (no BSH) and connections on top

Max
60°C
DHW

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 46
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: UFH – UI as RT

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 47
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: UFH –External RT

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 48
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: UFH - HPC

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 49
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: Multiple room: 1 zone

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 50
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: Multiple room: 1 zone with ext. RT

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 51
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: Multiple room: 1 zone combination UFH


+ HPC

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 52
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Typical application: Multiple room: 2 water zones

Mixing valve
station
necessary!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 53
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 54
All Seasons

°
CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
3. Equipment selection

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3. Equipment selection
1. Specs: LT GQI 1ph ERHQ*BAV3 9. ESP GBS & GQI

2. Specs: LT GQI 3ph ERHQ*BAW1 10. Field-wiring: Integrated & wall hung

3. Specs: LT GQI 1ph ERLQ*CAV3 11. Field-wiring: preferential power supply

4. Specs: LT GQI 3ph ERLQ*CAW1 12. Wiring the BUH

5. Specs: LT GBS 13. Wiring the user interface

6. Specs: indoor unit 14. Wiring diagram

7. Operation range- GBS 15. Field piping

8. Operation range- GQI


All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 56
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.1 Specs: LT GQI 1ph ERHQ*BAV3 GQI

No ducting
allowed!!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 57
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.1 Specs: LT GQI 1ph ERHQ*BAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 58
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.1 Specs: LT GQI 1ph ERHQ*BAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 59
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.1 Specs: LT GQI 1ph ERHQ*BAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 60
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.2 Specs: LT GQI 3ph ERHQ*BAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 61
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.2 Specs: LT GQI 3ph ERHQ*BAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 62
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.2 Specs: LT GQI 3ph ERHQ*BAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 63
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.2 Specs: LT GQI 3ph ERHQ*BAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 64
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.3. Specs: LT GQI 1ph ERLQ*CAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 65
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.3. Specs: LT GQI 1ph ERLQ*CAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 66
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.3. Specs: LT GQI 1ph ERLQ*CAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 67
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.3. Specs: LT GQI 1ph ERLQ*CAV3 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 68
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.4. Specs: LT GQI 3ph ERLQ*CAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 69
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.4. Specs: LT GQI 3ph ERLQ*CAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 70
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.4. Specs: LT GQI 3ph ERLQ*CAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 71
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.4. Specs: LT GQI 3ph ERLQ*CAW1 GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 72
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.5. Specs: LT GBS GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 73
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.5. Specs: LT GBS GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 74
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.5. Specs: LT GBS GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 75
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.5. Specs: LT GBS GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 76
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.6. Specs: indoor unit


• Min flow rate (flowsensor): 5l/min (GBS) 11l/min (GQI)

• BUH 3V: 12l/min

• BUH 9W: 15l/min

• DHW connections: 1” female

• Space heating connections: 1,1/4” female

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 77
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.7. Operation range- GBS - LWT GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 78
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.7. Operation range- GBS - DHW GBS

4kW 6&8 kW

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 79
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.8. Operation range- GQI - LWT GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 80
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.8. Operation range- GQI - DHW GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 81
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.9. ESP GBS & GQI: wall hung indoor


GBS GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 82
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.9. ESP GBS & GQI: integrated indoor unit


GBS GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 83
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.10. Field-wiring: Integrated


Wires through top of the unit:
• A: Low voltage
• B: High voltage power supply
• C: High voltage control signals

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 84
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.10. Field-wiring: Integrated


Wiring through unit

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 85
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.10. Field-wiring: wall hung


Wires through bottom of the unit:
• A: Low voltage
• B: High voltage power supply
• C: High voltage control signals
contact

Left
Right

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 86
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.10. Field-wiring: wall hung


Additional wiring needed in case of DHW optional tank
installed

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 87
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.10. Field-wiring: wall hung & integrated


Wiring enters at bottom of switchbox:

Normal power supply (3x2,5mm²) –


interconnection cable

Field wiring
Fix with
tie wraps

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 88
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.11. Field-wiring: preferential power supply


• A: Interconnection cable
(=main power supply) Preferential power supply

• B: Preferential kWh rate power


supply
• IF preferential power supply is
interrupted

• C: Preferential power supply


contact (0,75mm² till 1,25mm²)
Fix with
tie wraps

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 89
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.11. Field-wiring: preferential power supply

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 90
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System layout: Standard – Preferential kWh rate


A.2.1 Standard
1 Unit type
2 Compressor type
3 Indoor software type
Set [A.2.1.6]: Preferential kWh rate (S1S on X5M) 4 Backup heater steps
5 Backup heater type
 (0) No/ (1)Active Open / (2)Active closed 6 Preferential kWh rate
7 Unit control method
8 Number of water zones
9 Pump operation mode
A Power saving possible
possible
B User interface location
Active open Active closed
• Forced off when contacts opens • Forced off when contacts closes
• Operation allowed when contact is • Operation allowed when contact is
closed open

• Power supply wiring has to be connected accordingly

• Always make sure [A.6.1]: Auto restart is enabled


(default=enabled)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 91
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


The setup of the BUH consists of following actions:

1) Separate power supply + fuse

2) Correct wiring of BUH power supply entering indoor switchbox

3) Correct setting of faston terminals in indoor switchbox

4) Measure resistance on contactors indoor switchbox

5) Settings quickwizard

6) Customize settings (priority etc..) on remocon

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 92
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH dedicated power supply and separate fuse
• *3V units have prewired BUH
• Unified BUH models *9W => BUH has to be wired according
to power supply

• Use a dedicated power supply with safeties installed!


Fuse in switchbox only protects the inner wiring, not the field wiring!
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 93
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH wiring (3V)
• Connect power supply to the fuse
• Prewired in factory

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 94
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH wiring (9W)
• Power supply has to be connected correctly to the fuse
2 extra bridges

Power wiring fastons


1 extra bridge

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 95
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH wiring (9W)
• Power supply has to be connected correctly to the fuse

• On first start up the correct power supply for the BUH has to
be set (in the Quick Wizard)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 96
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH wiring (9W)
• Connections have to be set correctly in switch box to set
the right power supply/capacity
• Wiring is color coded (ref, also wiring diagram & manual)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 97
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH wiring (9W): miswiring possible => measure resistance
1. Different backup heater types: Different resistances
2. ALWAYS measure the resistance on the contactor clamps
K1M, K2M, and K5M.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 98
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


BUH wiring (9W)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 99
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater A.2.1 Standard


1 Unit type
2 Compressor type
3 Indoor software type
4 Backup heater steps
Set [A.2.1.5]: BUH type (must be correctly wired by installer) 5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
 (1) 1PN,(1/1+2): 6 kW 1~ 230 V (*9W-6V3) 9 Pump operation mode
A Power saving possible
(Step 2 can be disabled) possible
B User interface location

 (3) 3P,(1/1+2): 6 kW 3~ 230 V (*9W-6T1)

 (4) 3PN,(1/2): 6 kW 3N~ 400 V (*9W-6WN))

 (5) 3PN,(1/1+2): 9 kW 3N~ 400 V (*9W-9WN)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 100
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater A.2.1 Standard


1 Unit type
2 Compressor type
3 Indoor software type
4 Backup heater steps
Set [A.2.1.5]: BUH type (must be correctly wired by installer) 5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
 (1) 1PN,(1/1+2): 6 kW 1~ 230 V (*9W-6V3) 9 Pump operation mode
A Power saving possible
(Step 2 can be disabled) possible
B User interface location

 (3) 3P,(1/1+2): 6 kW 3~ 230 V (*9W-6T1)

 (4) 3PN,(1/2): 6 kW 3N~ 400 V (*9W-6WN))

 (5) 3PN,(1/1+2): 9 kW 3N~ 400 V (*9W-9WN)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 101
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater A.2.1 Standard


1 Unit type
2 Compressor type
3 Indoor software type
4 Backup heater steps
Set [A.2.1.4]: BUH steps 5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
 1 step 9 Pump operation mode
A Power saving possible

 2 steps possible
B User interface location

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 102
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater A Installer settings


1 Language
Set [A.2.3.2/3]: BUH step 1/2 2 System layout
3 Space operation

• Default: 4 Domestic hot water


5 Heat source
6 System operation
BUH [A.2.3.2]: [A.2.3.3] 7 Commissioning
model BUH 1 BUH2 Total 8 Overview settings
3V 3 0
9W 3 6 9 A.2 System layout
1 Standard
2 Options
3 Capacities
• In case of 9W, adjust manually to: 4 Confirm layout

A.2.3 Capacities
1 Booster heater
[A.2.3.2]: [A.2.3.3] 2 Backup heater (step 1)
BUH type [A.2.1.5] BUH 1 BUH2 Total 3 Backup heater (step 2)
1P,(1/1+2): 3 kW 1~ 230 V (*9W) 1 3 0 3 6 Bottom plate heater
3P,(1/1+2): 6 kW 3~ 230 V (*9W) 3 3 3 6
3PN,(1/2): 6 kW 3N~ 400 V (*9W) 4 3 3 6
3PN,(1/1+2): 9 kW 3N~ 400 V (*9W) 5 3 6 9

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 103
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater A.2.1 Standard


1 Unit type
2 Compressor type
3 Indoor software type
4 Backup heater steps
Set [A.5.1]: BUH operation mode 5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
 enabled 9 Pump operation mode
A Power saving possible

 disabled possible
B User interface location

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 104
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.12. Wiring the Backup Heater


Attention: BUH

• Thermal fuse is in line with heater elements!

• No error will appear if thermal fuse is broken (breaks at 92°C)

• Check by verifying resistance over the contactors

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 105
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.13. Wiring the user interface


User interface
• Optional user interface is connected
in parallel
• 2x 0,75 mm² till 1,25mm²
• Max length 500m

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 106
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.14. Wiring the power supply GBS

Power supply & interconnection cable

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 107
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.14. Wiring the power supply GQI

Power supply & interconnection cable

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 108
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.14. Wiring the power supply GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 109
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.14. Wiring the power supply GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 110
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 111
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: external RT/HPC


• Separate contacts for main/additional zone room thermostats (or HPC)
on X2M: 1A, 2A
• Min: 0,75mm²

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 112
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: 2nd user interface & thermistor


• Additional user interface

• Optional thermistors

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 113
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: circulation pump & 2way valve

For cooling or for main zone (if multiple zones)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 114
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: energy metering


• GBS: energy consumption is calculated according to power input on
outdoor and capacities of BUH. Optional, external meters can be set
up.

• GQI external energy meters have to be set up

Daikin recommends ABB ODIN

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 115
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: energy metering


Make sure all power input is covered!

Single phase Three phase

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 116
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: energy metering


• If 230 & 400V grid is combined => 2meters needed
• Preferential power supply => generally two meters used

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 117
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: bivalent operation (KRP1HB)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 118
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: bivalent operation (KRP1HB)


• According to changeover temperature and hysteresis, external
heat source can be allowed
• Optional outdoor ambient sensor can be used to ensure correct
changeover (eg. install in the shade at north side)

• Alternative: (only if ext RT control & 1 water temp zone)


Signal is given to boiler or hp.
2 relays: 1 for time delay

! Both systems
cannot operate
simultaneously!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 119
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: power limitation (KRP1AHTA)

only for GBS! (connect to indoor)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 120
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.15. Wiring diagram: DHW tank connection


only for wall hung

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 121
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping

 ERLQ*CA – GBS models: see databook or IM

 ERHQ*BA(V3/W1) & ERLQ*CA(V3/W1) GQI models:

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 122
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GQI GQI

1 Drill 8 Pipe outlet plate


2 Centre area around knockout hole 9 Screw front plate
3 Knockout hole 10 Pipe outlet plate screw
4 Slit A Forward
5 Connecting pipe B Backward
6 Bottom frame C Sideways
7 Front plate D Downward

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 123
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GQI – ERHQ* GQI

Requirement V3 w1
Maximum allowable refrigerant piping length between
75m (95) 75m (95)
outdoor and indoor unit
Minimum allowable refrigerant piping length between
5m (3) 5m (3)
outdoor and indoor unit
Recharge!
Maximum allowable height difference between outdoor
30m 30m
and indoor unit
Chargeless piping length 30m 10m
Maximum allowable distance between the 3-way valve
and the indoor unit (only for installations with domestic 3m 3m
hot water tank).
Maximum allowable distance between the domestic hot
water tank and the indoor unit (only for installations with
domestic hot water tank). The thermistor cable supplied 10m 10m
with the domestic hot water tank is 12m in length.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 124
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GQI - ERLQ* GQI

Requirement V3 w1
Maximum allowable refrigerant piping length between
50m (70) 50m (70)
outdoor and indoor unit
Minimum allowable refrigerant piping length between
3m 3m
outdoor and indoor unit
Maximum allowable height difference between outdoor
30m 30m
and indoor unit
Chargeless piping length 10m 10m
Maximum allowable distance between the 3-way valve
and the indoor unit (only for installations with domestic 3m 3m
hot water tank).
Maximum allowable distance between the domestic hot
water tank and the indoor unit (only for installations with
domestic hot water tank). The thermistor cable supplied 10m 10m
with the domestic hot water tank is 12m in length.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 125
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GBS – ERLQ* GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 126
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GQI refrigerant charge ERHQ*BA


GQI
Additional calculation

V3

W1

Complete refrigerant

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 127
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GQI refrigerant charge ERLQ*CA


GQI
Additional calculation
• Less then 10m => NOT needed
• More then 10m
• Additional charge [kg] = (total length (m) of liquid piping - 10m) x 0.054
Rounded in units of 0.1kg

Complete recharging

• Total refrigerant charge [kg]


= 3.4kg + (total length (m) of liquid piping - 10m) x 0.054

REMARK : Factory charge is 3.4kg

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 128
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GQI: necessity of oiltrap


GQI
To avoid that oil inside the rising piping
flows back into the compressor when
stopped and causing liquid compression
phenomenon.
Install trap at each difference in
height of 10 m is required.

•Trap installation spacing.


A Outdoor unit
B Indoor unit
C Gas piping
D Liquid piping
E Oil trap
H Install trap at each difference in height of 10 m
Oil trap is not necessary when the outdoor
unit is installed in a higher position than the
indoor unit.
Cautions for necessity of a trap
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 129
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping GBS refrigerant charge


GBS
Limitation

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 130
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

3.16. Field piping


GBS
Additional calculation
Less then 10m => NOT needed

More then 10m


Additional charge [kg] = 20g/m
Add amount on the fluorinated greenhouse gases label

Complete recharging
Check the fluorinated greenhouse gas label.
If not available, check the nameplate and make calculation

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 131
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 132
All Seasons

°
CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
4. System operation

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4. System operation: content


1. Refrigerant concept: GQI ERHQ*BA (1ph & 3ph)

2. Refrigerant concept: GQI ERLQ*CA (1ph & 3ph)

3. Refrigerant concept: GBS ERLQ*CAV3

4. Hydraulic concept: Wall hung & Integrated

5. Main components: integrated GBS & GQI

6. Main components: wall hung & integrated

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 134
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.1. Refrigerant concept: GQI ERHQ*BAV3 GQI

1 phase

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 135
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.1. Refrigerant concept: GQI ERHQ*BAW1 GQI

3 phase

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 136
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3 GQI

1 phase

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 137
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3


GQI
ERLQ*BAV3 ERLQ*CAV3

SUBCOOL PASS

distributor

sealing

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 138
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3


GQI
• Hot gas pass in bottom plate
• Limited operation (during defrost)

HOTGAS BYPASS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 139
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3


GQI
More height difference
BOTTOM PLATE HEATER

• 100W reduced to 35 W
• Standard operation only during
defrost (3 min.) and max. 3 times per
5 drain holes hour

Reduction of electrical consumption

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 140
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3


GQI

60

10

70

COLD CLIMATE IMPROVEMENTS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 141
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3


GQI

LIQUID INJECTION

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 142
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3 GQI


Ta Ta
35 35

Previous single New ERLQ unit


( single and 3phase) Max. leaving water
phase ERLQ unit
temp. is independent of
the ambient temp.
0 0
Compressor
operation till -25°C
-20 -20

-25 -25

25 40 55
25 40 55 Tlw Tlw

Optimised operation range for SPH (due to liquid injection)


Avoid too high discharge
temp by low liquid injection
Pressure (Bar)

X X
Liquid injection by
EEV
(precise control)

Enthalpy (KJ/KG)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 143
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.2. Refrigerant concept: GQI ERLQ*CAV3 GQI

Optimised operation range for DHW (due to liquid injection + softw)

Outdoor temp. (°CDB) Outdoor temp. (°CDB)


LT BA LT CA

35 35
25

-10
-20 -20
DHW tank DHW tank
-25
temp. (°C) temp. (°C)

25 50 80 25 50 x 80

 Booster heater operation only*

 Operation possible but no guarantee of capacity. X = 55 °C


combined with Hydrobox from BB-series
If outdoor T < -25°C, the heat pump will stop. onwards and EKHTS based tank

* No booster heater in EKHTS…AC tank

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 144
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.3. Refrigerant concept: GBS ERLQ*CAV3 GBS

New high pressure


sensor and high
pressure switch

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 145
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.3. Refrigerant concept: GBS ERLQ*CAV3


GBS

condenser

New high pressure


expansion valve compressor
sensor and high
pressure switch
evaporator

• Pressure sensor: optimised subcool


• Pressure sensor and switch are same as
GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 146
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.3. Refrigerant concept: GBS ERLQ*CAV3 GBS

New compressor

• New compressors for entire range


• Specific compressor for 004 class

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 147
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.3. Refrigerant concept: GBS ERLQ*CAV3


GBS

Free hanging coil Free hanging coil

No more bottom plate heater required:


• Reduction of power input of 60W when Ta < 4°C
• Lower power input increasing the SCOP
• Unified model for the whole of Europe (no more GBS ERHQ required)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 148
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.4. Hydraulic concept: Wall hung

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 149
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.4. Hydraulic concept: Integrated

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 150
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.4. Hydraulic concept: waterflow

• Inverter pump will modulate according to delta T over the heat


emitters

• Minimum flow in heat pump operation:


• GBS: 5l/min
• GQI: 11l/min

• Minimum flow for BUH operation:


• 3V: 12l/min
• 9W:15l/min

• New flowsensor: range:


• 04kW unit: 2-40l/min
• 08 & 16kW unit: 5-100l/min (same flowsensor for 08 & 16)
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 151
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.5. Main components: GQI ERLQ*CA*


GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 152
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.5. Main components: GQI ERLQ*CA*


GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 153
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.5. Main components: GBS ERLQ*CA*


GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 154
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.6. Main components: wall hung EHB*CAV

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 155
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.6. Main components: wall hung EHB*CAV


GBS GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 156
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.6. Main components: integrated EHV*CAV

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 157
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.6. Main components: integrated EHV*CAV

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 158
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

4.6. Main components: switchbox indoor unit

Options!!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 159
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 160
All Seasons

°
CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
5. Fieldsettings

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5. Fieldsettings: overview
1. User interface EKRUCAL

2. The Quick Wizard

3. Switching homescreens

4. Symbols

5. Tips & tricks

6. Enduser settings

7. Installer settings

8. Additional info
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 162
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.1. User interface EKRUCAL

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 163
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.1. User interface EKRUCAL

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 164
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.2. The Quick Wizard

Only on first start up – Quick Wizard is shown


• Installer has to set:
• Language
• Date

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 165
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.2. The Quick Wizard

• Installer has to set:


• Time
• System layout

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 166
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.2. The Quick Wizard A Installer settings


1 Language
System layout 2 System layout
A.2 System layout 3 Space operation
A.2.1 Standard
1 Standard 4 Domestic hot water
1 Unit type
2 Options 5 Heat source
2 Compressor type
3 Capacities 6 System operation
3 Indoor software type
4 Confirm layout 7 Commissioning
4 Backup heater steps
8 Overview settings
5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
9 Pump operation mode
A Power saving possible possible
B User interface location

A.2.2 Options A.2.2.6 Digital I/O pcb


1 DHW operation 1 Ext. backup heat source
3 DHW tank heater 2 Solar kit
4 Contact type main 3 Alarm output type
5 Contact type add 4 Bottom plate heater
6 Digital I/O pcb
7 Demand pcb
8 External kWh meter 1
9 External kWh meter 2
A External DHW pump
B External sensor

A.2.3 Capacities
1 Booster heater
2 Backup heater (step 1)
3 Backup heater (step 2)
6 Bottom plate heater
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 167
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.2. The Quick Wizard


System layout
• After setting system layout => installer has to confirm layout
• After confirmation the system will automatically restart.

• The confirm layout line will never be visible anymore after that
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 168
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Breadcrumbs???
Just like Little Thumbling did, you can find breadcrumbs in our
controller in the left upper corner.
They make it easy for you to find your way.
Example: 7.4.1.1 leads you to the comfort temperature for heating

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 169
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System layout: Standard A Installer settings


A.2 System layout 1 Language
A.2.1 Standard 2 System layout
1 Standard 1 Unit type
2 Options 3 Space operation
2 Compressor type 4 Domestic hot water
3 Capacities 3 Indoor software type
4 Confirm layout 5 Heat source
4 Backup heater steps 6 System operation
5 Backup heater type 7 Commissioning
6 Benefit kWh supply 8 Overview settings
7 Unit control method
8 Number of water zones
9 Pump operation mode
A Power saving possible possible
B User interface location

• On new units some items are already read only:


• (1) Unit type (e.g. LT split)
• (2) Compressor type (GBS - 008/GQI - 016)
• (3) Indoor software type (e.g. Type 1 (H+C))
• (4) BUH steps (e.g. 2)
• Capacities menu is used for energy metering (so in case of GQI and
no energy meteres => not shown)
• If two user interfaces are used, during quick wizard other shows busy.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 170
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System layout: Standard - BUH type A.2.1 Standard


1 Unit type
2 Compressor type
3 Indoor software type
4 Backup heater steps
Set [A.2.1.5]: BUH type (must be correctly wired by installer) 5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
 (1) 1PN,(1/1+2): 6 kW 1~ 230 V (*9W-6V3) 9 Pump operation mode
A Power saving possible
(Step 2 can be disabled) possible
B User interface location

 (3) 3P,(1/1+2): 6 kW 3~ 230 V (*9W-6T1)

 (4) 3PN,(1/2): 6 kW 3N~ 400 V (*9W-6WN))

 (5) 3PN,(1/1+2): 9 kW 3N~ 400 V (*9W-9WN)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 171
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System layout: Standard – Preferential kWh rate


A.2.1 Standard
1 Unit type
2 Compressor type
3 Indoor software type
Set [A.2.1.6]: Preferential kWh rate (S1S on X5M) 4 Backup heater steps
5 Backup heater type
6 Preferential kWh rate
7 Unit control method

 (0) No/ (1)Active Open / (2)Active closed 8 Number of water zones


9 Pump operation mode
A Power saving possible
possible
B User interface location

Active open Active closed


• Forced off when contacts opens • Forced off when contacts closes
• Operation allowed when contact is • Operation allowed when contact is
closed open

• Power supply wiring has to be connected accordingly

• Always make sure [A.6.1]: Auto restart is enabled


(default=enabled)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 172
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System Layout - Standard – Unit control method


A.2.1 Standard
1 Unit type
2 Compressor type
3 Indoor software type
Set [A.2.1.7]: Unit control method 4 Backup heater steps
5 Backup heater type
6 Preferential kWh rate
7 Unit control method
8 Number of water zones

 (0) LWT 9 Pump operation mode


A Power saving possible
possible
B User interface location

 (1) External thermostat control

 (2) Room thermostat control (by ambient temperature measured on


the user interface)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 173
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality

Unit operates based on ambient tempeature by user interface

• Main settings in menu structure:


A Installer settings A.2 System layout A.2.1 Standard
1 Language 1 Standard 1 Unit type
2 System layout 2 Options 2 Compressor type
3 Space operation 3 Capacities 3 Indoor software type
4 Domestic hot water 4 Confirm layout 4 Backup heater steps
5 Heat source 5 Backup heater type
6 System operation 6 Benefit kWh supply
7 Commissioning 7 Unit control method
8 Overview settings 8 Number of water zones
9 Pump operation mode
A Power saving possible possible
B User interface location

A.3 Space operation A.3.1 Leaving water A.3.1.1 Water temp main
1 Leaving water 1 Main 1 LWT setpoint mode
2 Room thermostat 2 Add 2 Temperature range
3 Operation range 3 Delta T emitter 3 Set weather dependent heating
4 Set weather dependent cooling
5 Modulated LWT
6 Shut off valve
7 Emitter type

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 174
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Adjust room temperature setpoint

• By scheduled operation (refer to [5] Select schedules)


• Or on the homescreen (basic / detailed)
 Press OK or up/down to see ‘Desired’ temperature

Basic home screen Detailed home screen


• Up/Down overrules temperature • Up/Down overrules temperature set by
schedule timer
set by schedule timer
 Next scheduled action takes over set
 Next scheduled action takes point again
over set point again • Comfort/Eco mode can be chosen
 [7.2] > Temperature lock is applicable
(refer to [7] User settings
• If overruled: icon is shown

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 175
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Determination of the LWT setpoint

A.3.1.1.1 LWT setpoint: Absolute or WD


Weather depending LWT setpoint
Absolute LWT setpoint Set A.3.1.1.3. graph
• (eco/comf preset values- • Eco/comf shift preset value
[7.4.2.1~4]) ) is linked to room ([7.4.2.5~8]) is linked to room
temperature setpoint temperature setpoint
• WD shift value is applied on the
temperature calculated according
to the WD settings.
Eco/comf Shift

[7.4.2.1]
[7.4.2.5]
e.g +3°C
[7.4.2.2]
[7.4.2.6]
e.g 0 °C

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 176
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Determination of the leaving water set point

A.3.1.1.5 Modulated LWT = ON

• Modulation depends mainly on running time and difference


between room temperature and room temperature setpoint
• If difference > 2°C => LWT temperature setpoint can be automatically
adjusted higher
• If difference < 2°C => LWT temperature setpoint can be automatically
adjusted lower

 Set [8-06]: maximum modulation (default 3°C)


 E.g. [8-06] = 3°C: LWT can be modulated from -3°C to 3°C

ATTENTION: user can not adjust LWT on homescreen anymore!!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 177
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Determination of the leaving water set point

LWT shift around 0°C


 Set [D-03]
• Local shift value is added to target LWT SP
• Around 0°C more capacity can be needed as energy can go
towards e.g. melting ice.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 178
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Determination of the leaving water set point

• Leaving water setpoint is the total of:

& Absolute leaving water temperature / Shift value (in case WD)
& Weather dependent leaving water temperature (in case WD)
& Modulation of the leaving water temperature
& LWT shift around 0°C in heating

Modulated LWT = ON Modulated LWT = OFF


• LWT setpoint on homescreen is not • LWT setpoint on homescreen is adjustable
adjustable (icon visible)
• LWT setpoint is linked to RT setpoint by • If weather depending => shift value can be
preset values set

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 179
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Unit operates based on ambient tempeature by user interface

RESUME: Main settings in menu structure:

 Set [A.2.1.7]: Unit control method: (2) room thermostat control

 Set [A.2.1.B]: User interface location: Room


(if two user interfaces – one in room measures room temperature)

 Set [A.3.1.1.5]: Modulated LWT: YES/NO

 Set [A.3.1.1] LWT setpoint mode: Absolute/weather depending

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 180
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]:Room thermostat functionality


Unit operates based on ambient tempeature by user interface

Extra specific setting in overview settings:


 Set [9-0C]: Room thermostat Hysteresis

• Effect In heating mode: • Effect In cooling mode


• Thermo ON if: • Thermo ON if:
Room temp < setpoint – [9-0C]/2 Room temp > setpoint + [9-0C]
• Thermo OFF if: • Thermo OFF if:
• Room temp > setpoint + [9-0C]/2 Room temp < setpoint - [9-0C]
• Default: 1°C A Installer settings
1 Language
• Range: 1°C~6°C 2 System layout
3 Space operation
• Step 0.5 4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 181
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System Layout - Standard – Unit control method


A.2.1 Standard
1 Unit type
2 Compressor type
3 Indoor software type
Set [A.2.1.7]: Unit control method 4 Backup heater steps
5 Backup heater type
6 Preferential kWh rate
7 Unit control method
8 Number of water zones

 (0) LWT 9 Pump operation mode


A Power saving possible
possible
B User interface location

 (1) External thermostat control

 (2) Room thermostat control (by ambient


temperature measured on the user interface)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 182
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: LWT control

Unit operates based on leaving water temperature

 Main settings in menu structure:


A Installer settings A.2 System layout A.2.1 Standard
1 Language 1 Standard 1 Unit type
2 System layout 2 Options 2 Compressor type
3 Space operation 3 Capacities 3 Indoor software type
4 Domestic hot water 4 Confirm layout 4 Backup heater steps
5 Heat source 5 Backup heater type
6 System operation 6 Benefit kWh supply
7 Commissioning 7 Unit control method
8 Overview settings 8 Number of water zones
9 Pump operation mode
A Power saving possible possible
B User interface location

A.3 Space operation A.3.1 Leaving water A.3.1.1 Water temp main
1 Leaving water 1 Main 1 LWT setpoint mode
2 Room thermostat 2 Add 2 Temperature range
3 Operation range 3 Delta T emitter 3 Set weather dependent heating
4 Set weather dependent cooling
5 Modulated LWT
6 Shut off valve
7 Emitter type

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 183
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: LWT control


Setting / Adjusting the leaving water temperature setpoint

• By scheduled operation (refer to [5] Select schedules and only


if A.3.1.1. LWT setpoint mode = abs/WD + SCHED)
• For additional zone: actions are limited to: Enable/disable

• Or on the homescreen (basic / detailed)


Basic home screen Detailed home screen
• Up/Down overrules temperature • Up/Down overrules temperature set by
set by schedule timer schedule timer (if WD: shift is
 Next scheduled action takes adjusted)
over set point again  Next scheduled action takes over
set point again
• If overruled: icon is shown

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 184
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: LWT control


Determination of the leaving water set point

LWT shift around 0°C


 Set [D-03]
• Local shift value is added to target LWT SP
• Around 0°C more capacity can be needed as energy can go
towards e.g. melting ice.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 185
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: LWT control


Determination of the leaving water set point

• Leaving water setpoint is the total of (both main/add):

+ Absolute leaving water temperature / Shift value (WD)


+ LWT shift around 0°C in heating
+ Weather dependent leaving water temperature (in case WD)

Weather depending ON Weather depending off (absolute SP)


• Preset values are shift values • Preset values are absolute values
• Schedule timer: program shift values • Schedule timer: program absolute values
• Shift can be overruled on homescreen • Absolute value can be overruled on
homescreen

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 186
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: LWT control


Unit operates based on leaving water temperature

RESUME: Main settings in menu structure:

 Set [A.2.1.7]: Unit control method: (0) leaving water temperature control

 Set [A.2.1.8] : Number of water zones: 1 or 2

 Set [A.3.1.1] : LWT Setpoint mode:


• (0) Absolute
• (1) WD
• (2) Abs+sched
• (3) WD + sched (Available as well for Additional zone)

 Set [5.2.1]: Set schedule

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 187
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: LWT control


Unit operates based on leaving water temperature

Extra setting in overview settings:

 Set [9-04]: LWT overshoot setting

• Default: 1°C

• Range : 1°C~4°C

A Installer settings
• Step: 1°C 1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 188
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1] System Layout - Standard – Unit control method


A.2.1 Standard
1 Unit type
2 Compressor type
3 Indoor software type
Set [A.2.1.7]: Unit control method 4 Backup heater steps
5 Backup heater type
6 Preferential kWh rate
7 Unit control method
8 Number of water zones

 (0) LWT 9 Pump operation mode


A Power saving possible
possible
B User interface location

 (1) External thermostat control

 (2) Room thermostat control (by ambient


temperature measured on the user interface)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 189
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: external RT control

Unit operates based external room thermostat


• Main settings in menu structure:

A Installer settings A.2 System layout A.2.1 Standard


1 Language 1 Standard 1 Unit type
2 System layout 2 Options 2 Compressor type
3 Space operation 3 Capacities 3 Indoor software type
4 Domestic hot water 4 Confirm layout 4 Backup heater steps
5 Heat source 5 Backup heater type
6 System operation 6 Benefit kWh supply
7 Commissioning 7 Unit control method
8 Overview settings 8 Number of water zones
9 Pump operation mode
A Power saving possible possible
B User interface location

A.3 Space operation A.3.1 Leaving water A.3.1.1 Water temp main
1 Leaving water 1 Main 1 LWT setpoint mode
2 Room thermostat 2 Add 2 Temperature range
3 Operation range 3 Delta T emitter 3 Set weather dependent heating
4 Set weather dependent cooling
5 Modulated LWT
6 Shut off valve
7 Emitter type

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 190
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: external RT control


A.2.2 Options
1 DHW operation
3 DHW tank heater

• Set [A.2.2.4]: the contact types for main/add 4 Contact type main
5 Contact type add
6 Digital I/O pcb
• C/H request 7 Demand pcb
8 External kWh meter 1
• IF 1 water zone: C/H changeover decided by ext room thermostat 9 External kWh meter 2

• Thermo ON/OFF A External DHW pump


B External sensor

• If 2 water zones => C/H operation is decided by user


interface

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 191
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: external RT control


• LWT set determination:

+ Absolute temp or shift value


+ Shift around 0°C
+ Weather dep value (if WD)

Weather depending ON Weather depending off (absolute SP)


• Shift can be overruled on • Absolute value can be overruled on
homescreen homescreen

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 192
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.7]: external RT control


Unit operates based external room thermostat

RESUME: Main settings in menu structure:

 Set [A.2.1.7]: Unit control method: (1) Ext. room


thermostat control

 Set [A.3.1.1] LWT septoint mode: Absolute/weather


depending

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 193
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.8]: System layout - Standard – number of LWT zones

Set [A.2.1.8]: Number of LWT zones

2 LWT zones:
1 LWT zone:
- 1 Main zone: Lowest LWT in heating
(highest in C)
- 1 Add zone: Highest LWT in heating(
lowest in C)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 194
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.9]: System layout - Standard – Pump operation mode


A.2.1 Standard
1 Unit type
2 Compressor type
Set [A.2.1.9]: Pump operation mode 3 Indoor software type
4 Backup heater steps
5 Backup heater type
6 Preferential kWh rate
7 Unit control method
 (0) Continuous pump operation 8 Number of water zones
9 Pump operation mode
• Regardless of thermo ON/OFF A Power saving possible
possible
• Always possible to choose B User interface location

 (1) Sample
• Samples every 5 minutes for 3 minutes
• Only possible to choose if [A.2.1] unit control method = LWT control

 (2) Request
• Operates when external contact generates thermo ON request
• Only possible to choose if [A.2.1] unit control method = External
room thermostat control or room thermostat

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 195
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.A]: System layout - Standard – Power saving possible


A.2.1 Standard
1 Unit type
2 Compressor type
Possible if 3 Indoor software type
4 Backup heater steps

+ Unit is not operating 5 Backup heater type


6 Preferential kWh rate
7 Unit control method
+ Ambient temperature is not very low 8 Number of water zones
9 Pump operation mode
+ Timer to prevent frequent on/off of outdoor unit is A Power saving possible
B User interface location

not running A Installer settings


1 Language
2 System layout
3 Space operation
4 Domestic hot water
Based on outdoor temperature and discharge 5 Heat source
6 System operation
temperature => Unit decides if preheat is necessary 7 Commissioning
8 Overview settings
and if power saving mode can be started.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 196
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.A]: System layout - Standard – Power saving possible


A.2.1 Standard
1 Unit type
2 Compressor type
 [A.2.1.A]: Power saving possible (read only) 3 Indoor software type
4 Backup heater steps
• Only possible if GBS 5 Backup heater type
6 Preferential kWh rate
7 Unit control method
Extra setting in overview settings: 8 Number of water zones
9 Pump operation mode

 [E-08] Power saving enabled/disabled: A Power saving possible


B User interface location
A Installer settings
• (0): Disabled (default) 1 Language
2 System layout
• (1): Enabled 3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

Jumper has to be removed from


OU as well! (while power off)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 197
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.B]: System layout Standard – User interface location


A.2.1 Standard
1 Unit type
2 Compressor type
 Set [A.2.1.B]: User interface location (room/unit) 3 Indoor software type
4 Backup heater steps
5 Backup heater type
6 Preferential kWh rate
7 Unit control method
Only applicable if two user interfaces 8 Number of water zones
9 Pump operation mode
A Power saving possible
B User interface location
• No difference in operation, all information is synchronized
• Except for homescreens
• Except for locks

• Room thermostat measures the room temperature


• Important for room temperature control (refer to :[A.2.1.7]:Room
thermostat functionality)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 198
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.1.A]: System layout Standard – User interface location


A.2.1 Standard
1 Unit type

• On first connection of extra user interface:


2 Compressor type
3 Indoor software type
4 Backup heater steps
 U5 error will appear 5 Backup heater type
6 Preferential kWh rate
 Message to push 4s ON/OFF button on the main user 7 Unit control method
8 Number of water zones
interface 9 Pump operation mode
A Power saving possible
 After reinitializing: possibilty to send or receive data B User interface location

• All data is sent/received: Language files, settings,


schedule timers,…

• Errors related to use of multiple user interfaces


• U5 (both main UI)
• U8 (both sub UI)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 199
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout - Options

A Installer settings
1 Language
2 System layout
A.2 System layout A.2.2 Options A.2.2.6 Digital I/O pcb 3 Space operation
1 Standard 1 DHW operation 1 Ext. backup heat source 4 Domestic hot water
2 Options 3 DHW tank heater 2 Solar kit 5 Heat source
3 Capacities 4 Contact type main 3 Alarm output type 6 System operation
4 Confirm layout 5 Contact type add 4 Bottom plate heater 7 Commissioning
6 Digital I/O pcb 8 Overview settings
7 Demand pcb
8 External kWh meter 1
9 External kWh meter 2
A External DHW pump
B External sensor

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 200
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout - Options

 Set [A.2.2.1] DHW operation ((0)Yes / (1) No)

 Set [A.2.2.3] DHW tank heater ((0) Horizontal / (1) BUH)

 Set [A.2.2.4] Contact type main ((1) Thermo ON/OFF request / (2) C/H request)

 Set [A.2.2.5] Contact type Add((1) Thermo ON/OFF request / (2) C/H request)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 201
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout - Options – Digital I/O PCB


A.2.2 Options
1 DHW operation
3 DHW tank heater
A.2.2.6 Digital I/O pcb 4 Contact type main
1 Ext. backup heat source 5 Contact type add
2 Solar kit 6 Digital I/O pcb
3 Alarm output type 7 Demand pcb
4 Bottom plate heater 8 External kWh meter 1
9 External kWh meter 2
A External DHW pump

 Set [A.2.2.6.1]: Ext. BUH source ((0) None / (1) Bivalent) B External sensor

 Set [A.2.2.6.2]: Solar pump station kit ((0) Not installed / (1)
Installed) (D-07, previously F-04!)
 Set [A.2.2.6.3]: Alarm output type: (C-09, previously C-01!)

Possible to detect power


failure by alarm contact

 Set [A.2.2.6.4]: Bottom plate heater connected to indoor unit


((0) No / (1) Yes)
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 202
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.8] System Layout - Options A Installer settings


1 Language
Additional settings in overview settings 2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
 Set [C-03]: Bivalent ON temperature 8 Overview settings

 Set [C-04] Bivalent hysteresis

 Set [F-02]: Bottom plate heater ON temperature: 3~10°C


(default 3°C)

 Set [F-03]: Bottom plate hysteresis: 2~5°C (default 5°C)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 203
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout - Options


A.2.2 Options
1 DHW operation
 Set [A.2.2.7]: Optional demand PCB ((0) Not installed / (1) 3 DHW tank heater
4 Contact type main
Installed) 5 Contact type add
6 Digital I/O pcb
• Only for ERLQ004~008CAV3 7 Demand pcb
8 External kWh meter 1
• PCB’s digital inputs used for power limitation 9 External kWh meter 2
• A External DHW pump
B External sensor

 Set [A.2.2.8/9]: Ext. kWh meter 1/2((0) Not installed / (1)


Installed)
• 0 (No): NOT installed
• (1) Installed (0.1 pulse/kWh)
• (2) Installed (1 pulse/kWh)
• (3) Installed (10 pulse/kWh)
• (4) Installed (100 pulse/kWh)
• (5) Installed (1000 pulse/kWh)

• In case of GQI: To enable power metering, ext kWh meter


must be installed (GBS OU can measure power
consumption). Refer to [6.2] Information > Power metering
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 204
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout - Options – External DHW pump


A.2.2 Options
1 DHW operation
 Set [A.2.2.A]: External DHW pump 3 DHW tank heater
4 Contact type main
• (0) Not installed 5 Contact type add
6 Digital I/O pcb
• (1) Secondary retour (instant hot water at tap points 7 Demand pcb
8 External kWh meter 1
• (2) Disinfection shunt pump 9 External kWh meter 2
• Never heat up to above 80°C! (can lead to damage and possibleAB External
External DHW pump
sensor
leakage)

DANGER: RISK OF BURNING


During and shortly after disinfection, the temperature at the hot water tap is as high
as the disinfection tank temperature. If necessary, install a mixing valve to limit the
temperature at the hot water tap
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 205
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout Options


A.2.2 Options
1 DHW operation
3 DHW tank heater
4 Contact type main
 Set [A.2.2.B]: External sensor 5 Contact type add
6 Digital I/O pcb
 Not installed (sensor of user interface is used to measure 7 Demand pcb
8 External kWh meter 1
indoor temp, sensor of outdoor unit for ambient temp) 9 External kWh meter 2
A External DHW pump
 (1) Outdoor sensor B External sensor

 (2) Room sensor


• Offset can be set (refer to [A.3.2.3] UI sensor, [A.3.2.3] ext.
Sensor for room temp, [A.6.5] Ext. Sensor for ambient temp.

• External sensor is used for all operation logic (except


for protection functions)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 206
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2.2] System Layout -Capacities A Installer settings


1 Language
2 System layout
A.2 System layout A.2.3 Capacities 3 Space operation
1 Standard 1 Booster heater 4 Domestic hot water
2 Options 2 Backup heater (step 1) 5 Heat source
3 Capacities 3 Backup heater (step 2) 6 System operation
4 Confirm layout 6 Bottom plate heater 7 Commissioning
8 Overview settings
• Set [A.2.3.1]: Booster heater (default 0)
• Set [A.2.3.2/3]: BUH step 1/2
• Default: BUH [A.2.3.2]: [A.2.3.3]
model BUH 1 BUH2 Total
3V 3 0
9W 3 6 9

• In case of 9W, adjust manually to:


[A.2.3.2]: [A.2.3.3]
BUH type [A.2.1.5] BUH 1 BUH2 Total
1P,(1/1+2): 3 kW 1~ 230 V (*9W) 1 3 0 3
3P,(1/1+2): 6 kW 3~ 230 V (*9W) 3 3 3 6
3PN,(1/2): 6 kW 3N~ 400 V (*9W) 4 3 3 6
3PN,(1/1+2): 9 kW 3N~ 400 V (*9W) 5 3 6 9

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 207
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.3. Switching homescreens

 Possible homescreens: LWT/Room/tank/LWT add

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 208
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.4. Symbols

IMPORTANT

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 209
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.5. Tips and tricks


1. If the OK-button is pushed for 5 seconds, the buttons are
locked. Unlock by pushing OK again for 5 seconds.

2. You can lock functions separately by entering the menu and


then pushing the OK button for 5 seconds.

3. By pushing the ‘ON/OFF’ button for 5 seconds, you shut down


the whole system (tank, LWT, room, ..). Pushing ‘ON/OFF’
again for 5 seconds will turn the whole system ON again.

4. Otherwise every screen needs to be put ON/OFF separately

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 210
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.6. User settings


To enter main menu:
push menu-button

1. Set time/date
2. Holiday
3. Quiet mode
4. Operation mode
5. Select schedules
6. Information
7. User settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 211
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[1] Set time/date

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 212
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[1] Set time/date

 Date
• Always: (d)d mmm yyyy (E.g. 1 Jan 2011)

 Time

 Daylight Saving Time


• Last Sunday of March at 02:00 => time + 1 hour
• Last Sunday of October at 3:00 => time – 1 hour

 Clock type (24hours clock hh:mm / 12 hours clock: h:mm


am/pm)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 213
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[2] Holiday

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 214
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[2] Holiday
• Only usable if RT control
! If ext. RT for add. zone => also
program Home Away
• Deviate from normal schedules
during holiday
 Set Holiday mode: Home or Away
 Set ‘From’ and ‘Until’
Staying at home during holiday Going away during holiday
 Select a day schedule (eg.  Set operation mode
Saturday) (H/C/Automatic/OFF)
• Space H/C and DHW will work • Space H/C will work according to
according to the temperature of the holiday settings
selected day • DHW is turned off, only disinfection
mode will work
• DHW will resume normally from 0:00
the day you return
 Set Space H/C setpoints
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 215
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[2] Holiday Home Away

• After setting up: Activate holiday!


 In [2.1] Holiday => Activate => Yes => OK!
Holiday mode = Home and activated Holiday mode = Away and activated
• Holiday icon is visible • Not running: Holiday icon is visible

• You can not see ‘Holiday’ screen • When running ‘Holiday’ screen is
visible:

All Seasons °
CLIMATE COMFORT • LED is off
V. Eylenbosch 30 March 2018 216
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[2] Holiday Home Away

• If you come home during holiday

• Holiday mode is configured and active

• You come home for a few hours and want to use your normal
schedule.Deactivate the holiday mode.

• When you go away again, activate the holiday mode again.


(No need to change schedule or holiday configuration!)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 217
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[3] Quiet mode (outdoor)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 218
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[3] Quiet mode (outdoor)


• Can be locked
• Status is indicated in menu
• If active is visible on home screen
• Quiet level: [7.4]: > User settings > Preset values

 Set Quiet mode OFF / Auto / On

• Quiet mode according to scheduled • Quiet mode active until the next
action: [7.3.6] User settings>Set scheduled action
schedule>Quiet mode
New for GBS models!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 219
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[4] Operation mode

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 220
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[4] Operation mode


• Not visible if:

 Heating only heat pump!


 1 water tempature zone + external RT control + seperate C/H signal

 Manually set heating, cooling or automatic changeover

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 221
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[4] Operation mode AUTOMATIC

Automatic changeover: Restriction per month (take priority)


 Set [7.5]: > User settings > Allowed operation mode (per
month)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 222
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[4] Operation mode AUTOMATIC

Installer sets:
Changeover based on outdoor ambient temperature:
 [A.3.3.1] > Space operation > System: Space heating OFF temp
 [A.3.3.2.] > Space operation > Space cooling ON temp

OU Ambient temp
Operation changes
over to cooling
[A.3.3.1] SPH
off

[A.3.3.1] SPC
off
Operation changes
over to heating

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 223
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[4] Operation mode AUTOMATIC


if RT control + 1water zone + quick heat emitters
Installer sets:
Based on indoor temperature (in overview settings):
 [4-0B]: Minimum hysteresis (default: 1°C)
 [4-0D]: Minimum offset (default: 3°C)
• Only meaningful Only possible if outdoor temp is allowing both heating
and cooling
Operation changes
Room temp over to cooling

Cooling SP [4-0B] Hysteresis

Heating SP [4-0D] Offset

Operation changes
over to heating
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 224
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[4] Operation mode AUTOMATIC

• Restrictions per month still have priority (will change


accordingly)

• Not possible if:


& External room thermostat control
& 1 water zone
& Thermostat with 2 contacts (1 for heating and 1 for cooling)
 Then the external thermostat determines which space operation mode is
used; not the user interface.

• Possible:
+ All other cases

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 225
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[5] Select schedules

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 226
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[5] Select schedules

• Select and activate schedules


• Room temperature
• LWT main
• LWT additional
• Tank temperature

 Select control for schedule. (E.g.: [5.1] Room temperature)


 Set operation mode for schedule. (E.g.: [5.1.1] Heating)
 Set a predefined or user-defined schedule
• Menu is only visible if allowed by installer (in case of room
thermostat control (always) or Absolute/WD + schedule)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 227
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[5] Select schedules: Programming schedules

• To program a schedule
• Room temperature
• LWT main
• LWT additional
• Tank temperature
• Booster heater permission
• Quiet mode
• DHW pump
 Go to [7.3]: > User settings > Set schedules
 Open empty, predefined or user-defined schedule
 Change & save
• Room temperature and LWT main:
3x Heating + 3x Cooling (Based on Eco & Comfort SP)
• LWT additional : 3x Heating + 3x Cooling (Based on ON/OFF)
• DHW: 3x (Based on Start storage comfort & storage eco)
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 228
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[5] Select schedules: Using preset values

• Define preset values for multiple controls

 Set [7.4]: > User settings > Preset values.


 Select control (E.g. Room temperature)
 Select a preset value (E.g. Comfort (heating)
 Set a temperature

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 229
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 230
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information:

• Visible information depends on user level


• End user (default)
• Advanced end user* (hold for 5 seconds in [6] or sublevel)
• Installer* (hold for 4 seconds in [6.4]: > User permission level)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 231
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Sensor information

• [6.1] Sensor information


• Room and tank temperature
• Outdoor temperature, LWT (BUH), LWT (PHE), RWT, Refrigerant
temperature, flow rate, (outdoor temp (external sensor))

6.1 Sensor information


1 Room temperature
2 Outdoor temperature
3 Tank temperature
4 Leaving water (BUH)
5 Leaving water (PHE)
6 Returning water temp
7 Refrigerant temp
8 Flow rate

A Outdoor temp (ext)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 232
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Energy metering

• [6.2] Energy metering (kWh)


• Energy consumption (Total and combined last 12 months)
• Energy consumption (Additionally shows last two months)*
6.2.1 Consumed electricity 6.2.1.x yyyy
B November 1 Space heating
C December 2 Space cooling
D Last 12 months 3 DHW
E Total 4 Total

 All values are split up in cooling/heating/DHW and Total


 Outdoor power consumption: calculated by Watt meters or instantaneous
power received from OU (GBS)
 Pump power: PWM value is taken into account
 BUH, BSH, BPH, Heater tape, .. According to specification and ON/OFF

- Not shown if GQI unless external energy meters are installed


(then only Space heating/cooling/DHW)
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 233
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Energy metering

• [6.2] Energy metering (kWh)


• Produced energy (Total and combined last 12 months)
• Produced energy (Additionally shows last two months)* A.2.2 Options
1 DHW operation
3 DHW tank heater
6.2.2 Produced electricity 6.2.2.x yyyy 4 Contact type main
B November 1 Space heating 5 Contact type add
C December 2 Space cooling 6 Digital I/O pcb
D Last 12 months 3 DHW 7 Demand pcb
E Total 4 Total 8 External kWh meter 1
9 External kWh meter 2
A External DHW pump

 All values are split up in cooling/heating/DHW and Total B External sensor

 In heating: HP+BUH (if applicable +ext. BUH)


 In DHW HP + BSH (or BUH)

- Not shown if GQI unless external energy meters are installed


(then only Space heating/cooling/DHW)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 234
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Energy metering

A.2.2 Options
1 DHW operation
3 DHW tank heater
4 Contact type main
5 Contact type add
6 Digital I/O pcb
7 Demand pcb
8 External kWh meter 1
9 External kWh meter 2
A External DHW pump
B External sensor

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 235
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Others

• [6.3] Error handling


• Error history (20 last error codes+ date/time & details)
• Contact/helpdesk number (read only)
• Contact/helpdesk number (installer can set)

• [6.4] User permission level


6.5 Actuators 6.6 Operation modes
• Current user permission level 1 Pump 1 Legionella
2 Compressor 2 Defrost / oil return
• For installer level: hold 4s button 3 Backup heater: step 1 3 Hot start
4 Backup heater: step 2 4 Emergency (outdoor)
5 Booster heater 5 Emergency (indoor)
6 2 way valve 6 Bivalent


7 3 way valve 7 Power limit level
[6.5] Actuators* 8 BPH 8 Power limit status
B Solar pump 9 Powerful
• Status/mode of each actuator. C HP tariff A Quick heat up
D Thermostat main A B Waterpipe freezeup
E Thermostat main B C Room antifrost
F Thermostat add A D Power saving possible
• [6.6] Operation modes* G Thermostat add B E Draft prevention

• Current operation mode


All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 236
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Others

• [6.7] Running hours*


• Running hours of the system*
• Displayed in hours*
• Current month, previous month and Total
• Pump, BSH, compressor (split up per mode, also count of start/stops is
shown) BUH (split up in steps and modes), ext BUH’s, solar pump,
BPH,…
6.7 Running hours 6.7.1 Previous month 6.7.1.2 Compressor
1 Previous month 1 Pump 1 Space heating
2 Current month 2 Compressor 2 Space cooling
3 Total 3 Backup heater: step 1 3 Domestic hot water
4 Backup heater: step 2 4 Total
5 Booster heater 5 Nr starts
6 BPH
9 Solar pump 6.7.1.3 BUH1
1 Space heating
2 Domestic hot water
3 Total

6.7.1.4 BUH2
1 Space heating
2 Domestic hot water
3 Total
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 237
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[6] Information: Others

• [6.8] Version*
• Version information about the system
6.8 Version 6.8.1 User interface
1 User interface 1 Software
2 Indoor unit 2 Micon ID
3 Outdoor unit 3 EEPROM
4 Language file

6.8.2 Indoor unit


1 Model name
2 Software
3 EEPROM

6.8.3 Outdoor unit


1 Capacity
2 Model name
3 Software

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 238
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[7] User settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 239
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[7] User settings: Display

 Set [7.1.1] > Display > Contrast


 Set [7.1.2] > Display > Backlit LCD time
• When Installer level => automatically longer backlit time 10min
 Set [7.1.3] > Display > User profile

Extra visible:
• Modes (comfort, eco,
scheduled,..)
• Next scheduled action

 Set [7.1.4] > Display > Available home pages


All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 240
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[7] User settings: other

 Set [7.2] > Temperature lock


Operation mode change from
scheduled to eco/comfort =>
Timer before switching
automatically back to scheduled

• Permanent/2/4/6/8 hours
 Set [7.3] > Set schedules
• Refer to [5] Select schedules
 Set [7.4] > Preset values
 Select control (E.g. Room temperature)
 Select a preset value (E.g. Comfort (heating)
 Set a temperature
 Set [7.5] > Allowed operation mode
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 241
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.7. [A] Installer settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 242
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.1] Installer settings: language A Installer settings


1 Language
2 System layout
3 Space operation

• Here you can select the controller language. 4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings
• You can choose from the languages that are on
the controller, depending EKRUCAL1 or
EKRUCAL2.

• In case 2 controllers are connected


(EKRUCAL1 & 2), both languages are
available.

• More languages can be downloaded from


www.daikineurope.com

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 243
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.2] Installer settings: System layout


A Installer settings
1 Language
2 System layout
A.2 System layout 3 Space operation
A.2.1 Standard
1 Standard 4 Domestic hot water
1 Unit type
2 Options 5 Heat source
2 Compressor type
3 Capacities 6 System operation
3 Indoor software type
4 Confirm layout 7 Commissioning
4 Backup heater steps
8 Overview settings
5 Backup heater type
6 Benefit kWh supply
7 Unit control method
8 Number of water zones
9 Pump operation mode
A Power saving possible possible
B User interface location

A.2.2 Options A.2.2.6 Digital I/O pcb


1 DHW operation 1 Ext. backup heat source
3 DHW tank heater 2 Solar kit
4 Contact type main 3 Alarm output type
5 Contact type add 4 Bottom plate heater
6 Digital I/O pcb
7 Demand pcb
8 External kWh meter 1
9 External kWh meter 2
A External DHW pump
B External sensor

A.2.3 Capacities
1 Booster heater
2 Backup heater (step 1)
3 Backup heater (step 2)
6 Bottom plate heater
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 244
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.3] Space operation

A Installer settings A.3 Space operation A.3.1 Leaving water A.3.1.1 Water temp main
1 Language 1 Leaving water 1 Main 1 LWT setpoint mode
2 System layout 2 Room thermostat 2 Add 2 Temperature range
3 Space operation 3 Operation range 3 Delta T emitter 3 Set weather dependent heating
4 Domestic hot water 4 Set weather dependent cooling
5 Heat source 5 Modulated LWT
6 System operation 6 Shut off valve
7 Commissioning 7 Emitter type
8 Overview settings
A.3.1.2 Additional water temp 1
1 LWT setpoint mode
2 Temperature range
3 Set weather dependent heating
4 Set weather dependent cooling
A.3.1.3 Delta T emitter
1 Heating
2 Cooling
A.3.2 Room thermostat
1 Room temp range
2 Room temp offset
3 Ext. room sensor offset
4 Room temp step

A.3.3 Operation range


1 Space heating OFF temp
2 Space cooling On temp

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 245
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.3.1.1.6] Space operation: shutoff valve A.3.1.1 Water temp main


1 LWT setpoint mode
2 Temperature range
3 Set weather dependent heating
4 Set weather dependent cooling
5 Modulated LWT

 Set [A.3.1.1.6]: Shut off valve 6 Shut off valve


7 Emitter type

• (1) Close the valve during thermo ON/OFF of the main zone ((0)Do not close /
(1)close)

• (2) Close the valve during cooling operation ((0)Do not close / (1)close)

• Only available if additional zone is enabled A.3.1.1.6 Shut off valve


1 Thermo On/OFF
2 Cooling

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 246
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.3.1.1.7] Space operation Water temp main A.3.1.1 Water temp main
1 LWT setpoint mode
2 Temperature range
3 Set weather dependent heating

 Set [A.3.1.1.7]: Emitter type 4 Set weather dependent cooling


5 Modulated LWT
6 Shut off valve
7 Emitter type

Reaction time of the system:

• (0): Quick. E.g.: Small water volume and fan


coils.
• Allows for more modulation ref. [A.3.1.1.5] Modulated
LWT

• (1): Slow. Example: Large water volume, floor


heating loops.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 247
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.3.1.1.6] Space operation > LWT

 Set [A.3.1.2]: Additional zone water temp

A.3.1.2 Additional water temp 1


1 LWT setpoint mode
2 Temperature range
3 Set weather dependent heating
4 Set weather dependent cooling

 Set [A.3.1.3]: Delta T over the heat emitters (def: 5°c)

A.3.1.3 Delta T emitter


1 Heating
2 Cooling

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 248
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.3.2] Space operation > Room thermostat


A.3.2 Room thermostat
1 Room temp range
2 Room temp offset
3 Ext. room sensor offset
 Set [A.3.2.1]: Room temp range 4 Room temp step

A.3.2.1 Room temp range Min~max (°C) Default (°C)


1 Minimum temp (heating) 12~18 12
2 Maximum temp (heating) 18~30 30
3 Minimum temp (cooling) 15~25 15
4 Maximum temp (cooling) 25~35 35

 Set [A.3.2.2]: Room temp offset (-5~5°C)

 Set [A.3.2.3]: External room sensor offset (-


5~5°C)
• Ref to [A.2.2.B]: Installer settings > System layout >
Options: External sensor

 Set [A.3.2.4]: Step for setting desired room


temperature
°
on UI (0,5 or 1°C)
All Seasons CLIMATE COMFORT V. Eylenbosch 30 March 2018 249
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.3.3] Space operation > RT operation range


A.3.3 Operation range
1 Space heating OFF temp
2 Space cooling On temp

 Set [A.3.3]: Operation range


• Prevent overheating/overcooling
A.3.3 Operation range Min~max (°C) Default (°C)
1 SPH OFF temp (GBS) 14~25 25
1 SPH OFF temp (GQI) 14~35 35
2 SPC OFF temp (both) 10~35 20

• Used as base for automatic changeover (refer to


[4] Operation mode)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 250
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.8] Space operation > additional overview settings


A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
 Set [2-06]: Room frost protection 5 Heat source
6 System operation
• 0: Disabled 7 Commissioning
8 Overview settings
• 1: Enabled (default)

 Set [2-05]: Room antifrost temperature


• 4~16°C (default: 12°C)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 251
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4] Domestic hot water (DHW)

A Installer settings A.4 Domestic hot water A.4.2 Scheduled DHW


1 Language 1 SP mode 1 Schedule temperatures
2 System layout 2 Scheduled DHW 2 Storage comfort SP mode
3 Space operation 3 SP readout 3 Weather dependent curve
4 Domestic hot water 4 Disinfection A.4.3 SP readout A.4.3.2 Conversion graphical temp
5 Heat source 5 Maximum SP 1 SP readout type 1 1 pers
6 System operation 2 Conversion graphical temp 2 2 pers
7 Commissioning 3 3 pers
A.4.4 Disinfection
8 Overview settings 4 4 pers
1 Disinfection
2 Operation day 5 5 pers
3 Start time 6 6 pers
4 Temperature target
5 Duration

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 252
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode A.4 Domestic hot water


1 SP mode
 Set [A.4.1]: SP mode 2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP

• (0): Reheat only (not advised for integrated)


• Minimum temperature is kept according to reheat
• Bad for COP, almost constant operation of BUH

• (1): Reheat + sched.


• Main heat up according to schedule
• Minimum temperature is kept according to reheat

• (2): Scheduled only (no reheat operation) - default

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 253
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode – Scheduled DHW

A.4 Domestic hot water


 Set [A.4.2.1]: Schedule temperature 1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP
Actions possible in tank scheduled timer: A.4.2 Scheduled DHW
1 Schedule temperatures
2 Storage comfort SP mode
3 Weather dependent curve
 Preset (default): Will use:
• Storage comfort (preset value)
• Storage eco (preset value)
• Storage stop (ex. When SPH is required again)

 Custom: Will use


• [Custom temperature]
• Storage stop

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 254
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode – Scheduled DHW

 Set [A.4.2.2]: Storage comfort SP mode


A.4 Domestic hot water
1 SP mode
2 Scheduled DHW
 Absolute (default) 3 SP readout
4 Disinfection
 Weather depending => No shift possible on UI 5 Maximum SP
A.4.2 Scheduled DHW
• Applicable setpoint depends on [A.4.1]: SP mode 1 Schedule temperatures
2 Storage comfort SP mode
3 Weather dependent curve

[A.4.1]: SP mode = (1) Sched / [A.4.1]: SP mode = (0) Reheat only


Sched + reheat • Also applicable!
• Comfort SP = weather • Reheat SP = weather depending
depending • Reheat SP not adjustable on tank
• Eco SP = not WD, to be set in homescreen
preset value [7.4.3.2]

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 255
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode – Scheduled DHW

A.4 Domestic hot water


 Set [A.4.2.3]: Weather dependent curve 1 SP mode
2 Scheduled DHW

• Only applicable if WD SP mode 3 SP readout


4 Disinfection
5 Maximum SP
• Graphically displayed! A.4.2 Scheduled DHW
1 Schedule temperatures
2 Storage comfort SP mode
3 Weather dependent curve

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 256
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode A.4 Domestic hot water


1 SP mode
 Set [A.4.1]: SP mode 2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP

• (0): Reheat only (not advised for integrated)


• Minimum temperature is kept according to reheat
• Bad for COP, almost constant operation of BUH

• (1): Reheat + sched.


• Main heat up according to schedule
• Minimum temperature is kept according to reheat

• (2): Scheduled only (no reheat operation) - default

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 257
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
REFER TO RN12-16A – attention points and recommendations 2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

[4-03] Booster heater operation: defines whether the optional


booster heater operation is enabled (1) or has certain limitations
(0/2/3).
[4-03]=1, The booster heater operation is only determinded by booster
heater OFF temperature (TBH OFF), booster heater ON Temperature (TBH
ON), and/or schedule timer.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 258
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

[4-03]=0, The booster heater operation is only allowed during


“Disinfection function” and “Powerful domestic water heating”.
• This setting is only recommended in case the capacity of the
heat pump can cover the heating requirements of the house and
domestic hot water over the complete heating season.
• REMARK: When the ambient outdoor temperature is lower than
field setting [5-03] and setting [5-02] is activated, then the domestic
hot water will NOT be heated.
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 259
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings
[4-03]=2, is the setting that results in the most optimum coverage of
domestic hot water heated by the pump. Then the Booster heater is
only allowed if the heat pump is “out of range”.
• Has the same functionallity as setting [4-03]=0 added with following
conditions (3 times OR):
1. Ta < [5-03]
2. Ta > 35°C
3. TDHW > THP OFF – 2°C

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 260
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

[4-03]=3, is the setting that results in optimum coverage of domestic


hot water heated by heat pump in relation with [8-04]. Has the same
functionallity as setting [4-03]=1 added with following restrictions:
• The booster heater is OFF when the heat pump is active in domestic
hot water mode.
• This results that the Booster heater will not work simultaneous with
the heat pump for hot water production and that the setting [8-03] is
not relevant.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 261
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Extra settings in Overview settings 5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
• [6-00] Start: temperature difference determining the heat 7 Commissioning
8 Overview settings
pump ON temperature

• [6-01] Stop: temperature difference determining the heat


pump OFF temperature
(temperature difference based on the “Maximum heat
pump temperature”) (advised: 48°C)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 262
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP

TU : User set point temperature (as set on the user interface or weather depending)
THP MAX : Maximum heat pump temperature at sensor in domestic hot water tank
(Depends on OU)
THP OFF : Heat pump OFF temperature
THP ON : Heat pump ON temperature

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 263
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Extra settings in Overview settings 5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
• [7-00] Domestic hot water step length: temperature 5 Heat source
6 System operation
difference above the domestic hot water set point 7 Commissioning
8 Overview settings
temperature before the booster heater is turned off.

• [7-01] Hysteresis value booster heater: temperature


difference determining the booster heater ON
temperature TBH ON = TBH OFF – [7-01]

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 264
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP

• Depending on the setting for DHW temperature, you can see that the BUH
might be working a lot which is not good for COP. Choosing Reheat only
must be well considered before using.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 265
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Extra settings in Overview settings: 5 Maximum SP
A Installer settings
1 Language
2 System layout
95
3 Space operation
4 Domestic hot water
• [8-00] Minimum running time for DHW (no SPH allowed 5 Heat source
6 System operation
even when target has been reached) 7 Commissioning
8 Overview settings
• [8-01] Maximum running time for DHW (even when target
has not been reached)
• If Unit control method = (ext.) Room thermostat control:
 Max timer only taken into account if there is a request for space
heating or cooling.
 f there is NO request for space heating/cooling, the tank is heated
until heat pump OFF temperature.
• The actual maximum running time will automatically vary
between [8-01] and [8-01] + [8-04] depending on the
outdoor temperature
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 266
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Extra settings in Overview settings: 5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
• [8-02] Anti-recycling time: minimum required interval 5 Heat source
6 System operation
between two H/P domestic hot water heating cycles. 7 Commissioning
8 Overview settings

• [8-03] Booster heater delay timer: the start-up delay time


of booster heater after booster heater thermostat ON.

• [8-04] Additional running time at space heating/cooling off


(SPH OFF [A.3.3.1] = [4-02]/ SPC OFF =[A.3.3.2] = [F-02])

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 267
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) ReheatA.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Extra settings in Overview settings: 5 Maximum SP
A Installer settings
1 Language
2 System layout
3 Space operation
4 Domestic hot water
5 Heat source
6 System operation
• Booster heater allowance 4-03 and schedule timer for 7 Commissioning
8 Overview settings
booster heater

• 3 actions a day/weekly timer

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 268
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode = (0) Reheat

Time CAPA
DHW DHW + S
DHW+SPACE P
House demand
ONLY SPACE A
Spare C
Capacity HP capacity capacity of [8.04]
E
shortage of HP Maximum running time
HP O
B2
N
L
DHW by BSH A1
Y
ONLY [8.01] Maximum running time
B1
[8.02] Ta
Anti-recycle time A2

Equilibrium [5.01] Space heating OFF [4.02] 35°C


temperature 4x°C
Space Cooling permission [F.01]
All Seasons °
CLIMATE COMFORT
[5.03] Space heating priority
V. Eylenbosch 30 March 2018 269
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode A.4 Domestic hot water


1 SP mode
 Set [A.4.1]: SP mode 2 Scheduled DHW
3 SP readout
4 Disinfection
5 Maximum SP

• (0): Reheat only (not advised for integrated)


• Minimum temperature is kept according to reheat
• Bad for COP, almost constant operation of BUH

• (1): Reheat + sched.


• Main heat up according to schedule
• Minimum temperature is kept according to reheat

• (2): Scheduled only (no reheat operation) - default

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 270
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode (1/2) ReheatA.4+Domestic


sched /
hot water
Scheduled 1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Reheat: 5 Maximum SP

• Minimum temperature maintained: preset value [7.4.3.3]


Reheat (default 45°C)

• E.g. User sets [7.4.3.3] = 50°C => Tanks starts heating at


40°C

• Weather depending settings only applies to comfort


setpoint that can be scheduled

• Hysteresis in reheat: [6-08] (default:10°C)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 271
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.1] Domestic hot water: SP mode (1/2) ReheatA.4+Domestic


sched /
hot water
Scheduled 1 SP mode
2 Scheduled DHW
3 SP readout
4 Disinfection
Scheduled operation: 5 Maximum SP

• Predefined tempeatures that can be used (ref preset values –


A.4.2.1.):
• Storage comfort (can be WD– not settable)
• Eco comfort
• Reheat setpoint

• Custom temperatures

• Select schedule in [5]

• Set schedule in [7.3.4]

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 272
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.3] Domestic hot water: SP Read out A.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout

 Set [A.4.3.1]: Read out mode: Temp/Graph 4 Disinfection


5 Maximum SP

A.4.3 SP readout
1 SP readout type
 Set [A.4.3.2]: Conversion (eg. 1 person = 40°C 2 Conversion graphical temp

DHW SP)

A.4.3.2 Conversion graphical temp


1 1 pers
2 2 pers
3 3 pers
4 4 pers
5 5 pers
6 6 pers

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 273
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.3] Domestic hot water: SP Read out A.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout

• The user can overrule the setpoint (unless it’s WD) 4 Disinfection
5 Maximum SP

depending on SP readout setting:


 Amount of persons
 Temperature

• User can select powerful mode

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 274
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.4] Domestic hot water: disinfection A.4 Domestic hot water


A.4.4 Disinfection
1 SP mode
1 Disinfection
2 Scheduled DHW
2 Operation day
3 SP readout
3 Start time
4 Disinfection
4 Temperature target
5 Maximum SP
5 Duration

 Set [A.4.4.1]: Disinfection: (Enabled/disabled)

 Set [A.4.4.2]: Operation Day: Monday~Sunday

 Set [A.4.4.3]: Start time: 00~23hr

 Set [A.4.4.4]: Temperature target


• With BSH: Default: 70°C, range 55~80°C
try to reach the target
• With BUH: Default 60°C, fixed.
temperature within 4
hours
 Set [A.4.4.4]: Duration

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 275
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.4.5] Domestic hot water: Maximum tank setpoint A.4 Domestic hot water
1 SP mode
2 Scheduled DHW
3 SP readout

 Set [A.4.5]: Maximum setpoint for DHW operation 4 Disinfection


5 Maximum SP

• Max settable depends on [A.2.2.3] = E-07 (BSH or BUH)

• 40-80°C for tanks with BSH

• 40-60°C for tanks heated up by BUH

• Maximum does not apply to disinfection!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 276
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.5] Heat source

A Installer settings A.5 Heat sources A.5.1 Backup heater


1 Language 1 Backup heater 1 Operation mode
2 System layout 2 Auto emergency operation
3 Space operation 3 Enable BUH step 2
4 Domestic hot water 4 Equilibrium temperature
5 Heat source
6 System operation
7 Commissioning
8 Overview settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 277
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.5.1] Heat source - BUH A.5.1 Backup heater


1 Operation mode
2 Auto emergency operation
3 Enable BUH step 2
 Set [A.5.1.1]: Operation mode 4 Equilibrium temperature

• (0): Limited
• (1): Enabled (default)
• (2): DHW only
• Only possible if tank installed without BSH (e.g. integrated model)
• BUH is then only enabled during DHW operation

 Set [A.5.1.2]: Auto emergency operation


• (0): Not allowed
• (1): Allowed (default)
 In case of OU communication error U4
 In case of OU error

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 278
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.5.1] Heat source - BUH A.5.1 Backup heater


1 Operation mode
2 Auto emergency operation
3 Enable BUH step 2
 Set [A.5.1.3]: Enable BUH step 2 4 Equilibrium temperature

• (0) Not allowed


• (1) Allowed (default)

Limits backup heater capacity!!


For tank without BSH:
• Storage temperature setpoint > 50°C => Recommended to allow
BUH step 2 )

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 279
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.5.1] Heat source - BUH A.5.1 Backup heater


1 Operation mode
2 Auto emergency operation
3 Enable BUH step 2
 Set [A.5.1.4]: Equilibrium temperature 4 Equilibrium temperature

• Temp below which BUH can help during SPH


1: Heat pump (outdoor unit) capacity
2: Required heating capacity (site dependent)
3: Additional heating capacity provided by the backup
heater
4: Equilibrium temperature
TA: Ambient (outdoor) temperature
PH: Heating capacity

 [5-02] Space heating priority status: specifies whether space


heating priority is enabled (1) or disabled (0) for low outdoor
temperatures.
 [5-03] Space heating priority temperature: below this outdoor
temperature, the sanitary water will be heated by the booster
heater only (or BUH will help during DHW)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 280
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.5.1] Heat source – BUH (extra overview settings)

 [5-04]: Set point correction for DHW temperature


A Installer settings
1 Language
 [C-00]: Solar kit (if installed) priority: 2 System layout
3 Space operation
• 0: Solar kit 4 Domestic hot water
5 Heat source
• 1: Heat pump 6 System operation
7 Commissioning
8 Overview settings

 [C-01]: SPH/DHW priority


• 0: Operation with highest request
• 1: Always space heating/cooling priority

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 281
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6] System operation

A Installer settings A.6 System operation A.6.2 Benefit kWh supply


1 Language 1 Auto restart 1 Allowed heater
2 System layout 2 Benefit kWh supply 2 Forced pump off
3 Space operation 3 Power consumption control
4 Domestic hot water 4 Average time A.6.3 Power consumption control A.6.3.5 Amp limits for DI
5 Heat source 5 Ext. amb. sensor offset 1 Mode 1 limit DI 1
6 System operation 6 forced defrost 2 Type 2 limit DI 2
7 Commissioning 3 Amp value 3 limit DI 3
8 Overview settings 4 kW value 4 limit DI 4
5 Amp limits for DI
6 kW limits for DI A.6.3.6 kW limits for DI
7 Priority 1 limit DI 1
2 limit DI 2
3 limit DI 3
4 limit DI 4

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 282
TOP SECRET
SECRET
INTERNAL USE ONLY
A.6 System operation PUBLIC

[A.6] System operation – auto restart 1 Auto restart


2 Benefit kWh supply
3 Power consumption control
4 Average time
5 Ext. amb. sensor offset
6 forced defrost
 Set [A.6.1]: Auto restart ((0) Disabled / (1) Enabled)
• Operation is restarted

• Exception: DHW operations: legionella, powerful, comfort storage, eco


storage (storage will start again on next scheduled action)

• DHW reheat will continu

• Default: Enabled

If power failure > 48 hours => operation is restarted according to


[A.6.1] but:
• Date/time is reset to default (e.g. 0000 1 JAN 20212)
• Schedule timers and disinfection operation will operate faulty
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 283
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.2] System operation – preferential kWh rate


A.6 System operation
1 Auto restart
2 Preferential kWh rate

• Only settable if enabled: [A.2.1.6] > Installer settings >


power supply
3 Power consumption control
4 Average time
System layout > Standard > preferential kWh rate 5 Ext. amb. sensor offset
6 forced defrost
A.6.2 Preferential kWh rate
power supply
1 Allowed heater

 Set [A.6.2.1] Allowed heater: 2 Forced pump off

• (0) None (default)


• (1): Booster heater only
• (2): Backup heater only
• (3): All heaters
Only meaningful if:
• Preferential kWh rate power supply is of type 1 (signal for forced thermo OFF but no
power cut)
• Indoor unit is connected to a normal power supply and the BUH and BSH are not
connected to the preferential kWh rate power supply.
When tank without booster heater => Do not use (1) or ()3

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 284
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.2] System operation – preferential kWh rate


A.6 System operation
1 Auto restart
2 Preferential kWh rate

 Set [A.6.2.1] Allowed heater


power supply
3 Power consumption control
4 Average time
• Depending on tank: with BSH or without BSH 5 Ext. amb. sensor offset
6 forced defrost
A.6.2 Preferential kWh rate
power supply
1 Allowed heater
2 Forced pump off

EKHWS tank ([d-00]=A.6.3.1) Tank without booster heater

• Do not set (1) or (3)

 Set [A.6.2.2] Forced pump off


• (0) Forced off during preferential kWh rate
• (1) No limitation

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 285
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.3] System operation – power consumption control


Power consumption control: only for GBS and application
without BSH! A.6 System operation
1 Auto restart
2 Benefit kWh supply
3 Power consumption control
 Set [A.6.3.1]: Mode 4 Average time
5 Ext. amb. sensor offset
• (0): Disabled. 6 forced defrost

• (1): Enabled: The power is limited to setting


• (2): Enabled: The power limitation depends on status of relevant
digital inputs (att: optional demand pcb must be connected and set in A.2.2.7)

 Set [A.6.3.2]: Type


A.6.3 Power consumption
control
1 Mode
• (0): Based on current [A] 2 Type
3 Amp value
• (1): Based on power [kW]. 4 kW value
5 Amp limits for DI
6 kW limits for DI
7 Priority

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 286
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.3] System operation – power consumption control


A.6 System operation
1 Auto restart
2 Benefit kWh supply

• [A.6.3.1] = 1: The power is limited to setting: 3 Power consumption control


4 Average time
5 Ext. amb. sensor offset
• [A.6.3.2] = 0 6 forced defrost

 Set [A.6.3.1]: Amp value A.6.3 Power consumption


control

• [A.6.3.2] = 1 1 Mode
2 Type
3 Amp value
 Set [A.6.3.1]: kW value 4 kW value
5 Amp limits for DI
6 kW limits for DI
7 Priority

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 287
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.3] System operation – power consumption control


A.6 System operation
1 Auto restart
• [A.6.3.1] = 2: The power limitation depends on 2 Benefit kWh supply
3 Power consumption control
status of relevant digital inputs 4 Average time
5 Ext. amb. sensor offset
• Only if (ref. [A.2.2.7]> Optional demand PCB = 6 forced defrost
A.6.3 Power consumption
Yes) control
1 Mode
• [A.6.3.2] = 0 2 Type
3 Amp value
 Set [A.6.3.5]: Amp value 4 kW value
5 Amp limits for DI
A.6.3.5 Amp limits for DI Range (A) Default (A) 6 kW limits for DI
1 limit DI 1 0~50 50 7 Priority

2 limit DI 2 0~50 50 Linked to [A.6.3.3]


3 limit DI 3 0~50 50
4 limit DI 4 0~50 50

• [A.6.3.2] = 1
 Set [A.6.3.6]: kW value
A.6.3.6 kWlimits for DI Range (kW) Default (kW)
1 limit DI 1 0~20 20
2 limit DI 2 0~20 20 Linked to [A.6.3.4]
3 limit DI 3 0~20 20
4 limit DI 4 0~20 20
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 288
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.3] System operation – power consumption control


A.6 System operation
1 Auto restart
2 Benefit kWh supply
3 Power consumption control
4 Average time
5 Ext. amb. sensor offset
6 forced defrost
A.6.3 Power consumption
control
1 Mode
2 Type
3 Amp value
4 kW value
5 Amp limits for DI
6 kW limits for DI
7 Priority

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 289
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.3] System operation – power consumption control


A.6 System operation
1 Auto restart
2 Benefit kWh supply

• [A.6.3.7] : Priority 3 Power consumption control


4 Average time
5 Ext. amb. sensor offset
• Depends on [A.6.3.1]: Mode: 0 or 1/2 6 forced defrost
A.6.3 Power consumption
control
1 Mode
[A.6.3.1] = 0 Disabled 2 Type
[A.6.3.1] = 1/2 Enabled
• (0) None 3 Amp value
• Not applicable (can only be 4 kW value
• (1) BSH priority (BUH can 5 Amp limits for DI
enabled if no BSH) 6 kW limits for DI
not operate 7 Priority
simultaneously)
• (2) BUH priority (BSH can
not operate
simultaneously)
• Menu item is only
accessible in case of GBS.
If GQI => access via [4-01]

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 290
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.4] System operation – average time


A.6 System operation
1 Auto restart
 Set [A.6.4]: Average time 2 Benefit kWh supply
3 Power consumption control
• (0) No averaging 4 Average time
5 Ext. amb. sensor offset
• (1) 12 6 forced defrost

• (2) 24
• (3) 48
• (4) 72

Reduces influence of quick temperature changes


Is used for:
• Weather depending operation
• Automatic C/H changeover
• Evaluation of [A.3.3.1] & [A.3.3.2] (space heating/cooling OFF
temperature)
During defrost: Ambient temp is frozen (to avoid influence)
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 291
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

[A.6.4] System operation – ext. Amb sensor & defrost


A.6 System operation
1 Auto restart
2 Benefit kWh supply

 Set [A.6.5]: Ext. Ambient sensor offset 3 Power consumption control


4 Average time
5 Ext. amb. sensor offset
• Range: -5~+5°C 6 forced defrost

 Set [A.6.6]: Forced defrost (OK/Cancel)


• Same as a normal defrost
• Possible in both SPH/DHW

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 292
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

5.8. Additional system info

1. BUH operation

2. Defrost operation

3. Control specification (frequency control)

4. Starting control – guard timer

5. Forced operation (emergency)

6. Pump down

7. Thermistors
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 293
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Operation Controls - Back up heater operation


Normal Back up heater operation.
In order to provide bigger heating capacity by low outdoor temperatures the back up heater can / will
provide addittional capacity.

Back up heater permission decision


BUH operation permission/prohibition by Setting [4.00]

Back up heater priority decision


BUH operation priority by Setting [4.01]

BUH operation ON
- BUH permissioned to operate ([4.00] =1)
- Ambient temperature ≤ setting [5.01] equilibrium temperature
& - Request to operate BUH (determined by capacity demand)
- Delay timer of 10 minutes is over (anti recycle timer for BUH:6min)
- [4.01] = 1 AND Booster heater is NOT operating
- Or
- [4.01] = 0

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 294
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Operation Controls - Back up heater operation

BUH will stop operation when one of the below conditions are applicable

BUH operation OFF


- BUH permissioned to operate ([4.00] =0)
- NO Request to operate BUH (determined by capacity demand)
- Ambient temperature > setting [5.01] + 3°C
or - [4.01] = 1 AND Booster heater is operating

Remark The BUH heater will stop immediately by following safety items:
- Low flow signal (ref min flow for BUH)
- Outlet water temperature after BUH higher then 65°C (in DHW: 75°C)
- No return water temperature thermistor abnormality
- Thermal protector of BUH is open

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 295
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Operation Controls - Back up heater operation

Start-up control by space haeting operation.


In order to start up the heat pump in controlled way when low outside air and low water temperature.

Start-up Operation.
BUH operates when:
- Indoor demand operation mode is Heating.
- No defrost operation
& - Inlet water temperature lower then 18°C.

&

- Outlet water temperature after BUH lower then 65°C [Overheat protection temperature].
& - No return water temperature thermistor abnormality [Error code 80 on interface].

- This control overrules the settings [4] & [5].


- BUH forced OFF when Pump OFF

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 296
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Operation Controls - Back up heater operation

Heat exchanger freeze prevention BUH control.


In order to prevent breakage by heat exchanger freeze from defrost (Start-up) operation when low outside
air and low water temperature.

Space heating defrost Operation.


BUH operates when:
- Indoor demand operation mode is Heating(no bivalent)
& - Defrost operation
- Return water temperature below 18°C
&

& - Outlet water temperature after BUH lower then 65°C


- No return water temperature thermistor abnormality [Error code 80 on interface].

- This control overrules the settings [4] & [5].


- BUH forced OFF when Pump OFF

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 297
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Operation Controls - Back up heater operation

BUH protection control.


In order to prevent breakage by BUH.

The BUH heater will stop immediately by following safety items:

- Low Flow signal


- Outlet water temperature after BUH higher then 65°C
- Thermal protector of BUH is open [Error code AA on interface]

Remark (during commissioning )


BUH operates for short periods. Due to remaining air in the piping short ‘no flow’ BUH stops and
delay timer (6min) restarts.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 298
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Defrost conditions (IU)


 Heating or DHW

 Pump runs at maximum speed

 BUH operation depends on BUH thermo on/off status during


heating

 BSH depends on BSH DHW thermo ON/OFF

 Pump keeps turning for 6min when defrost stops

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 299
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control Max. Frequency 011Class (BA)


Heating: 107 Hz (184Hz
Cooling: 123 Hz

Max. Frequency 014 Class (BA)


Heating: 139 Hz
• How to determine the frequency Cooling: 174 Hz

• Frequency command from the hydro-box Max. Frequency 016 Class (BA)
Heating: 155 Hz
• Frequency initial settings Cooling: 194 Hz

• PI control

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 300
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

How to determine the frequency:


The compressor’s frequency will finally be determined by talking
the following steps.

1. Determine command frequency.

2. Determine upper limit frequency.

3. Determine lower limit frequency.

4. Determine prohibited frequency.


􀂊

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 301
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

Determine command frequency :


1. Limiting frequency by drooping function

1. Input current
2. Discharge pipe temperature
3. Low Hz high pressure limit
4. Peak cutting
5. Freeze prevention
6. Fin thermistor temperature

2. Limiting defrost control time

3. Indoor frequency command


􀂊

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 302
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

Determine upper limit frequency :


Set a minimum value as an upper limit for the following conditions:

1. Compressor protection
2. Input current
3. Discharge pipe temperature
4. Low Hertz high pressure
5. Peak cutting
6. Freeze prevention
7. Defrost

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 303
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

Determine lower limit frequency :


Set a maximum value as a lower limit for the following conditions:

1. Four way valve operation


2. Draft prevention
3. Pressure difference upkeep

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 304
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

Determine prohibited frequency :


Some frequencies will be prohibited such as power supply frequency.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 305
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

A => Capacity demand from the hydro-box


The capacity demand of the hydro-box is based on the ΔT
(temperature difference between the Set point and the actual
outlet water temperature or the temperature in the tank).

B=> The target evaporation / condensation temperature


The target Te / Tc will be determined by the Set piont
and the hydro-box ΔT.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 306
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Control specification - Frequency control

The target operation compressor frequency


The target operation compressor frequency is controlled in
order to keep a constant Te / Tc during cooling / heating
operation.

The compressor frequency


In case other controls are activated (eg start up, discharge
pipe control,…) an other compressor frequency can be used
as the initial target operation compressor frequency.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 307
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Starting Control - GQI

Initial start-up parameters for the different accurators.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 308
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Guard timer after compressor OFF

3/5 minutes anti-recycling guard timer for GBS/GQI


=> Pressure equalisation/prevent frequent on/off

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 309
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Defrost control - GQI

Defrost Condition ON

Defrost Upper limit A:


- Outdoor temperature > - 5°C : 2 hours
- Outdoor temperature ≤ - 5°C : 2~6 hours

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 310
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Defrost control - GQI

Defrost Condition ON

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 311
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Defrost control - GQI

Defrost Condition OFF

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 312
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Forced Operating mode (Emergency operation)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 313
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Forced Operating mode (Emergency operation)


• In cooling, the unit runs for 20 minutes and then stops for 10 minutes
in order to avoid freeze-up of the indoor coil

• In heating, defrost is activated for 3 minutes once every hour.

• Change position of the emergency switch only when the power is


turned off.

• Emergency operation by outdoor unit will only operate in case a


malfunction is applicable.

• Broken outdoor unit/no outdoor connected


• Hydro-box will go automatically in emergency operation
• Only BUH and BSH

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 314
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Pump Down - GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 315
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Pump Down - GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 316
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Pump Down - GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 317
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R1T: Outdoor temperature

R1T R1T
Cooling
•Inverter current protection control

Heating
•Inverter current protection control
•Defrost control

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 318
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R2T: Discharge pipe temperature

R1T R2T
Cooling
•Discharge superheat control
•Expansion valve control
•Crankcase heater

Heating
•Expansion valve control
R2T
•Crankcase heater

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 319
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R3T: Suction pipe temperature

R1T R3T
Cooling
•Expansion valve control (SH control)

Heating
•Expansion valve control (SH control)
•Suction pipe superheat protection
control
R3T R2T

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 320
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R4T: Outdoor heat exchanger temperature

R1T R4T
Cooling
•Inverter current protection control

R4T
Heating
•Inverter current protection control
•Defrost control

R3T R2T

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 321
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R5T: Outdoor heat exchanger middle temperature

R1T R5T
Cooling
R5T •Calculate the expected high pressure.
•Outdoor fan speed control
R4T

R3T R2T

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 322
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R6T: Liquid refrigerant temperature

R1T R6T
Cooling
R5T •Calculate the subcool.
•Expansion valve control ?
R4T

R6T R3T R2T

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 323
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

R10T: Inverter power module temperature

R1T R10T
Cooling
R5T •Outdoor fan speed control
•Inverter fin temperature control
R4T
•Pressure difference control

Heating
•Inverter fin temperature control
R6T R3T R2T

Thermistor R10T is located in the switch


box.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 324
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 325
All Seasons

°
CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
6. Commisioning and test run

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6. Commissioning & testrun: Overview


1. Site requirements: OU

2. Installation attention: IU

3. Installation attention: general

4. Installation attention: water circuit

5. Installation attention: electrical wiring

6. Commissioning

7. Handover to enduser

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 327
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• Minimum installation spacing (mind outlet & inlet air) GBS

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 328
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 329
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 330
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 331
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU

• If outlet is directly exposed to wind, install baffle plate

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 332
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• Prevent snow from covering the unit or touching the heat
exchanger

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 333
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• Underground must be strong and level to prevent vibration
noise
• In case of risk of snowfall, install on pedestal with minimum
height of snowfall

Fixation feet delivered with GBS unit

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 334
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• To ensure minimum spacing of 15cm below bottom plate for
snowfall, use the EKFT optional U-beams (GBS)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 335
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• GBS Mounting on the wall
(advised to use the option kit)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 336
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• Optional drain pan can be installed EKDP008CA for GBS

GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 337
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU


• Optional drain pan can be installed EKDP008CA for GBS

GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 338
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU GBS


• Fixation feet for mounting OU

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 339
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU: GBS


• Mount optional U-beams in line with supporting structure
• Mount fixation close to end (to prevent snow build up reaching
the coil)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 340
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU GBS


Slide unit all the way (fixation feet should
be hidden under the coil)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 341
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU GBS


• If unit is slided to the back, fix the position by bolting the front

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 342
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.1. Site requirements: OU GQI thermistor

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 343
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.2. Installation attention: IU

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 344
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.2. Installation attention: IU


• Transportation stays have to be removed (integr)
• Unit weight 120kg (integrt) / 60kg (wall hung)!

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 345
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.2. Installation attention: IU


• Required space

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 346
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.2. Installation attention: IU


• Level the unit

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 347
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.2. Installation attention: IU


Location requirements:

• Ambient temperature around the indoor unit should be >5°C.

• Indoor installation only: ambient temperatures ranging


5~35°C in cooling mode and 5~30°C in heating mode.

• Do NOT install the unit in sound sensitive areas (e.g. near a


bedroom)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 348
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• NEVER install a drier in the R410A unit (drying material may
dissolve and cause damage)

• Protect the piping to prevent dirt, liquid or dust from entering


the piping

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 349
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• First check refrigerant piping, only then open stop valve
• Flare connections:
• Coat the flare inner surface with ether oil or ester oil

• Tighten 3 or 4 turns by hand, before tightening firmly.


• Always use two wrenches together when loosening a flare nut.
• Always use a spanner and torque wrench together to tighten the
flare nut

• Use the flare nuts that are delivered with the unit
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 350
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• Brazing

• Always braze with nitrogen (20kP)

• Do NOT use anti-oxidants when brazing pipe joints.

• Do NOT use flux when brazing copper-to-copper refrigerant piping. Use


phosphor copper brazing filler alloy (BCuP), which does not require
flux.a)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 351
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


Service ports: factory closed

• Stem cap: handle with care and close afterwards


• Service port: schrader
Check for leaks after closing

If low operating pressure possible


(cooling while low ambient):
Sufficiently seal the flare nut in the
stop valve on the gas line with
silicon sealant to prevent freezing.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 352
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• Use polyethylene foam as insulation
material: Heat transfer rate between 0.041 and
0.052 W/mK (0.035 and 0.045 kcal/mh°C)

• Temperature >30°C & humidity>80%


than RH 80% => thickness of the sealing
> 20 mm in order to avoid condensation
on the surface of the sealing.

• Be sure to insulate the liquid and gas-side


field piping.

(The highest temperature that the gas-side piping can


reach is around 120°C (GQI) / 110°C (GBS) , so be
sure to use insulating material which is
very resistant.)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 353
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general

GBS GQI

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 354
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• Indoor wall hung/integrated

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 355
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• Recommended to run field piping through duct or wrap in insulation

• If possible that small animals enter the system through the knockout
holes, plug the holes with packing materials (field supplied).

• To prevent short circuit In cold climates, seal knockout holes to avoid


enterance of snow and humidity

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 356
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


Do NOT exceed the maximum operation pressure of 4000 kPa
(40 bar).
Only use recommended bubble test solution.

1. Charge the system with nitrogen gas up to a gauge pressure


of at least 200 kPa (2 bar).

2. Check for leaks by applying the bubble test solution to all


connections.

3. Discharge all nitrogen gas.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 357
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


Use a 2-stage vacuum pump with a non-return valve which can
evacuate to a gauge pressure of -100.7kPa
1. Connect the vacuum pump to the service port of the: gas side
(GBS) / both liquid and gas (GQI)

2. Evacuate to a gauge pressure of –100.7 kPa After turning OFF


the pump, check the pressure for at least 1 minute. If the
pressure increases, this indicates the presence of moisture or
leaking from connection parts. Perform vacuum drying to fix
All Seasonsthis.
°
CLIMATE COMFORT V. Eylenbosch 30 March 2018 358
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


Use a 2-stage vacuum pump with a non-return valve which can
evacuate to a gauge pressure of -100.7kPa
1. Evacuate for at least 2 hours to a pressure on the manifold of
–0.1 MPa (–1 bar).
2. After turning OFF the pump, check the pressure for at least 1
hour.
3. If you do NOT reach the target vacuum or cannot maintain the
vacuum for 1 hour, do the following:
4. Check for leaks again.
5. Perform vacuum drying again.
After opening stop valve, it is possible that pressure in refrigerant piping does
not rise. This might be caused by e.g. closed state of expansion valve in
outdoor circuit, but does not present any problem for correct operation of unit

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 359
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• Shut off valves for SPH/C circuit are supplied with unit
• Also advised to install shut off valves on DHW circuit

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 360
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.3. Installation attention: general


• A drain device and pressure relief device should be
installed on the cold water inlet connection of the domestic hot
water cylinder.
• Recommended to install the pressure relief valve on higher position as
top of the domestic hot water
• To avoid back siphonage, it is recommended to install a
non-return valve on the water inlet of the domestic hot
water tank in accordance with the applicable legislation.
• It is recommended to install a pressure reducing valve on
the cold water inlet in accordance with the applicable
legislation.
• An expansion vessel should be installed on the cold water
inlet in accordance with the applicable legislation.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 361
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit


• Connect the pressure relief valve outlet to a drain

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 362
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit


• Provide drain taps at all low points of the system in order to
allow complete drainage of the water circuit.

• Provide air vents at all high points of the system

• Never use Zn-coated parts in the water circuit. Because the


unit's internal water circuit uses copper piping, excessive
corrosion may occur.

• Use appropriate tooling

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 363
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit

• Recommended to install an additional filter on the


heating water circuit. Especially to remove metallic particles from the
filed heating piping, it is advised to use a magnetic or cyclone filter
(Small particles may damage the unit and will NOT be removed by
the standard filter of the heat pump system)

If air, moisture or dust gets into the water circuit,


problems may occur. To prevent this:
1. ■Only use clean pipes
2. ■Hold the pipe end downwards when removing burrs.

3. ■Cover the pipe end when inserting it through a wall, to prevent dust

and/or particles entering the pipe.


4. ■Use a decent thread sealant to seal connections.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 364
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit


• Immediately after installation, the domestic hot water tank must be
flushed with fresh water. This procedure must be repeated at least
once a day the first 5 consecutive days after installation so a passive
layer can be formed on the inside of the tank (weldings).

• Insulate water piping to prevent condensation during cooling


operation and reduction of the heating and cooling capacity.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 365
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit


GQI min vol: 20l
!!! Caution !!! GBS min vol: 10l
The minimum water volume of the system is the available water
volume in the most critical situation (WITHOUT indoor)
The most critical situation in this type In this type of installation, the minimum water
of installation is in case all valve are volume is equal to the total system water
closed. Available water volume is only volume.
field piping volume

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 366
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit


Check the maximum water volume according to the
pressure of the expansion vessel

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 367
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit

• Set the pre pressure correctly: Pg=(H/10+0.3) bar

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 368
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.4. Installation attention: water circuit


Charging
• Make sure the auto air purge is at least 2 turns open
• Fill the system until +-2bar
• During filling, purge the air as much as possible

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 369
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.5. Installation attention: electrical wiring

• If stranded conductor wires are being used, install a round


crimp-style terminal on the tip

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 370
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning
• During the first running period of the unit, the required power
may be higher that stated on the nameplate of the unit.
This phenomenon originates from the compressor that needs elapse
of a 50 hours run in period before reaching smooth operation and
stable power consumption.

• Before startup, the installation must be powered for at least 2


(GBS) / 6 (GQI) hours to allow the cranckcase heater to
operate.
GBS does not have a crankcase heater, one of the compressor windings is
used to keep the compressor warm.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 371
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning
1. Checking the "Checklist before test run".

2. Performing an air purge.

3. Performing a test run for the system.

4. If necessary, performing a test run for one or more actuators.

5. If necessary, performing an underfloor heating screed dryout.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 372
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning
• Verify everything is according to the checklist before operating
the unit

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 373
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning
A Installer settings A.7 Commissioning A.7.1 Test run
1 Language 1 Test run 1 Heating test run
2 System layout 2 UFH screed dryout 2 Cooling test run
3 Space operation 3 Air purge 3 Tank test run
4 Domestic hot water 4 Actuator test run
5 Heat source A.7.2 UFH screed dryout
6 System operation 1 Set dryout program
7 Commissioning 2 Start dryout
8 Overview settings 3 Dryout status

A.7.3 Air purge


1 Mode
2 Speed
3 Circuit
4 Start air purge

A.7.4 Actuator test run


1 BSH
2 BUH 1
3 BUH 2
6 Pump
7 Solar pump
8 2 way valve
9 3 way valve
A BPH
B Bivalent
C Alarm
D C/H signal
E Quick heatup
F Circulation pump

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 374
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: airpurge


• Perform an air purge via the commissioning menu.
• Attention: Unit must be ‘OFF’

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 375
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: airpurge A.7 Commissioning


1 Test run
2 UFH screed dryout
3 Air purge

 Set [A.7.3]: Air purge mode: Manual / Automatic 4 Actuator test run
A.7.3 Air purge
1 Mode
2 Speed
3 Circuit
Manual mode Automatic 4 Start air purge

 Set speed: Low/High • Speed and circuit is automatic


 Set circuit: Space/DHW • Changeover: 6min low speed ->
• Start air purge 1min stop -> 6min high speed
• Test screen is displayed • If tank installed: switchover 3-way
• Ends after 28min or by pressing valve each 3min
ON/OFF button and confirming • Ends after 28min or by pressing
ON/OFF button and confirming
6m high

Pump 6m low
operation 1m 1m 6m low …
off off

28min
3-Way valve
DHW 3m 3m
SP …
3m 3m 3m
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 376
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: testrun A.7 Commissioning


1 Test run
2 UFH screed dryout
3 Air purge

 Select and start test run in [A.7.1] 4 Actuator test run


A.7.1 Test run
1 Heating test run
2 Cooling test run
3 Tank test run
• Test screen is shown

• Test run automatically ends after 30min

• To end manually press ON/OFF button and confirm

• During test => only menu [6] Information is accessible: sensor


info & actuator info

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 377
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: actuator test run


Confirm operation of the actuators via the commissioning menu
(ref to system operation chapter)
• Booster heater test
• Backup heater (step 1) test
• Backup heater (step 2) test
• Pump test
• Solar pump test
• 2-way valve test
• 3-way valve test
• Bottom plate heater test
• Bivalent signal test
• Alarm output test
• Cooling/heating signal test
• Quick heatup test
• Circulation pump test
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 378
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: actuator test run A.7 Commissioning


1 Test run
2 UFH screed dryout
3 Air purge
 Select and start actuator run in [A.7.1.4] 4 Actuator test run
A.7.4 Actuator test
• Displays test screen Test run stops: run
1 BSH
• After 30min 2 BUH 1
• Manually by pushing ON/OFF button and confirming 3 BUH 2
6 Pump
• When reaching stop condition 7 Solar pump
8 2 way valve
9 3 way valve
A BPH
• BSH: Start: tank temp < 40°C. Stop: 50°C B Bivalent
C Alarm
D C/H signal
E Quick heatup
• BUH: Start: LWT<30°C. Stop LWT>40°C F Circulation pump

• Pump: Maximum speed

• Solar pump: Start: tank temp < 40°C. Stop: 50°C

• Bivalent: Bivalent permission: ON & 3-way valve to DHW


All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 379
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: screed dry-out


• The installer is responsible to:
• Contact the screed manufacturer for the initial heating instructions to
avoid cracking the screed,
• Program the under floor heating screed dry out schedule according to
the above instruction of the screed manufacturer,
• Check on regular base the good working of the setup,
• Select the correct program that complies with the type of used screed for
the floor.

• Screed dry out function is possible by BUH only (if no OU yet


installed)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 380
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: screed dry-out A.7 Commissioning


1 Test run
2 UFH screed dryout
3 Air purge

 Set and start dryout in [A.7.2] 4 Actuator test run


A.7.2 UFH screed

• 20 steps duration 1~72 hours, steps of 1hr dryout


1 Set dryout program
2 Start dryout
• LWT default temp: 25 3 Dryout status

• Prefferential kWh rate power supply must be disabled before starting!


(A.2.1.6)
• During operation: Status screen shown with: current step, total remaining
time and active LWT setpoint
• If finished: home screen returns to normal and A.7.2.3 Dryout
status=finished
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 381
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: screed dry-out A.7 Commissioning


1 Test run
2 UFH screed dryout
3 Air purge
• Dryout status can be consulted: Not started/busy at step 4 Actuator test run
A.7.2 UFH screed
xx/stopped (if stopped before finishing)/finished dryout
1 Set dryout program
2 Start dryout
3 Dryout status

Manual stop Stop due to error


• ON/OFF button + • If warning/caution: dryout can continue
confirmation after error reset
• Jumps back to • If error: after error is reset => U3 is shown
dryout menu • U3 error can only be reset while installer
level!
• If power reset => U3

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 382
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.6. Commissioning: screed dry-out A.7 Commissioning


1 Test run
2 UFH screed dryout
3 Air purge

• Extra specific setting F-05: 0 / 1 4 Actuator test run


A.7.2 UFH screed
dryout
1 Set dryout program
2 Start dryout
Time based (default) Time and temperature 3 Dryout status

• The dryout program is executed based A Installer settings


1 Language
according to the programmed • The time starts running 2 System layout
3 Space operation
time only if LWT is above 4 Domestic hot water
setpoint 5 Heat source
6 System operation
7 Commissioning
8 Overview settings

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 383
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

6.7. Handover to enduser


Once the test run is finished and the unit operates properly,
please make sure the following is clear for the user:

• Fill in the installer setting table (in the operation manual) with the actual settings.

• Make sure that the user has the CD and the printed documentation and ask him/her to
keep it for future reference.

• Explain the user how to properly operate the system and what he/she has to do in
case of problems.

• Show the user what jobs he/she has to do in relation to maintenance of the unit.

• Explain the user about energy saving tips as described in the operation manual.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 384
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 385
All Seasons

°
CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
7. Maintenance

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maintenance
Check the following at least once a year:
• Water pressure
• Check whether the water pressure is above 1 bar. If it is lower, add
water.
• Water filter
• Handle the water filter with care. Do NOT use excessive force when you
reinsert the water filter so as NOT to damage the water filter mesh.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 387
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maintenance
Water pressure relief valve

• Open the valve and check the correct operation. Water may be very
hot!
• Water flow coming from the relief valve (on the tank if applicable) is high
enough, no blockage of the valve or in between piping is suspected.
• Water coming out from the relief valve and contains debris or dirt:
• Open the valve untill the discharged water does not contain dirt anymore flush
the system and install an additional water filter (a magnectic cyclone filter is
preferably).
• To make sure this water originates from the tank, check after a tank heat
up cycle.
• It is recommended to do this maintenance more frequently.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 388
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maintenance
• Relief valve hose
• Check whether the pressure relief valve hose is positioned appropriately to drain
the water

• Switch box
• Using an ohmmeter, check for correct operation of contactors K1M, K2M, K3M
and K5M (depending on your installation). All contacts of these contactors must
be in open position when the power is turned OFF.
• Carry out a thorough visual inspection of the switch box and look for obvious
defects such as loose connections or defective wiring

• Descaling
• Depending on water quality and set temperature, scale can deposit on the heat
exchanger inside the domestic hot water tank and can restrict heat transfer. For
this reason, descaling of the heat exchanger may be required at certain intervals.
• Chemical disinfection

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 389
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Maintenance
• Chemical disinfection

• If the applicable legislation requires a chemical disinfection in specific


situations, involving the domestic hot water tank, please be aware that
the domestic hot water tank is a stainless steel cylinder containing an
aluminium anode. We recommend to use a non-chloride based
disinfectant approved for use with water intended for human
consumption.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 390
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Overview
1. Introduction

2. System build up

3. Equipment selection

4. System operation

5. Fieldsettings

6. Commissioning and test run

7. Maintenance

8. Troubleshooting
All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 391
All Seasons

°
CLIMATE COMFORT
Heating

Air Conditioning

S-XAM08 Altherma LT CA Applied Systems

Refrigeration
8. Troubleshooting

TOP SECRET
SECRET
INTERNAL USE ONLY
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8. Troubleshooting: Overview
1. Troubleshooting: Error codes

2. Troubleshooting: Warnings/cautions

3. Troubleshooting: How to reset

4. Service tool: Inverter checker RSUK09-17

5. Service tool: Dchecker

6. Spare part pcb

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 393
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.1. Troubleshooting: Error codes


• If error happens => error screen immediately shown: Error code+detailed
error code (in case of multiple error, highest rank is shown).

• Some errors can only be reset when in installer level

• Homescreen: information symbol is flashing as long as error is active

• ON/OFF during error screen has no function

• Error is saved in Error History [6.3.1]:

• LED is flashing during error, if back to home scree => not flasing anymore
• Flashes during error screen
• Doesn’t flash during homescreen (only I symbol is displayed)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 394
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.2. Troubleshooting: Warnings/cautions


• Error screen is not displayed immediately (e.g. “AH” unfinished
disinfection)

• If info button is pushed: show


• Error code + detail , unit number, description, OK button not visible to
reset abnormality

• On the home screen the information symbol is flashing as long


as there’s a warning (on/off etc still works)

• Warning is not saved in to history (except for exceptions in


error list)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 395
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.3. Troubleshooting: How to reset


• All functionality must be off (DHW, Space, LWT)

• If power reset necesssary => remocon reset has no meaning

• If error is reset by hydrobox => disappears on remocon

• Press “OK” in error screen after cause has been cleared to


reset the error

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 396
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.4. Inverter checker RSUK09-17: index


• Outlook

• How to connect?

• How to use?

• Diagnosis

• Caution

• How to disconnect?

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 397
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Outlook

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 398
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

How to connect?
Turn the power off before connecting the inverter checker

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 399
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

How to use on Daikin Altherma GQI


1. Power on
2. Wait until initialisation is
finished
3. Activate setting
4. Start operation on
remocon

For LT -> press 2x BS2


For HT -> press 28x BS2

At the status shown in 6) , outdoor unit will run in power transistor check mode after the remocon has been switched on

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 400
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Diagnosis

Easy to use checker for inverter


PCB function 6 LED’s

Connected to
compressor U-V-W

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 401
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Diagnosis

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 402
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

Caution
1. When the output frequency is low, the LED flashes slowly. As
the frequency increases, the LED flashes quickly. (It looks like
the LED is lit)

2. Wait until the system has initialised before activating the


“power transistor check” operation

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 403
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

How to disconnect on Daikin Altherma


1. Press BS1 once and switch the unit off on the remocon.
2. The LED’s will stop flashing (if necessary set setting back in
OFF condition)
3. Wait approx. 10 seconds and then 2 LED’s will lit up, this is
for unloading the capacitors of the inverter (+/- 500 VDC)

4. It is safe to disconnect the inverter checker once the LED’s


are off.
5. Press mode again to go to normal operation.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 404
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.5. Service tool: NEW D-checker


Demo (final version not available yet)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 405
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.5. Service tool: NEW D-checker


Demo (final version not
available yet)

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 406
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.6. Replacement by spare Part pcb


There are 2 different spare part pcb’s for the indoor LT-CA:

1. for the 004 class (dedicated flowsensor)


2. for the other classes (same flowsensor)

Together with the spare part, there is an instruction delivered


with settings that need to be done in order to set the spare part
for the correct indoor unit.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 407
TOP SECRET
SECRET
INTERNAL USE ONLY
PUBLIC

8.6. Replacement by spare Part pcb


Attention! Replacing the indoor pcb or remocon or both might
mean that all fieldsettings are reset to factory setting.
Therefore, it is advised to take pictures of the 15 screens in
overview settings.

When pcb is replaced and spare part settings are done, you can
check the overview settings again and correct them back to
previous fieldsettings as desired.

All Seasons °
CLIMATE COMFORT V. Eylenbosch 30 March 2018 408