Você está na página 1de 38

Co-ordination of LV Protection

Devices

E58640

DBTP107PRE-En-07/00
Contents

 Operator needs
Availability of electrical energy 3
 Co-ordination of LV protection devices 8
 Co-ordination techniques 12
o The IEC 60947-2 standard 12
o Discrimination techniques 16
o Limitation 21
o Cascading 23
 Schneider solutions 24
o Masterpact and the incoming end of the installation 25
o Compact NS and power distribution 30
o Multi 9 circuit-breaker and final distribution 33
o Discrimination rules for 1 to 6300 A 34
 Conclusion 35

DBTP107PRE-En-07/00 2
From one application to another
operator needs are the same

61343

60803
85293

…The availability of electrical energy...

DBTP107PRE-En-07/00 3
The availability of electrical energy

 Savings for the operator through:


o the continuity of electrical supply
o the optimised cost of his installation

63647-7
62242

61485

60632
…A source of profit for the operator...

DBTP107PRE-En-07/00 4
Availability of electrical energy
and the LV protection plan
Structure of LV Distribution

Level 1 General LV
= incomer Switchboard

Level 2
= MSB
feeders

Distribution
Level 3 Switchboard
= power or
distribution motor
control

Level 4 Final
= final distribution switchboards
distribution

E62649
Loads

DBTP107PRE-En-07/00 5
Availability of electrical energy
and the LV protection plan
Structure of LV Distribution

 Installation design
o priority / non priority feeders

 Protection of LV distribution
o level 1 and 2: using Air Circuit-Breaker (ACB) or
Moulded Case Circuit-Breaker (MCCB) with high rating
800 to 6300 A
o level 3: using LV industrial Fuse or Moulded Case Circuit-Breaker (MCCB)
63 to 1250 A
o level 4: using Miniature Circuit-Breaker (MCB)
1 to 100 A

DBTP107PRE-En-07/00 6
Availability of electrical energy
and the LV protection plan

Continuity of Cost of the


Customer needs electrical electrical
energy supply installation

Co-ordination of
Protection Plan protection devices:
discrimination,
cascading
& constraint limitation

DBTP107PRE-En-07/00 7
LV co-ordination techniques

 Optimising LV electrical distribution through 3 actions at the Protection


Plan Level

o 1) discrimination to guarantee continuity of supply

o 2) limitation to reduce constraints

o 3) cascading to optimise performances

DBTP107PRE-En-07/00 8
Co-ordination of protection devices
1) discrimination
 Whatever the fault:
o overload
A
o short-circuit
o insulation fault
only the circuit-breaker located just upstream from the fault trips
B C
 4 types of discrimination
o current
E41139

o time
o energy
o logic

DBTP107PRE-En-07/00 9
Co-ordination of protection devices
2) limitation
 Technique that allow for the harmful effects of short-circuit currents
to be diminished

 Limitation reduces effects of the following type:


o electromagnetic: reduction in EMC disturbances
o mechanical: reduction of deformation and/or breaks
o thermal: rise in the life span of trunkings

Isc I2sc
 A2
Isc presumed 100 %
100 % Presumed
transient peak energy
Isc presumed 100 %
steady peak

Isc limited peak

10 % Limited
1% energy

E62651
E62650

<1%
t t
tsc

DBTP107PRE-En-07/00 10
Co-ordination of protection devices
3) cascading
 The limiting upstream circuit-breaker helps the downstream
circuit-breakers to open
 Technique that allows for the cost of LV electrical distribution
to be optimised

Non priority
feeder
E62667

DBTP107PRE-En-07/00 11
The IEC 60947-2 standard
and co-ordination of protection devices
 Recognises the 2 co-ordination elements (appendix A)
o discrimination
o cascading

 Defines testing to guarantee this co-ordination


 Characterises the circuit-breakers capable of time discrimination
o utilisation category B
E55229

DBTP107PRE-En-07/00 12
The IEC 60947-2 standard appendix A
discrimination
 Definition of the discrimination limit Is

E62653
 Tests to be conducted

E62654
DBTP107PRE-En-07/00 13
The IEC 60947-2 standard appendix A
cascading
 Definition of the current IB and of the reinforced breaking capacity IcuD2+D1
E62680
 Tests to be conducted

E62681
DBTP107PRE-En-07/00 14
The IEC 60947-2 standard
category B circuit-breakers
 They ensure time discrimination that is characterised by Icw during Dt
o Icw must be at least equal to 12 In or 5 kA for In  2500 A
30 kA for In > 2500 A
o Dt - standardised delay - of: 0.05 - 0.1 - 0.25 - 0.5 - or 1 s
 They are subjected to additional testing
E62652

DBTP107PRE-En-07/00 15
LV discrimination techniques

 Quality of discrimination
Comparison of the discrimination limit Is to the
presumed short-circuit current Isc determines the quality of discrimination

o total discrimination: Is > Isc

o partial discrimination: Is < Isc

E62682
only D2 trips D1 and D2 trip

o if the discrimination limit is equal to the Icu of the upstream circuit-breaker


discrimination is total

DBTP107PRE-En-07/00 16
Current discrimination

 Linked to the natural staging of Long Delay curves of the association


o discrimination limit Is = Isd1
E62655

o discrimination technique generally used in Final Distribution

DBTP107PRE-En-07/00 17
Time discrimination

 Time delay Dt of the upstream circuit-breaker’s Short Delay CR tripping


o extension of current safety
E62683 o discrimination limit Is = Ii1 (= Icw1)

o discrimination technique generally used on the incoming end of the installation


the upstream circuit-breaker is from category B with a high EDW (Icw1 = Icu1)

DBTP107PRE-En-07/00 18
Energy discrimination

 Comparison of energy curves (tripping D downstream/non


tripping ND upstream) allows for the discrimination limit Is to be determined

D
Tripping

ND
Non
tripping
E62656

E68104
 Only the manufacturer can guarantee the quality of discrimination
of the energy type

DBTP107PRE-En-07/00 19
Logic discrimination (ZSI)

 Circuit-breakers fitted out with electronic trip units


o a pilot wire between upstream / downstream circuit-breakers
E62659
o no threshold rules

 This technique
o is easily implemented
o reduces to a minimum constraints from delayed tripping of time discrimination

DBTP107PRE-En-07/00 20
Limitation

 Technique consists in using the arc voltage


to limit short-circuit currents I asymetric
peak

 3 criteria to be considered Isc

IL
o early o fast o high

early fast high

E62660
E68105

 Technique that has multiple advantages


o limitation of constraints on the installation
o better discrimination
o circuit-breaker cascading

DBTP107PRE-En-07/00 21
Improving discrimination through limitation

 The use of a limiting downstream circuit-breaker extends current


and/or time discrimination with the upstream circuit-breaker
Isc
in D2 D2
non limiting

D2
Is limiting
E62657

Is Is Isc (D2)
D2 non limiting D2 limiting presumed

 The downstream circuit-breaker by limiting the fault current Id increases


the discrimination limit Is

DBTP107PRE-En-07/00 22
Cascading

 The use of a limiting upstream circuit-breaker “increases” the breaking


capacity of the downstream circuit-breaker
E62661

E62662
 Technique that allows for the installation of a limiting circuit-breaker
downstream from circuit-breakers with optimised Breaking Capacities

DBTP107PRE-En-07/00 23
Schneider solutions

Continuity of Cost of the


Customer needs
electrical electrical
energy supply installation

Totally co-ordonated Constraint


Schneider protection Discrimination as a Limitation
devices standard in the Economical association
circuit-breaker ranges of circuit-breakers
through Cascading

DBTP107PRE-En-07/00 24
Masterpact power circuit-breakers

 Discrimination upstream: setting


the long delay (LR) slope (IDMTL)
allows for better discrimination

 Discrimination downstream:
o better time discrimination
thanks to higher Icw
o on very high Isc (up to 150 kA),
maintains a high level
of discrimination

 Limitation of very high constraints

E62663
Masterpact offers unequalled performances as a standard
for all applications

DBTP107PRE-En-07/00 25
Improving MV/LV discrimination thanks to IDMTL
curves
 5 suggested slopes:
HVF curve
o DT: definite time tr = 2 s

o SIT: inverse standard time MV Fuse 80 A


brought to LV
I2t curve
o VIT: very inverse time tr = 12 s
o EIT: extremely inverse time
o HVF: HV compatible fuse Short delay
threshold = 4 Ir

E62664
DBTP107PRE-En-07/00 26
Ensuring total time discrimination
as a standard
 Time discrimination with very high Icw (up to 85 kA 1s) thanks to:
o a globally reinforced mechanism, enclosure, copper parts
o the use of air CTs for measurement
63047-7

Accuracy zone of the


instantaneous
tripping threshold
E62675

(± 10 %)

Maximum time discrimination


NW H2
E62676

Icw = thermal withstand = self-protection DIN threshold

DBTP107PRE-En-07/00 27
Increasing the breaking capacity without
sacrificing discrimination
 Conciliate high breaking capacity (150 kA) and high Icw (65 kA -1s)
 Disengagement
Half moon actvating
the pole shaft

Effort sensor
61343

Kinematic chain
E62665
E68106

DBTP107PRE-En-07/00 28
Limiting as much as possible the constraints on
the incoming end of the installation
 Limitation
o using disengagement for very fast breaking
o modification of the fixed pole to increase the repulsion force
Breaking chamber
Presumed
short-circuit
current
E68106

Magnetic U Limited
current

Total breaking time

U-shaped
current loop
E62666

E62678
Intervention time

 Time discrimination up to 37 kA
Unequalled performances for a limiting circuit-breaker

DBTP107PRE-En-07/00 29
Compact NS power distribution

 New breaking technology


o roto-active breaking
o pressure (“reflex” tripping)
Fixed
contact Short-circuit
current

Breaking
Arc chamber Piston
053100

Mobile
Breaking
contact
enclosure

Arc

E62670
Breaking
chamber Fixed
contact 

E62669
E62669

Breaking chamber

o

o
 Provides an exceptional limiting capacity

DBTP107PRE-En-07/00 30
Natural discrimination

 Compact NS circuit-breakers have natural discrimination performances


o current and/or time tripping curves
o natural discrimination energy curves
053100

E62672
E62671

DBTP107PRE-En-07/00 31
Simultaneous discrimination and cascading

 Compact NS circuit-breakers have natural


Cascading performances
o reflex tripping (piston)
D1

 Reinforced Breaking Capacity


without loss of Discrimination
053100

D2

E62673
DBTP107PRE-En-07/00 32
Final distribution
Multi 9 circuit-breakers
 Technology with magnetic actuator
031887

E62674

 Guaranteed performances
o ultra rapid breaking
o exceptional limitation
o total discrimination with circuit-breakers located upstream

DBTP107PRE-En-07/00 33
Schneider discrimination rules

 Masterpact
o total discrimination with Compact NS (<630 A) circuit-breakers located
downstream

 Compact NS
o total discrimination as soon as the ratio between ratings is greater than 2.5

Note: it is necessary to conserve current and time threshold staging

The Schneider solution ensures total natural discrimination


from 1 to 6300 A

DBTP107PRE-En-07/00 34
The Schneider solution: mastering the technique

 Continuity of supply thanks to total discrimination

CA

Recording
box

production
Compact NS
1 to 160 A

Factory assembly line

E62679
DBTP107PRE-En-07/00 35
The Schneider solution: mastering the financial
aspect
 Upon installation
 During operation
Thanks to the quality of limitation of these circuit-breaker ranges
E43480

E43481
DBTP107PRE-En-07/00 36
The Schneider solution: mastering services

 Simple and high-performance tools


E43478

o software: Ecodial 3
o catalogue: Exhaustive choice table

E43477
E43476

LV Catalogue

DBTP107PRE-En-07/00 37
“No one in the world does more with electricity”

Schneider offers circuit-breaker ranges


from 1 to 6300 A with unequalled performances

 Standards are respected

CT150fi
 Performance of co-ordinations:
o discrimination as a standard
o highly economical cascading
E68107

056409

053100
 Simple and high-performance catalogues
and software

031887
Schneider guarantees a safe and high-
performance electrical installation for
mastering the LV protection plan

E62677