Teleprotection - Contents
ABB Automation
Utility Communication Systems
CHPAU NKT F 2
Teleprotection - Introduction
• What is it ?
-> Tele-Communication + Protection - Signalling
• Where is it used ?
-> Mainly at the higher and highest voltage levels
• Why is it used ?
-> Clearance of faults within the shortest possible time
ABB Automation
Utility Communication Systems
CHPAU NKT F 3
TPS Standards and Publications
IEC standards:
IEC 60834-1 Teleprotection equipment of power systems - Performance and testing
Part 1: Narrow-band systems (First edition, 1988)
Part 1: Command systems (Second edition, 1999)
IEC 60834-2 Performance and testing of teleprotection equipment of power systems
Part 2: Analogue comparison systems (First Edition 1993)
CIGRE publications:
"Teleprotection Guide", Study Committees 34 + 35, Joint Working Group on
Teleprotection, 1969;
Revised Version "Protection Systems Using Telecommunication", 1985
Revised Version "Protection Using Telecommunications", 2000 (in preparation)
ABB Automation
Utility Communication Systems
CHPAU NKT F 4
Protection System Architecture
Substation A Substation B
HV-line
Tele- Tele-
Protection Physical Protection
protection protection
Relay Link Relay
Equipment Equipment
Telecommunication
System
Teleprotection System
Protection System
ABB Automation
Utility Communication Systems
CHPAU NKT F 5
Protection Signal Transmission
Type of Information:
• Continuous signals
• Magnitude and/or phase of power frequency currents
ABB Automation
Utility Communication Systems
CHPAU NKT F 6
Protection Systems
Protection system based on:
Signal-transmission Signal-transmission
not required required
conditionally selective
ABB Automation
Utility Communication Systems
CHPAU NKT F 7
Signal Transmission for Line Protection
commands
ABB Automation
Utility Communication Systems
CHPAU NKT F 8
Distance Protection
Typical stepped distance/time characteristics
Operating Time
ZONE 3
TA3
ZONE 2
A B TB2 C
ZONE 1 TA2
RA RB RC
TA1 TB1
Distance
A, B, C Stations
RA,RB, RC Protection Relay
TA1, TA2, TA3 Operating Times, Relay A
TB1, TB2, TB3 Operating Times, Relay B
ABB Automation
Utility Communication Systems
CHPAU NKT F 9
Distance Line Protection
Permissive Underreach Transferred Tripping (PUTT)
B LBC C
F
BC1
RBC
RCB
CB1
L
NSD NSD
ABB Automation
Utility Communication Systems
CHPAU NKT F 10
Distance Line Protection
Permissive Overreach Transferred Tripping (POTT)
B LBC C
F
BC1
RBC
CB1
RCB
L
NSD NSD
ABB Automation
Utility Communication Systems
CHPAU NKT F 11
Distance Line Protection
Direct Transfer Tripping (DTT)
B LBC C
F
BC1
RBC
CB1
RCB
L
NSD NSD
ABB Automation
Utility Communication Systems
CHPAU NKT F 12
Transformer Protection
Example for direct tripping
NSD 70C
B
P Pilot cable
P L
L HV Transmission Line
C or -Cable
NSD 70C
ABB Automation
Utility Communication Systems
CHPAU NKT F 13
Distance Line Protection
Blocking
B LBC C F
RBC
BCe BCi
CBi
RCB CBe
L
NSD NSD
Command
input (local)
Transmission Disturbance,
time Impairments
Command
output (remote)
Dependability Security
ABB Automation
Utility Communication Systems
CHPAU NKT F 15
Telecommunication Channel Impairments
ABB Automation
Utility Communication Systems
CHPAU NKT F 16
Performance Criteria for Teleprotection
Transmission Security
Time (Probability of
unwanted command)
Dependability Bandwidth or
(Probability Data Rate
of missing
command)
ABB Automation
Utility Communication Systems
CHPAU NKT F 17
Line Protection
Possible Signal Connections Between two Distance Relays
ABB Automation
Utility Communication Systems
CHPAU NKT F 18
Total Fault-Clearance-Time
• Time delay between fault occurrence and line tripping
• The fault-clearance time results from:
• Relay-time (fault detection) TREL
• Command transmission time TAC
• Switching delay of line breaker TBR
• Typical values:
TTotal = TREL + TAC + TBR
75 ms = 20 ms + 15 ms + 40 ms
ABB Automation
Utility Communication Systems
CHPAU NKT F 19
Typical requirements for different applications
ABB Automation
Utility Communication Systems
CHPAU NKT F 20
Command Systems, Typical Figures
Blocking Analog systems Digital systems
• short transmission time Tac < 15 ms < 10 ms
• moderate security Puc < 1E-2 < 1E-6
• high dependability Pmc < 1E-3 < 1E-3
Permissive tripping
• moderate transmission time Tac < 20 ms < 10 ms
• moderate to high security Puc < 1E-3 ....1E-4 < 1E-6
• moderate to high dependability Pmc < 1E-2 ....1E-3 < 1E-3
Direct tripping
• moderate transmission time Tac < 40 ms < 10 ms
• very high security Puc < 1E-5 .... 1E-6 < 1E-9
• very high dependability Pmc < 1E-3 < 1E-3
ABB Automation
Utility Communication Systems
CHPAU NKT F 21
Teleprotection Equipment Command Systems
NSD 50 / NSD550
• Plug in unit for multi-purpose Power Line Carrier type ETL
HSD 50
• Dedicated protection Power Line Carrier
NSD 70, NSD 70C
• for analog bearers
• cables
• speech channels of analog and digital links
• power line carrier channels
NSD 70D
• for digital bearers
• digital multiplexers
• digital radio, fibre optic links
• with plug-in fibre optic line unit for dedicated fibres
ABB Automation
Utility Communication Systems
CHPAU NKT F 22
TEBIT: Teleprotection & binary interface
ABB Automation
Utility Communication Systems
CHPAU NKT F 23
Digital Networks
ABB Automation
Utility Communication Systems
CHPAU NKT F 24
Digital Cross-Connect Networks
Network -
Management
Network management
activities may have a
detrimental impact on a
Digital network
protection system, unless
adequate precautions are Digital Cross-Connect
taken Protection terminal
ABB Automation
Utility Communication Systems
CHPAU NKT F 25
Digital Cross-Connect Precautions
ABB Automation
Utility Communication Systems
CHPAU NKT F 26
800 kV redundant Line Protection (with NSD 50 and NSD 70)
Breaker Transducers
HV transmission line
PUTT Permissive underreach
tripping
PUTT A NSD 70 indirect
LINE POTT1 B NSD Coupling
PROT POTT2 C 50 POTT 1 Permissive overreach
I ETL PLC
RM91 D tripping
81 I
RE93 NSD 70 indirect
A NSD
B 70
POTT 2 Permissive overreach
BFP tripping
NSD 50 indirect
ABB Automation
Utility Communication Systems
CHPAU NKT F 27
800 kV redundant Line Protection
Breaker Transducers
HV transmission line
PUTT Permissive underreach
tripping
PUTT A PLC NSD 70 indirect
LINE POTT1 B NSD Coupling
PROT POTT2 C 550 POTT 1 Permissive overreach
I ETL
RM91 D tripping
580
RE93 NSD 70 indirect
A NSD
B 70
POTT 2 Permissive overreach
BFP tripping
NSD 550 indirect
ABB Automation
Utility Communication Systems
CHPAU NKT F 28