1.0 Introduction
1.1 Introduction
1. 2 Training Overview
1.0 - Introduction :
BiltBilt Middle
Middle East
East LLCLLC
BILT MIDDLE EAST LLC PO Box No. 2393, Dubai
PO Box No. 2393, Dubai UAE UAE 4
Project : The Sevens CHILLED WATER PUMPS
There are total three Chilled water pump rooms. The main pump room is located in Chiller Yard
and comprises of 4 nos. Primary pumps of 50 L/s each & 3 nos. Secondary Pumps of 66 L/s
each.
The Secondary pump serves chilled water to the Tertiary pumps located in Player’s Club House
& Grand Stand respectively through pre-insulated HDPE pipes laid underground
There are 2 Tertiary pumps in Club House Pump Room each of 36 L/s & 2 Tertiary pumps in
Grand Stand Pump Room each of 52 L/s.
These pumps are of Centrifugal end section type complete with Cashing, internally self flushing,
mechanical seals, flexible couplings, base frame and motor. Split casing design allows
servicing of bearing & seal without disturbing to piping.
These pumps are of Centrifugal end section type complete with Cashing, internally self
flushing, mechanical seals, flexible couplings, base frame and motor. Split casing design
allows servicing of bearing & seal without disturbing to piping.
DUCTILE IRON CASING, SS SHAFT, BRONZE IMPELLER, MECHANICAL SEAL, TEFC MOTOR
ENCLOSURE & CLASS F INSULATION
ITT-BELL & GOSSETT PUMPS.
QTY : 3 NOS
Continues……
DUCTILE IRON CASING, SS SHAFT, BRONZE IMPELLER, MECHANICAL SEAL, TEFC MOTOR
ENCLOSURE & CLASS F INSULATION
ITT-BELL & GOSSETT PUMPS.
QTY : 4 NOS
DUCTILE IRON CASING, SS SHAFT, BRONZE IMPELLER, MECHANICAL SEAL, TEFC MOTOR
ENCLOSURE & CLASS F INSULATION
ITT-BELL & GOSSETT PUMPS.
QTY : 2 NOS
DUCTILE IRON CASING, SS SHAFT, BRONZE IMPELLER, MECHANICAL SEAL, TEFC MOTOR
ENCLOSURE & CLASS F INSULATION
ITT-BELL & GOSSETT PUMPS.
QTY : 3 NOS
Chilled water pumps shall be controlled through VFD except primary chilled water pumps.
switch installed in primary chilled water pups shall shut off pump if the pressure
difference across the suction & discharge line of the pump is falling below then the set
point.
In the event of receipt of an alarm on the secondary chilled water pump, the faulty pump
shall be kept as a last priority until the fault is rectified.
4.0 Documentation
4.1 Review of O&M Manuals
For Description of the System, please refer Section 2.2 of Volume 1 HVAC
services.
4.0 -- Documentation
4.0 -- Documentation
4.0 -- Documentation
MONITORING
4.0 -- Documentation
4.1.2 Maintenance Routines
SHUTTING DOWN
CLOSE THE VALVE IN DISCHARGE PIPE RIGHT BEFORE (MAX. 30SEC) SWITCHING OFF THE
MOTOR.
CLOSE AUXILIARY SYSTEMS. DO NOT SHUT DOWN COOLING SYSTEM UNTIL PUMP HAS COOLED
DOWN.
CLEANING OF PUMPS
DIRT ON THE OUTSIDE OF THE PUMP HAS AN ADVERSE EFFECT ON TRANSMISSION OF HEAT.
THE PUMP SHOULD THEREFORE BE CLEANED WITH WATER AT REGULAR INTERVALS.
Continues…..