MiCOM P12x Range

MiCOM P120, P121, P122 & P123

Universal overcurrent relays

1 >P220 ARU–
MiCOM P12x Range
A range of overcurrent relays for:

 Industrial networks and substations

 Distribution networks and HV/MV feeder substations

 EHV/HV backup protections

2 >P220 ARU–
MiCOM P12x Range
A whole range for a global answer

 P120: Earth fault or Single phase O/C

 P121: 3 phases + earth O/C

 P122: Advanced 3 phases + earth O/C

 P123: Expert 3 phases + earth O/C

3 >P220 ARU–
Functions ANSI MiCOM MiCOM MiCOM MiCOM
Code P120 P121 P122 P123
Single-phase overcurrent 50/51 or X
50N/51N

Three-phase overcurrent 50/51 X X X


Earth fault overcurrent 50N/51N X X X X
Restrictive Earth fault 64N X X X X
Thermal overload (True RMS) 49 X X
Undercurrent 37 X X
Negative sequence overcurrent 46 X X
Broken conductor detection X X
Cold load pickup X X
Instantaneous/start contact X X X X
Latching output contacts 86 X X X X
Setting groups 1 1 2 2
Circuit breaker failure detection 50BF X X

Trip circuit supervision (TCS) X X


Switch on to fault (SOTF) X

4 >P220 ARU–
Functions ANSI MiCOM MiCOM MiCOM MiCOM
Code P120 P121 P122 P123
CB control Local / Remote X
Circuit Breaker monitoring and X X
control
Blocking logic X X X X
Selective relay scheme logic X X
Multi-shot autoreclose 79 X
Clock phase and anti-clock Phase X X
rotation operation
Measurements (True RMS) X X X X
Peak and rolling values X X
Event records X X
Instantaneous records X X
Fault records X X
Disturbance records X X
RS 232 front communication for X X
MiCOM S1 Software
RS 485 rear communication (Modbus X X X X
RTU, IEC 60870-5-103, Courier,
DNP3.0)

5 >P220 ARU–
MiCOM P12x Range
Housing
78
97 11.6
24.6 52

All dimensions
in mm. Panel cut-out
168 158 Flush mounting
fixing details

4 holes O
/ 3.4 99 4 holes O
/ 4.4 (M4 screw)
103 25.1 226
MiCOM P121

IA = 214.50 A
Trip

Alarme C 
Equip. fail

Auxiliary
supply 177 151.2 max.
AUX. 1

AUX. 2

AUX. 3

AUX. 4
AREVA

Flush mounting

6 >P220 ARU–
Rear face MiCOM
P120, P121, P122 & P123
Earth
Housing

2 blades 4,8mm x 0,8mm

+ 1 M4 screw

by connection
point

7 >P220 ARU–
User Interface MiCOM
P120, P121, P122 & P123

2 tactile button keypad for


reading and clearing 2 x 16
alarms and messages alphanumerical
backlit display

Trip Led
Alarm Led Retractable flaps
Equipment failure Led to withdraw
Auxiliary supply Led the active part
Programmable Leds

5 tactile buttons
keypad for setting
and consulting
Battery
(P122 & P123) RS 232

8 >P220 ARU–
DEFAULT DISPLAY
IL1 = 1245 A

OP PARAMETERS CONFIGURATION MEASUREMENTS COMMUNICATION

Password Frequency Communication ?


Display CT Ratio Led 5 / 6 / 7 / 8
**** 50.01 Hz Yes

Description Phase Text CT primary Led IL1 Baud Rate


P120 L1 1000 I> Y/N 257.05 A 19200 Bd
tI> Y/N
l>> Y/N
Reference CT sec tI>> Y/N Parity
ALST 1 I>>> Y/N None
tI>>> Y/N

Frequency Stop bits


50 Hz 1

Input 21 Relay Address


Status 01 12

Relay 4321
Status 1011

MiCOM P120 - V4 Software - Menu Content

9 >P220 ARU–
DEFAULT DISPLAY
IL1 = 1245 A

PROTECTION AUTOMAT. CTRL

[50/51] Phase OC Trip Commands Latch Functions Blocking Logic Output Relays Inputs 1/2

Trip tI > Latch tI > Block tI > Trip 432 None


I>? I>>> Yes Yes Yes 100 Unlatch
Yes 10.0 In
I> 52 a
Trip tI >> Latch tI >> Block tI >> tl > 52 b
Yes Yes Yes I >>
I> t I>>> CB FLT
0.1 In 110 ms tl >> Aux 1
Trip tI >>> Latch tI >>> Block tI >>> I >>> Aux 2
Yes Yes Yes tl >>> Blk Log
Delay Type CB Close
IDMT

Idmt
IEC SI

Tms
0.025

I>> ?
Yes

I>>
2.0 In

MiCOM P120 - V4 Software - Menu Content


t I>>
300 ms

I>>> ?
Yes

10 >P220 ARU–
MiCOM P12x Range
Communication

11 >P220 ARU–
MiCOM P12x Range
Communication

 Front communication port


 RS232

 Rear communication port


 RS485

12 >P220 ARU–
MiCOM P12x Range
RS 232 Front Communication Port

 MiCOM P120 and P121


 New firmware downloading (flash memory)

 MiCOM P122 and P123


 New firmware downloading (flash memory)
 MiCOM S1 setting software on PC

13 >P220 ARU–
MiCOM P12x Range
MiCOM S1 Software

 CONTROLS to MiCOM relays


 Settings
 CB Opening/Closing
 Setting group change

 Data extraction
 Settings
 Measurements
 Events records (75 events)
 Faults records (Last 5 faults)
 Disturbance records (5 records)

14 >P220 ARU–
MiCOM P121 Thresholds
Phase Overcurrent

 First threshold I> From 0.1 to 40 In


 Instantaneous time 30 ms
 Definite time 0 ms to 150 s
 Inverse time 5 IEC curves,
1 electromechanical curve,
5 IEEE/ANSI curves.

 I>> and I>>> thresholds From 0.1 to 40 In


 Instantaneous time 30 ms
 Definite time 0 ms to 150 s

15 >P220 ARU–
MiCOM P121 Thresholds
Earth Fault

 First threshold Ie>: From 0.002 to 25 Ien


(according to the selected range)
 Instantaneous time 30 ms
 Definite time 0 ms to 150 s
 Inverse time 5 IEC curves,
1 electromechanical curve,
5 IEEE/ANSI curves

 Ie>> and Ie>>> thresholds: From 0.002 to 40 Ien


(according to the selected range)
 Instantaneous time 30 ms
 Definite time 0 ms to 150 s

16 >P220 ARU–
Thresholds

Ith
Time

I>
tI>

I>>
tI>>
I<
I>>> tI>>>

Current

17 >P220 ARU–
Thresholds

Ie>
Time

Ie>>
tIe>>
Ie>>> tIe>>>

Current

18 >P220 ARU–
EARTH AND PHASE CURRENT OVERCURRENT FUNCTIONS

19 >P220 ARU–
EARTH AND PHASE CURRENT OVERCURRENT FUNCTIONS
INVERSE TIME CURVES
The first and second stage overcurrent threshold can be selected
with a dependent time characteristic.

The time delay is calculated with a mathematical formula.


There are eleven inverse time characteristics available.
The mathematical formula applicable to the first ten curves is :
Where:

t = Tripping time
K = Coefficient
I = Value of measured current
IS = Value of the programmed threshold (Pick-up value)
α = Coefficient
L = ANSI/IEEE coefficient (zero for IEC curves)
T = Time multiplier between 0.025 and 1.5
20 >P220 ARU–
EARTH AND PHASE CURRENT OVERCURRENT FUNCTIONS

21 >P220 ARU–
Measurements (P122 & P123)

22 >P220 ARU–
Measurements (P122 & P123)
Peak and Average Values Meas. on a Time Window

 The peak and average values by phase are calculated on a time RECORDS
window settable from 5mn to 60mn
TIME PEAK VALUE
 The display is presented in the Measurement menu at the end
TIME WINDOW =
of the time window 5 mn

 The calculation is re-started MEASUREMENTS


 By user interface
 Or by remote control Max & Average I
RST = [C]

23 >P220 ARU–
Measurements (P122 & P123)
Rolling and Peak Value Demands

 The average values by phase are calculated on a « Rolling demand RECORDS


sub period » settable from 1 mn to 60 mn
ROLLING DEMAND
 The fist display is given after the calculation of the average values
SUB PERIOD
on a given « Number sub periods » settable from 1 to 24 1mn

 Reset Num of Sub Per


2
MEASUREMENTS
 By user interface
 Or by remote control
ROLLING AVERAGE
RST = [C]

24 >P220 ARU–
Fault Records
(P122 & P123)

25 >P220 ARU–
Fault Records (P122 & P123)
Last 5 Faults

 Data available on the front of the relay and via communication


 Fault number (1 to 5)

 Time (13:07:15:53)

 Date (09/08/01)

 Active setting group (Gr1 or Gr2)

 Origin (I>, I>>, I>>>, Io>, Io>>,Io>>>,....)

 Fault magnitude

 Phases and earth magnitude of each phase

26 >P220 ARU–
Event Records
(P122 & P123)

27 >P220 ARU–
Event Records
(P122 & P123)

 All logic inputs and outputs change

 1 ms time stamped

 75 events stored in memory

 Records can be transferred using RS232 front or RS485


rear communication port

28 >P220 ARU–
Event Records
(P122 & P123)

29 >P220 ARU–
Disturbance Records
(P122 & P123)

 5 disturbance records
 Sampling 1600 Hz (at 50 Hz)

 Adjustable pre and post-time up to 3 s

 Start on instantaneous or on tripping

 One or all records can be


transferred using RS232 front
or RS485 rear communication
port

30 >P220 ARU–
Wiring & Connections

31 >P220 ARU–
2 Setting Groups (P122 & P123)
2 Identical Protection Setting Groups

 Possibility to change the setting group:

 From front panel

 From digital input


 On edge
 Or on level (high or low)

 From remote control

 Output relay indication:


 Open contact = Gr1, closed contact = Gr2

32 >P220 ARU–