Escolar Documentos
Profissional Documentos
Cultura Documentos
1889-Kennelly 14 25 12.5 15 15
12 33 16.5 20 20
10 46 23 28 25
• 1894 Insurance Co. set 8
6
58
78
29
39
35
47
35
50
at 50% 5 90 45 54 55
4 104 52 62 70
3 120 60 72 80
• 1896 Insurance Co. 2 144 72 86 90
1 172 86 103 100
revised to 60% 0 206 103 124 125
00 246 123 148 150
000 298 149 179 200
• 50C Code Grade Rubber 0000 360 180 216 225
250
300
350
400
500
600
Year 1923 1925 1935 1940
Rosch 14 15 15 15 15 20
12 193820 Rosch
20 20 20 26
•Used basic Heat 10 25 25 25 25 35
8 35 35 35 35 48
Transfer Equation to
determine ampacity
6
• Used
50 50
basic 50
Heat 45
Transfer 65
5 55 55 55 52 76
4
Equation
70
to
70
determine
70 60 87
ampacity
•Ampacity for 3 80 80 80 69 101
2 90 90 90 80 118
Conductors in free air 1 • Ampacity
100 100for Conductors
100 91 in 136
0 125
free air 125 125 105 160
00 150 150 150 120 185
•Ampacity for 000 175 175 175 138 215
Conductors in conduit • Ampacity
200 200for Conductors
200 in
0000 conduit
225 225 225 160 248
250 250 250 250 177 280
300 275 275 275 198 310
350 300 300 300 216 350
400 325 325 325 233 380
500 400 400 400 265 430
600 450 450 450 293 480
1938-1940
I Current Flow
𝑽𝒐𝒍𝒕𝒂𝒈𝒆 120V 0V
𝑰=
𝑹𝒆𝒔𝒊𝒔𝒕𝒂𝒏𝒄𝒆
Resistance of copper
conductor
Q Heat Flow
∆ 𝑻𝒆𝒎𝒑𝒆𝒓𝒂𝒕𝒖𝒓𝒆
Q= 50 30C
𝑻𝒉𝒆𝒓𝒎𝒂𝒍 𝑹𝒆𝒔𝒊𝒔𝒕𝒂𝒏𝒄𝒆
Thermal Resistance
Heat Transfer of Cable
Heat Transfer within Conduit
90 30
R1 R2 R3 R4
Insulation Air Resistance Conduit Conduit to Air
Resistance Inside Conduit Resistance Resistance
Heat Transfer
Conduction through
Insulation
Natural Convection
outside conduit
x Radiation in
x Radiation out
x Forced convection
outside (wind)
x Forced convection inside
(wind, chimney effect)
x Natural Convection inside
conduit
Ampacities of Three Single Insulated Conductors,
SIZE Rated 0-2000 Volts, IN Conduit in Free Air Based on 1984-1987
Ambient Air Temperature of 40C
60C 75C 90C
TYPE RH,
RHW, RUH,
TYPE SA, Proposals to NEC
AWG TYPES RUW, AVB, FEP,
MCM T, TW, UF
THW, THWN,
FEPB, THHN, Neher-McGrath Method 1956
XHHW, USE,
ZW
RHH, XHHW Corrected Rosch – 1938
Considered to be more accurate
Copper
14 18 22 25 Included in 1984 NEC for adoption in
12 23 28 32 1987
10 29 37 42
8 36 48 55
6
4
50
65
64
83
75
97
Most parts rejected in 1987 due
3 76 98 114 to termination concerns
2 87 112 130
Retained for medium voltage
1 104 134 156
0 119 153 179 Moved to Annex B for low voltage
0 135 175 204
0 160 207 242
0 184 238 278
250 210 271 317
300 232 300 351
350 254 328 384
400 274 354 475
500 314 407 477
Proposal 6-41 (1984)
1. The NEC is very conservative in its ratings of bare and covered conductors
(line wire).
2. The NEC does not employ a technique to account for the effect of sun and
wind.
3. The NEC does not correctly account for the difference in ampacity of bare and
covered line wire.
4. The NEC ratings for not more than three conductors in a raceway can cause
both the inspector and the user to make significant errors because:
They do not provide for the variables of load factor and earth thermal
resistivity in underground applications.
There is no derating factor that will get one to the most common earth
ambient - 20°C.
For most direct burial applications the NEC will waste money because it is
too conservative.
For conduit-in-air applications, the NEC ratings are too conservative.
Proposal 6-41 1984
Figure 8: EMT Conduit with Roof Surface at 350 K (77 °C, 170 °F), 30 Degree Contact Angle Roof
Wiring systems
raised off roof
Add 22C Celsius
Figure 9: EMT Conduit Raised off of Roof Surface
Roof
Convection Reflected Solar
Radiation
Solar
Radiation
Rooftop
Conduction
Roof
Solar
Radiation
Case 4: 3 No. 12 AWG in ¾” EMT
¾” EMT raceway
O.D. 0.92 in =23.4 mm
ID = 0.824 in = 21 mm
Wall = 0.049 in = 1.25 mm
Galvanized steel
k_s = 51 W/m-K
emissivity = 0.83
absorptivity = 0.7
Assumptions in model
• Tamb = 41 °C (105.5 °F)
• No forced air movement external to conduit (only natural convection)
• No axial air movement internal to conduit
• Absorption coefficient α = 0.7 (from NREL database)
• Emission coefficient ε = 0.83 (from NREL database, where ε = 0.88;
adjusted downward to match UL study data; Pessimistic adjustment)
• Natural convection coefficient = 6 W/m2K
• Resistance between wire and conduit = 0.5 K-m/W (from finite element
simulation)
• Solar radiation 1050 W/m2 (UL results only use data for insolation
between 1000 and 1100 W/m2)
• I = 0 A (for comparison with UL data)
• Temperature-variable model of wire resistivity used
• Radiation only through upper half of conduit (both absorption and
emission; net radiative exchange with roof assumed negligible)
Results – Compare to UL
measurements
4” EMT raceway
O.D. 4.5 in =114.3 mm
ID = 4.334 in = 110.1 mm
Wall = 0.083 in = 2.11 mm
Galvanized steel
k_s = 51 W/m-K
emissivity = 0.83
absorptivity = 0.7
Results – Compare to UL
measurements
Example
o 41 degree C ambient in Nevada
o 33 degree C ambient Temp Rise
in Conduit due to Radiation
o 50 degree C rise due to fully
loaded conductor.
• All conduits tested were raised off roof 8 inches. Did not compare with
conduits on roof to test for affects of roof conduction.
With 8 in
Without
Rooftop Adder
Each of the wiring methods experienced a temperature rise that exceeded the
ambient temperature. In the case of the energized conductors, which were the
minimum allowable size for the continuous load carried, the maximum
temperature experienced was 69° C, approximately 77% the temperature rating of
the conductor insulation (i.e., 90° C). In the case of the non-energized conductors,
the maximum temperature experienced was 60° C, approximately 67% the rated
temperature of the conductor insulation.
Since this is an experimental setup and not a working installation, the measured
temperatures are likely higher than a real-world installation due to the complete
exposure of the entire conduit length including origination points. Real-world
installations usually terminate on a rooftop, but originate in lower ambient
temperature locations such as in an electrical room or on the side of a building.
Findings
CDA / UL Report do not take into account how conduits are terminated.
CDA / UL Report assume that Heat Transfer outdoors is linear when it is not.
1000 W/m2 solar radiation. 1000 W/m2 is based maximum solar radiation
during a one or two hours a day, during one or two months out of a year.