BASICS
1. NO & NC CONTACTS
2. CIRCUIT BREAKER AUX SWITCH
3. ISOLATOR AUX SWITCH
4. PRESSURE SWITCH & DENSITY MONITOR
5. ANNUNCIATION
6. INDICATION
7. SEMOPHORE
8. CB OPERATING MECHANISAMS
9. CB ARC QUENCHING METHODS
10. INTERLOCKS BETWEEN CB & ISO
11. INTERLOCKS FOR LOCAL CLOSE OF CB
12. INTERLOCKS FOR REMOTE CLOSE OF CB
13. INTERLOCKS FOR ISOLATOR
14. INTERLOCKS FOR EARTH SWITCH
15. CB CLOSING CIRCUIT
16. CB TRIPPING CIRCUIT
17. WHAT IS BISTABLE RELAYS-NORMAL SWITCH
18. WHAT IS MONOSTABLE RELAYS-BELL SWITCH
19. ANTIPUMPING CONTACTOR
20. WHAT IS TSR & PRE CLOSE & POST CLOSE
21. AC FAIL CONTACTOR
22. DC FAIL CONTACTOR
23. SYNCHROSCOPE SOCKET – REQUIREMENTS – CONDITIONS
24. CB POLE DISCREPANCY RELAY
25. BINARY INPUT & BINARY OUTPUT OF RELAY
26. TNC SWITCH
27. LOCAL REMOTE SWITCH
28. SPRING CHARGE LIMIT SWITCH
29. TYPES OF WIRING- INTRA, INTER & CABLE SCHEDULE
30. PT / CVT IN MB
31. PT DISTRIBUTION
32. BUS PT SELCTION LOGIC
33. BUSPT LINE CVT SELECTOR SWITCH
34. CT IN MB & CORE CLASS & TERMINATION & STAR FORMATION FOR BUS & CIRCUIT
35. STANDARDS FOLLOWING
36. CABLE SCHEDULE
C & R Panel Contains
1. AC Circuits
2. DC Circuits
3. CT Circuits
4. PT/CVT Circuits
PURPOSE OF AC CIRCUITS
1. DOOR LAMP
2. PANEL HEATER
3. PLUG SOCKET
4. AUX SUPPLY TO ANNUNCIATION FACIA
5. AUXILIARY SUPPLY TO TRANSDUCER CKT
6. DC FAIL CIRCUIT
3
52 CB LINE
89A 89B
CVT LA/SA
PT/EMVT PT/EMVT
IF 89A ISOLATOR CLOSED BUS-1 PT VOLTAGE WILL BE SELECTED
IF 89B ISOLATOR CLOSED BUS-2 PT VOLTAGE WILL BE SELECTED
IF VOLTAGE SELECTOR SWITCH IS KEPT IN BUS THEN BUS PT
VOLTAGE IS EXTENDED TO RELAY
IF VOLTAGE SELECTOR SWITCH IS KEPT IN LINE THEN LINE CVT
VOLTAGE IS EXTENDED TO RELAY
THE CIRCUIT DIAGRAM SHOWN IN NEXT PRESENTATION
BUS-1 & BUS-2 PT IS COMING TO PT DISTRIBUTION BOX AND
DISTRIBUTED FURTHER.
VOLTAGE SUPPLY SELECTION
89AX MANUAL
+VE VOLTAGE
-VE SELECTOR
BUS-1 PT SUPPLY
SWITCH.
BUS LINE
R N
PT CVT
Y
89A B
BUS-1 ISOLATOR N
21 MAIN-1
89BX OR
+VE
21 MAIN-2
-VE
BUS-2 PT SUPPLY
PROT
R
Y RELAY
89B B
BUS-2 ISOLATOR N
LINE CVT SUPPLY
R
Y
B
N
CT NAME PLATE DETAILS
CLASS OF PRIMARY SECONDARY KNEE POINT MAGNETISING
CORE RATIO CORE RESISTANCE
ACCURACY WINDING WINDING VOLTAGE CURRENT
500/1 1S1 – 1S2 1000V 120mA 2.5 OHMS
PS
1 1000/1 PI – P2 1S1 – 1S3 2000V 60mA 5.0 OHMS
(PROTECTION)
2000/1 1S1 – 1S4 4000V 30mA 10.0 OHMS
500/1 2S1 – 2S2 1000V 120mA 2.5 OHMS
PS
2 1000/1 PI – P2 2S1 – 2S3 2000V 60mA 5.0 OHMS
(PROTECTION)
2000/1 2S1 – 2S4 4000V 30mA 10.0 OHMS
500/1 3S1 – 3S2
0.2
3 1000/1 PI – P2 3S1 – 3S3 BURDEN = 40VA
(METERING)
2000/1 3S1 – 3S4
500/1 4S1 – 4S2 1000V 120mA 2.5 OHMS
PS
4 1000/1 PI – P2 4S1 – 4S3 2000V 60mA 5.0 OHMS
(PROTECTION)
2000/1 4S1 – 4S4 4000V 30mA 10.0 OHMS
500/1 5S1 – 5S2 1000V 120mA 2.5 OHMS
PS
5 1000/1 PI – P2 5S1 – 5S3 2000V 60mA 5.0 OHMS
(PROTECTION)
2000/1 5S1 – 5S4 4000V 30mA 10.0 OHMS
CVT NAME PLATE DETAILS
SECONDARY
CORE CLASS OF ACCURACY PRIMARY WINDING PRIMARY VOLTAGE SECONDARY VOLTAGE VA BURDEN
WINDING
3P 1a1 – 1n
1 P1 – E 400KV / √3 110V / √3 200 VA
(PROTECTION) 1a2 – 1n
3P 2a1 – 2n
2 P1 – E 400KV / √3 110V / √3 200 VA
(PROTECTION) 2a2 – 2n
0.2 3a1 – 3n
3 P1 – E 400KV / √3 110V / √3 100 VA
(METERING) 3a2 – 3n
SECONDARY
CORE CLASS OF ACCURACY PRIMARY WINDING PRIMARY VOLTAGE SECONDARY VOLTAGE VA BURDEN
WINDING
3P 1a1 – 1n
1 P1 – E 220KV / √3 110V / √3 200 VA
(PROTECTION) 1a2 – 1n
3P 2a1 – 2n
2 P1 – E 220KV / √3 110V / √3 200 VA
(PROTECTION) 2a2 – 2n
0.2 3a1 – 3n
3 P1 – E 220KV / √3 110V / √3 100 VA
(METERING) 3a2 – 3n
PT / EMVT NAME PLATE DETAILS
SECONDARY
CORE CLASS OF ACCURACY PRIMARY WINDING PRIMARY VOLTAGE SECONDARY VOLTAGE VA BURDEN
WINDING
3P 1a1 – 1n
1 P1 – E 220KV / √3 110V / √3 200 VA
(PROTECTION) 1a2 – 1n
3P 2a1 – 2n
2 P1 – E 220KV / √3 110V / √3 200 VA
(PROTECTION) 2a2 – 2n
3a1 – 3n
3 0.2 P1 – E 220KV / √3 110V / √3 100 VA
3a2 – 3n
SECONDARY
CORE CLASS OF ACCURACY PRIMARY WINDING PRIMARY VOLTAGE SECONDARY VOLTAGE VA BURDEN
WINDING
0.2 1a1 – 1n
1 P1 – E 132KV / √3 110V / √3 100 VA
(METERING) 1a2 – 1n
0.5 2a1 – 2n
2 P1 – E 132KV / √3 110V / √3 100 VA
(PROTECTION) 2a2 – 2n
3P 3a1 – 3n
3 P1 – E 132KV / √3 110V / √3 100 VA
(PROTECTION) 3a2 – 3n
BUS-1 PT/EMVT
PRIMARY VOLTAGE UUUUU
220 KV / 1.732 UUUUU
SECONDARY VOLTAGE
BUS-1
110V/1.732 UUUUU
P1
OPEN DELTA CL: 0.5 MAIN-1 PROT CL:3P MAIN-2 PROT CL:3P METERING CL: 0.2
UUU UUU UUU UUU UUU UUU UUU UUU UUU UUU UUU UUU
PTMB
BUS-2 PT/EMVT
PRIMARY VOLTAGE UUUUU
220 KV / 1.732 UUUUU
SECONDARY VOLTAGE
110V/1.732 UUUUU
BUS-2
P1
BUS PT AT YARD
OPEN DELTA CL: 0.5 MAIN-1 PROT CL:3P MAIN-2 PROT CL:3P METERING CL: 0.2
UUU UUU UUU UUU UUU UUU UUU UUU UUU UUU UUU UUU
PTMB
TB 4
10
10
3
4
3
4
2
2
7
8
9
7
8
9
5
5
6
6
1
BAY MARSHELLING BOX BACK VIEW BAY MARSHELLING BOX FRONT VIEW
TB DISTRIBUTION AC DISTRIBUTION
IMPORTANT GUIDELINES
CT & VT Earthing
CT / VT secondary neutrals should be earthed at one
point only.
VT secondary neutral earthing is done at equipment
itself.
It is preferable to earth the CT secondary neutral in the
control / protection cubicle in order to provide
maximum security to the operating personnel.
CT POLARITY
As a practice the P1 terminal of the CT shall be towards
the bus and P2 away from the bus.
From the above for Main-1, Main-2 & Metering – Primary
current flows from P1 to P2. Accordingly secondary
current Flows S2 to S1. Star formation is all S2s.
For the BBM & BBC – Primary current flows from P2 to
P1. Accordingly secondary current Flows S1 to S2. Star
formation is all S1s. Please conclude here.
CABLE SCHEDULE
CABLE SCHEDULE
1. NAME OF THE SUBSTATION: 2. NAME OF THE FEEDER/ TRANSFORMER:
3. CB DETAILS: 4. CT DETAILS
5. CVT / PT / EMVT DETAILS: 6. ISOLATOR DETAILS
7. C&R PANEL DETAILS: 8. POWER TRANSFORMER DETAILS :
FROM TO CORE
S.No Cable DESCRIPTION / PURPOSE Cable REFERENCE
ID PANEL TB No FERRULE PANEL TB No FERRULE & Size NO
CABLE SCHEDULE
1 2 3 4 5 6 7
FROM TO
S.No
PANEL TB No FERRULE PANEL TB No FERRULE
1 5S1 TB-5-1 R-5S1
2 5S2 TB-5-2 R-5S2
3
R – PH CT CORE - 5 5S3
CTMB
TB-5-3 R-5S3
4 5S4 TB-5-4 R-5S4
5 5S1 TB-5-6 Y-5S1
6 5S2 TB-5-7 Y-5S2
7
Y – PH CT CORE - 5 5S3
CTMB
TB-5-8 Y-5S3
8 5S4 TB-5-9 Y-5S4
9 5S1 TB-5-11 B-5S1
10 5S2 TB-5-12 B-5S2
11
Y – PH CT CORE - 5 5S3
CTMB
TB-5-13 B-5S3
12 5S4 TB-5-14 B-5S4
CABLE SCHEDULE
8 9 10 11 12
DESCRIPTION / CABLE CORE
REFERENCE REMARKS
PURPOSE & SIZE No
1
R-PH CT TO
2 DRG NO:
CT MB OF 4C X 2.5
3 PAGE NO
CORE-5
4
1
Y-PH CT TO
2 DRG NO:
CT MB OF 4C X 2.5
3 PAGE NO
CORE-5
4
1
B-PH CT TO
2 DRG NO:
CT MB OF 4C X 2.5
3 PAGE NO
CORE-5
4
CIRCUIT BREAKER
S.No DESCRIPTION INCASE OF CGL BREAKER
1 LOCAL CLOSING INTERLOCK K5, K5A
2 LOCAL CLOSE (IN CB CUBICLE) - -
3 REMOTE CLOSE (FROM CONTROL PANEL HAND CLOSE) K1
4 LOCAL TRIP ( IN CB CUBICLE) --
5 REMOTE TRIP COIL-1 (FROM CONTROL PANEL HAND TRIP) K21A, K21B, K21C
6 REMOTE TRIP COIL-2 (FROM CONTROL PANEL HAND TRIP) K41A, K41B, K41C
7 CB OPEN INDICATION A11, A12-B11,B12-C11,C12
8 CB CLOSE INDICATION A41, A42-B41,B42-C41,C42
9 DC SUPPLY J1, J2 & J11 & J12
10 PROTECTION CLOSE OR AUTO RE-CLOSE K3
11 PROTECTION TRIP COIL-1 & POST CLOSE SUPERVISION K23A, K23B, K23C
12 PROTECTION TRIP COIL-2 & POST CLOSE SUPERVISION K43A, K43B, K43C
13 PRE CLOSE SUPERVISION OF TRIP COIL-1 K31A, K31B, K31C
14 PRE CLOSE SUPERVISION OF TRIP COIL-2 K49A, K49B, K49C
15 CB CONTACT DICTRIBUTION. NOs – 8, NCs – 8
16 CB POLE DISTURBANCE RELAY.
17 CB CONTACT MULTIPLICATION RELAY.
18 CB TROUBLE ALARMS - 63 AR, GA, GL, AL, AG, AA, OA
CIRCUIT BREAKER CLOSING CIRCUIT
J3
T N C
LCIL LOCAL J4
K1 K3 K5 52Y SPL 63N 63HO 63G 63A 52b
52CC
K3A
REMOTE 52Y
52Y 52Y
A/R CLOSE
SLS
52a
SSSS
SSS REMOTE
T N C SERVICE
CLOSE
86A 86B 96BB
BYPASS
REMOTE CLOSE INTERLOCK
21M1 A/R
A/R CLOSE
21M2 A/R
PROTECTION TRIP
REMOTE
+ POST CLOSE
SUPERVISION
SUPERVISION
PRE CLOSE
C&R PANEL
T N C
REMOTE J14
J13 63N 63HO 63G 63A 52a
T N C 52TC
PROTECTION TRIP
LOCAL
+ POST CLOSE
SUPERVISION
SUPERVISION
PRE CLOSE
PB
EMERGENCY TRIP
NOMINCLATURES
52 CB AUX CONTACT OPEN 52b CB AUX CONTACT
a WHEN CB OPEN CLOSE WHEN CB OPEN Synchronization Requirements
52
CC
CB CLSOING COIL 52T
C-1
CB TRIP COIL-1 1. Voltages must be match
63 AIR PRESSURE 52 CB TRIP COIL-2
2. Frequency must be match
A CONTACT TC- 3. Phase angle must be match
2
63 SF6 GAS PRESSURE 63 HYDRAULIC OIL 1. Line Voltage
G CONTACT HO PRESSURE CONTACT
2. Bus Voltage
63 NITROGEN PRESSURE 52Y ANTIPUMPING
N CONTACT CONTACTOR 3. DC Supply
SP SPRING CHARGE LIMIT LCIL LOCAL CLOSING 4. Closing Permission
LS SWITCH INTERLOCK
K3 REMOTE CLOSE TNC TRIP NEUTRAL CLOSE
A SWITCH
18 MONOSTABLE & SELF 86 A BISTABLE & HAND
6 RESETING 86 B RESETING
28 FAST ACTING HIGH 96 HIGH SPEED TRIP
6 SPEED TRIP RELAYS BB RELAY /
MASTER TRIP RELAYS
A/ AUTO RECLOSURE SSS SYNCHROSCOPE
R S SELECTOR SWITCH
SS SYNCHROSCOPE SOCKET PB PUSH BUTTON
S
LR LOCAL REMOTE SWITCH
LOCAL CLOSING INTERLOCK
TAKE AN EXAMPLE OF SINGLE BUS SYSTEM
89 / 29 89 / 29 L
52 CB
BUS
89 / 29 E 89 / 29 LE
89 / 29 AE
LOCAL CLOSING INTERLOCK DRAWING
89M/B 89L 89 E 89AE
K1 K3
TO CB TRIP
52 TC-1-B
TO ANNUN
TO SER
52 TC-2-Y
52 CIRCUIT BREAKER
-VE
TRIP CIRCUIT HEALTHY
-VE
TSR TO CB PROTECTION TRIP CB HEALTHYNESS 52 TC-1
+VE LED
+ POST CLOSE SUPERVISION
21 MAIN-1
186 R1
R PHASE
186 R2
TO LBB
TO TC-1
TO TC-1 TO TC-2
TO TC-2
186 Y1
Y PHASE
186 Y2
TO LBB
TO TC-1
TO TC-1
TO TC-2
TO TC-2
186 B1
B PHASE
186 B2
TO LBB
TO TC-1
TO TC-1
TO TC-2
TO TC-2
BINARY OUTPUT
MAIN-2 PROTECTION OPERATED
+VE -VE
21 MAIN-2
286 R1
R PHASE
286 R2
TO LBB
TO TC-1
TO TC-1 TO TC-2
TO TC-2
286 Y1
Y PHASE
286 Y2
TO LBB
TO TC-1
TO TC-1
TO TC-2
TO TC-2
286 B1
B PHASE
286 B2
TO LBB
TO TC-1
TO TC-1
TO TC-2
TO TC-2
BINARY OUTPUT
86 GA (MASTER TRIP RELAY) OPERATION
+VE
PB RESET -VE
21 MAIN-1
OPERATED
M1 BUILT IN FUNCTIONS TO ANN
TEED-1 PROTECTION TO SER
OVER VOLTAGE STAGE-1 PROT
DIRECT TRIP CHANNEL-1 RECEIVED TO CL I/L
TO LBB
TO TC-1
TO TC-2
TO M1 DR
TO M2 DR
21 MAIN-2
OPERATED
M2 BUILT IN FUNCTIONS
TO ANN
TEED-2 PROTECTION
TO SER
OVER VOLTAGE STAGE-2 PROT
LBB/BFR RELAY TO CL I/L
DIRECT TRIP CHANNEL-2 RECEIVED TO LBB
TO TC-1
TO TC-2
TO M1 DR
TO M2 DR
BAY5 CB PANEL
HIGH SPEED
TRIP RELAY
TRIP FROM 50 LBB
(96BB)FOR
TO START 50 LBB BAY5
BAY6 CB PANEL HIGH SPEED
TRIP FROM 50 LBB TRIP RELAY
(96 BB) FOR
TO START 50 LBB
BAY6
+VE
BUSBAR PANEL
96 BB (MASTER TRIP RELAY) OPERATION
+VE
PB RESET -VE
87 BUSBAR
OPERATED
TO D/T-1
FROM LBB TO D/T-2
TO ANNUN
TO CL I/L
TO LBB
TO SER
TO TC-1
TO TC-2
TO M1 DR
TO M2 DR
OL RELAY 51OL
PRD-1 TRIP
HV O/L+E/F PROT 67
86 AY
PRD-2 TRIP
+VE -VE
OLTC BUCHHOLZ-R TRIP
+VE TO 3PH GR-B 400KV MAIN CB
TO 3PH GR-B 220KV MAIN CB
REF RELAY 64REF
OLTC BUCHHOLZ-Y TRIP
86 BY
LV O/L+E/F PROT 67
WNDG TEMP-HV TRIP
86GR-B
96BB
TRIP COIL-2 CIRCUITS
TRIP COIL-2
186R1 186Y1 186B1
86GR-B
96BB
CB CONTACT MULTIPLICATION
S.No R-PHASE Y-PHASE B- PHASE REF PURPOSE A-POLE B-POLE C-POLE
1 A11,A12 B11,B12 C11,C12
ALARM-1
5 2+
250V DC
2+
NSD 70
ACTIVE START TRIP 5- RX 5- RX
6 C C
TRIP TRIP
R R
6+ A(C) 6+ C(A)
DISPLAY
9- TX 9- TX
C C
S TRIP TRIP
S
ALARM-2
C 7 B(D) D(B)
250V DC
10+ 10+
8 13- 13-
C RX C
RX
E R TRIP R TRIP
14+ B(D) 14+ D(B)
CS
G4AC V9LC 2 CARRIER SEND
G4AA V9LB 5
ABB
PANEL-1
+VE -VE
NSD 50
G4AC V9LC 10
G4AC V9LC 13
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIP
G4AC V9LC 14 AND CONNECTED IN ANOTHER PANEL
G4AC V9LC 9
ABB
PANEL-2
MAIN-2 PROTECTION CARRIER INTER TRIPPING
NSD 50
G4AC V9LC 1
G4AC V9LC 6 ABB REL316
IN OUT
CR
CARRIER RECEIVE
G4AC V9LC 5 -VE
CS
G4AC V9LC 2 CARRIER SEND
G4AA V9LB 5
ABB
ALARM
G4AA V9LB 6
PANEL-2
+VE -VE
NSD 50
G4AC V9LC 10
G4AC V9LC 13
THIS IS BACKUP FOR PERMISSIVE/ PROTECTION TRIP
G4AC V9LC 14 AND CONNECTED IN ANOTHER PANEL
G4AC V9LC 9
ABB
PANEL-1
DIRECT TRIP SEND CARRIER CHANNEL-1
PANEL-1
ABB
NSD 50
DC +VE
BUSBAR PROTECTION PANEL FROM PANEL
CONTROL PANEL
T NC
MAIN CB(1-52CB)
. G4AD V9LC 2
G4AD V9LC 1
RELAY PANEL
DC –VE FROM PANEL
50 LBB/BFR
CONTROL PANEL
T NC
MAIN CB(1-52CB)
. G4AD V9LC 2
G4AD V9LC 1
RELAY PANEL
DC –VE FROM PANEL
50 LBB/BFR
+VE -VE
PANEL-2
ABB
TO MAIN2 DR
NSD 50 TO MAIN1 DR
DC +VE TO ANNUNCIATION
TO 86-B MASTER TRIP RELAY
G4AD V9LC 6 (HIGH SPEED TRIP RELAY)
DIRECT TRIP-2
CARRIER RECEIVE
G4AD V9LC 5 RELAY