FIELD OF COOLING
REFRIGERATION Screw
- Min about 100 TR
- Temp no bar
Compression type Centrifugal
chillers - High capacity temp
- normally above zero
Reciprocating
- Low capacity
- temperature no bar
Ammonia
- Low COP
Vapour absorption - No bar for temp
type chillers - Custom built
LiBr
- Good COP
- Standard Series
- Temp limitation up to 0oC
1. WHAT DOES “TR” MEAN?
TR is the unit of measurement of refrigeration capacity and is defined as …
COMPRESSION ABSORPTION
CONDENSOR
CONDENSOR
REBOILER
COMPRESSOR
PUMP
EVAPORATOR ABSORBER
EVAPORATOR
VAPOUR ABSORPTION
CHILLERS
WORKING SUBSTANCES IN VAPOUR
ABSOPRTION CHILLER
• LiBr
– Hygroscopic Nature
– Properties
• Water
– Properties
PRINCIPLES OF VAPOUR ABSORPTION
MACHINE
a) Affinity to water
10 Kg/cm2(g) 175°C
760mm Hg 100°C
70mm Hg 45°C
6mm Hg 3.5°C
Pressure Boiling Point
Modifications
SINGLE EFFECT STEAM FIRED CYCLE DIAGRAM (SS)
KNOW YOUR EQUIPMENT VAM
MAKE : VOLTAS
CAPACITY : 300 TR
TYPE : STEAM FIRED LITHIUM BROMIDE TYPE VAM
CHILLED WATER COOLING RANGE : 11.4 TO 7 DEG
CONDENSER WATER WARM RANGE : 31.6 TO 37.2 DEG
COOLING TOWER WATER FLOW RATE : 170 CMH
TEMPERATURE DROP : 5.4 DEG
HEAT REMOVAL : 918000 KCAL/HR
COOLING WATER PUMP CAPACITY & HEAD : 170 CMH, 35 M
CHILLED WATER PUMP CAPACITY & HEAD : 115 CMH,40 M
VAM RUNNING PARAMETERS
SOP OF VAM
8 – Then check the steam control valve is 100% open it will open
automatically.
9 – Then slowly charge the steam in the system by opening the manual
valve from PRDS and it should be less than 8ksc.
10 – After 10 min start the vacuum pump to maintain vacuum upto 400 Hg
11 – Check the parameters mentioned below
A - Steam pressure should be less than 8 ksc.
B – Steam temperature should be less than 170 deg.
C – Solution dilution temperature should be less than 75 deg.
D – Absorber level must be full.
E – High generator level should be ½ and low generator level ¼
F – The difference between high solution temperature and steam
temperature should be maintain between 20 to 30 deg.
G – Vacuum pump must be run atleast 1hr in each shift.
SHUTDOWN
PARTS
1 – SOLUTION PUMP
2 - GENERATOR
3 – CONDENSER
4 – EVAPORATOR
5 – ABSORBER
Here Lithium Bromide is used as Absorbent and the entire process is
almost takes in a complete vacuum.
1 . SOLUTION PUMP
A dilute lithium bromide solution in the bottom of absorber shell. From
here a solution pump moves the solution through shell & tube heat
exchanger for preheating.
PARTS
2 . GENERATOR
After Passing through the heat exchanger the dilute solution moves to
the upper shell.The solution surrounds the tubes consisting of steam
or hot water.The steam transfer heat into the pool of dilute lithium
bromide solution.Hence the solution gets heated & refrigerant vapour
upward to the condenser leaving the concentrated lithium bromide
solution.The concentrated lithium bromide solution moves down to the
heat exchanger where it is cooled by the weak solution being pumped
to the generator.
3 . CONDENSER
The refrigerant vapour moves to the condenser tube and condenses on
the tubes.The heat removed by the cooling water which flows inside the
tubes.As refigerant condenses it is collected at the bottom of the
condenser.
PARTS
4 . EVAPORATOR
The refrigerant liquid moves from the condenser upper shell to the
evaporator in lower shell.Then after it is sprayed over the evaporator
tubes.Due to extreme vacuum in the lower shell the refrigerant boils at
approximately 39 deg F.This will create refrigerant effect .
5 . ABSORBER
As the refrigerant vapour moves to the absorber from the
evaporator.The strong lithium bromide solution is sprayed top of the
absober tubes.The lithium bromide solution pulls the referigerant vapour
creating vacuum in the evaporator.The absorption of the refrigerant
vapour into lithium bromide solution also generate heat removed by the
cooling water.Now the dilute lithium bromide solution collects in the
bottom of the lower shell where it flows down to the solution pump.The
chilling cycle is completed and process begins once again.
Types of Vapour Absorption Systems
Hot
Steam Water
Driven Driven
Types of Vapour Absorption Systems
• Based On No of Stages :
;J;JKJKKKKKKKKKKK
to name a few……