Basic Concepts
Introduction of VPMF
Resource Proposing Process Drinking Water
Proposal of 50,000m3/d Drinking Water Plant
Water VPMF
Quality of Treated Water
@Coagulation
Co n ven tio n al
2~3 2.5 0.1~0.5NTU
Pro cess @Sedimentation
@Filtration
@ VPMF-MQ
Pro p o sin g
@VPMF-UQ 1 1 0.1~0.3NTU
Pro cess
@ Sand Filter
Co m p atib le 1.5~2 3 0.08~0.3NTU
Pro cess @ Hollow Fiber
Membrane
Comparison of Each Process
-.Weak in
ariation of
V
SS No Need -.Sludge Cake is
Co n ven tio n al -.Not easy to estimated 30~60
Pro cess adjust suitable T
on per day
Q’ty of Coagulants
-.CIP Waste W
Co m p atib le -,Frequent CIP must be disposed
in Serious V
ariation Frequent CIP 2~3years
Pro cess of SS
at high cost
Comparison of Each Process
-,Density Flow
Problem because
Of temperature
Co n ven tio n al Difference
NO NO
3
Pro cess -.Unstable seperation
(Weak floc)
Pro p o sin g NO NO
NO
Pro cess 1
-.Frequently -.Membrane is
Fouled by gel Plugged for long
Co m p atib le No in sur face of time(This can not 0.8~1.3
Pro cess membrane be recovered by
(CIP) CIP(exchange of
Module)
The Trouble on UF Membrane
Filtration
Backwashing
Filtration for the Industry water and the recycling of Industry wastewater
VPMF-SQ 0.5 ㎛ Pre-treatment for membrane filters(R/O, NF)
Treatment for sanitary wastewater and dual water through the direct filtration
VPMF-UQ 0.2 ㎛ Drinking & Potable Water Plant .Recycling of sewage effluent
Recycling of Industrial Wastewater
Process for 10,000m3/day Plant
Capacity
(m3/h)
418 418 418 418
Turbidity
(NTU)
30~500 10~30 0.1~ 0.3 0.08~0.2
E-Coli
(MPN/100ml) 1Mil. 0.2Mil. <150 No Detect
Detailed Specification
Flowrate per
70m3/hr 45m3/hr
Unit Module
Space : 12mW*13mL*2.5mH
Reference System List
Turbidity Turbidity
Plant Flow rate Note
(Raw W.) (Treated W)
Samnam
400m3/H 10~80NTU 0.5NTU
Chemicals
Banwol Plate
30m3/H 8~50NTU 0.7NTU
Coating
Hampyung
10m3/H 3~10NTU 0.1~0.2NTU
City Hall
Capacity 10,000m3/day
Item Coag/Sed/Sand Filter VPMF-HUQ
Space 10~20 1
Water Quality to be treated 0.5~1NTU 0.1~0.2NTU
Running Cost 2~3 1
Dehydrator of Sludge Need No Need
Density flow in Sedimentation Tank Occurs sometimes None
Assistant Analyzer for optimum coagulation Need No Need
Availability for variation of concentration Weak Strong
Maintenance Manpower Many Small
Control for q’ty of produced water Difficult Easy
Comparison with Membrane Process