(Electrical) 08EYTEE010(E-1)
INTRODUCTION
Rajasthan Rajya Vidyut Prasaran Nigam Limited (RRVPNL).A company under the Companies Act of 1956.Established on 19 July, 2000 by Govt. of Rajasthan under the provisions of the Rajasthan Power Sector Reforms Act, 1999 as the successor company of RSEB.An ISO 9001:2000 Certified Company.Registered Office at Vidyut Bhawan, Jyoti nagar Jaipur.
Incoming Feeder
800-400-200/1A, 5C, 20KA/1Sec. SF6 Circuit Breaker 245KV, 40KA/3Sec Wave Trap NA Line Isolator 800A SF6 CB Ratings Voltage 245KV Normal Current 2000A Lightning impulse withstand voltage 1050 KV Short circuit breaking current 40 KA Short circuit breaking duration 3 sec Gas Pressure SF6 (20 degree) 7 bar Air Pressure 20 bar Line Charging breaking current 125 A
OFAF Rated Power HV(MVA) 50 70 100 LV(MVA) 16.67 23.33 33.33 Rated Voltage HV(KV) 220 IV (KV) 132 LV(KV) 11 Rated Line Current HV(A) 131.37 183.92 262.74 IV(A) 218.95 306.53 437.90 LV(A) 874.97 1225.96 1751.44 No. of Phases 3 Max. Temp. rise Top Oil 40 over an ambient of Avg. Winding 55 50 degree Celsius Frequency 50 HZ
KV,800A C.B. 1250A,145KV C.T. 400-200-100/5A,3C WT NA It has total of 13 bays with 10 SF6 type of CB & 3 Air Blast CBs
132/33KV 40/50MVA 1
132/33KV 20/25MVA 2 132/11KV 10/12.5MVA 1 33/0.4kv 250KVA 1
At total of 18 bays with 11 Vacuum CB & 6 MOCB also 1 SF6 CB Equipment Ratings 33 KV C.T 500-250-125/1A, 2C 33 KV Isolator.
Bus 630A 33 KV Circuit Breaker 1250A, 36KV 33 KV capacitor Bank 38 KV, 7.2 MVAR LA 28KV 33 KV PT(ON BUS-I) 33KV/ /3*110V, 100VA
11 KV C.T 400-200-100/5A,2C LA 11KV 11 KV PT ON BUS(3PH) 11KV/110 V, 100VA 11 KV Isolator Bus 400A 11 KV switchyard consisted of 6 bays, with all Vacuum types of CB
HEERAPURA ARE:1.SANGANER 220 KV 2.HEERAPURA ITSELF 11KV 3.SODALA 132KV 4.DUDU 132KV 5.BAGAD 33KV 6.VIDAYADAR NAGAR 33KV ETC.
Visual checking for any hot spot Checking of air and gas leakage from the breaker Checking of air and gas pressure of breaker Checking of oil level from CT and CVT
Thermo vision scanning of conductor joints and attending to the hot spot available Breaker operation. Checking from local and remote Isolators operation from
remote and local. Measurement of specific gravity and voltage of 220 V D. C Battery cells.