Escolar Documentos
Profissional Documentos
Cultura Documentos
Selecting Extinguishers
The size and type of portable fire extinguisher is based on the total amount of Class A combustible materials, the total amount of Class B flammables, or, for some occupancies, a combination of both. For many areas, the extinguishing agent also must be compatible with energized electrical equipment.
Classification of Hazards
Light (Low) Hazard: Are locations in which the total amount of Class A combustible materials, including furnishings, decorations, and contents, is minor. These occupancies may include buildings or rooms occupied as offices, classrooms, assembly halls. Small amount of Class B flammables used in duplicating machines, art departments, and the like are included.
Distributing Extinguishers
Extinguishers should be placed in locations provide easy access and are readily free from temporary blockage. Near normal paths of travel, near exits and entrances. Mounted on walls, the operating instructions must face outwards, and can be removed easily.
Continue
Ext. with gross weight of no more than 40 pounds (18 kgs) should be installed so that the top of the extinguisher is not more than 5 feet above the floor. Ext. more than 40 pounds (except wheeled types) should be installed so that the top of the extinguisher is not more than 3.5 feet from the floor. In no case should the clearance between the bottom of the extinguisher and the floor be less than 4 inches.
2-A
2-A
4-A
Class A Rating 1A 2A 3A 4A
6000
10000
9000
11250
11250
11250
57
57
6A
10 A
11250
11250
11250
11250
11250
11250
57
57
20 A
30 A
11250
11250
11250
57
40 A
Example
Example
Area 67500 Ft
67500 / 6000 = 12 fire extinguishers 12 x 2A light hazard 12 x 4A ordinary hazard 12 x 6A extra hazard In this case both distribution and travel distance rules are fulfilled.
Example
CEN System
Example
A room has an area of 1000 square meters, so 1000 x 0.065 = 65 If you assume that 9 litre water extinguishers with a fire rating of 13A will be used. By dividing 65 by 13 you will get the number of extinguishers required. 65/13 = 5 ext.
5B 10 B 10 B 20 B
40B
80B
CEN System
2.
3. 4.
1. For single open topped containers see table 1, serial 1, the rating must be reached by each extinguisher provided. 2. For undivided groups see table 1, serial 2 3. For divided groups see table 1, serial 3 4. Spillage, see table 1, serial 4
Example 1
Take a single dip-tank with an area of 2 square meters. The recommended rating of extinguisher is given by: Column2: 50x2.0 = 100 i.e. 113B (foam only) Column3: 80x2.0 = 160 i.e. 183 (any other type) The minimum aggregate rating is recommended as: Column4: 150 x 2.0 = 300B (The minimum aggregate rating of 300B is not met by a single ext., therefore: 300 / 183 = 2 183B
Example 2
Take a bund measuring 2.47 square meters (1.3 x 1.9 m). What is the minimum rating extinguisher recommended?