PLANILHA DE CLCULO PARA REDE DE HIDRANTES


OCUPAO
ENDEREO
ESGUICHO
Dim
Presso
(mm)
(mca)
13.00
15.60
13.00
17.85
XXX
XXXX
XXX
XXXX

EDIFCIO RESIDENDICAL
RUA
TRECHO

VAZO
(l/min)

H2 - A
H1-A
A - SB
SB - EB

A. BOMBA DE INCNDIO
1. Principal
P.
15.94 mca
V.
269.76 l/min
POT.
1.36 CV
POT.
1.00 KW

130.34
139.42
269.76
269.76

P=
V=

CLASSIFICAO

MANGUEIRAS
Dim. Compr J.Unit.
(mm) (m)
40.00 30.00
0.087
40.00 30.00
0.098
XXX
XXX
XXXXX
XXX
XXX
XXXXX

2. Auxiliar
mca
l/min

J.Total
2.597
2.942
XXXXX
XXXXX

A-2

CLASSE RISCO
QUANT.HIDRANTES

TUBULAO
Dim. Compr. C.Equiv. C.Total
(mm)
(m)
(m)
(m)
65.0
0.20
18.30
18.50
65.0
2.70
18.30
21.00
65.0
8.50
12.50
21.00
65.0
1.20
7.50
8.70

B. Acionamento
1. Manual
XX
2.Automatizada

Reservatrio
Elevado
XXXX
Subterran.
Nvel do Solo

J.Unit.
0.015198
0.017215
0.055913
0.055913

BAIXO
16

J.Total
0.281154
0.361507
1.174173
0.486443

Reservatrio de Incndio
RI=
8.09
m
RI adotado=
10
m

_______________________________________________
Responsvel Tcnico

Pgina 1

Elev.
(m)
0.00
-2.70
-3.00
-1.20

Plan1

Presso
(mca)
18.4781
18.4532
16.6523
15.9387

Pgina 2