Barragem CLOROÇÃO
SEMANA AMONIA FERRO MANGANES ORP CLORO LIVRE
DATA
2020
TOTAL
kg/h ppm ppm ppm % m3/h m3/h LBS/DIA ppm ppm ppm mV ppm
1 1/3/2020 4.77 3.18 3.08 670 100% 7.10 1500 3000 0.47 678
4 1/21/2020 3.14 2.36 2.36 439 99% 7.10 1330 2500 0.58 685
5 1/31/2020 1.50 1.13 0.00 250 100% 6.00 1330 1400 0.58 685
JAN-20 JAN-20 3.14 2.22 1.81 453.00 149% 6.73 1387 2300 0.54 683
2- TQ01F 3-ETA CLARIFICADA 5-ENTRADA-RAF-FILTRADA
MANGANES MANGANES FERRO RESIDUAL ORP CLORO LIVRE MANGANES MAGANES FERRO AMONIA ORP MANGANES MANGANES
TOTAL SOLUVEL ClO2 TOTAL SOLUVEL TOTAL SOLUVEL
ppm ppm ppm ppm mV ppm ppm ppm ppm ppm mV ppm ppm
0.54 0.02 0.10 656 0.52 0.01 768 0.01 0.01
0.55 0.02 0.00 693 0.50 0.01 807 0.01 0.01
0.55 0.02 0.00 693 0.50 0.01 807 0.01 0.01
FERRO AMONIA
3/16/2020
3/27/2020
4/2/2020
4/9/2020
4/16/2020
4/23/2020
5/12/2020
5/13/2020
5/14/2020
5/15/2020
5/18/2020
5/19/2020
5/20/2020
5/21/2020
5/25/2020
5/27/2020
5/29/2020
6/5/2020
6/9/2020
6/12/2020
6/16/2020
6/23/2020
6/25/2020
6/30/2020
Ação
FABIO DE FÉRIAS VISITA DO TÉCNICO FELIPE RODRIGUES PARA ACONPANHAMENTO DA PLANTA DE DIÓXIDO DE CLORO
RETORNO DE FÉRIAS FÁBIO - DESCARREGAMENTO DE ÁCIDO SULFURICO NA PLANTA - ANALISES DE MANGANÊS E EFICIENCIA
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS TESTE DE PRODUÇÃO MAXIMA
REALIZADO LIMPEZA DA AREA E CONTENÇÕES
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZADO SUBSTITUIÇÃO DE DIAFRAGMA DA BOMBA DE DOSAGEM DO ACIDO SULFURICO LIMPEZA DE FILTROS
REALIZADO APRESENTAÇÃO DA PLANTA DE DIÓXIDO DE CLORO PARA ENG DE OTIMIZAÇÃO ( Luciana) E VERIFICADO CALIBRA
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
SOLICITAÇÃO DE ATENDIMENTO EMERGENCIAL RUPTURA DE LINHA RIGIDA SAIDA DE DIÓXIDO DE CLORO MOTIVO ERRO OPERACIONA
AUMENTAR A ATENÇÃO DOS OPERADORES " AREX" QUE PARTEM O GERADOR FORA DO HORARIO DE ATENDIMENTO DA ECOLAB PRO
FOI OBSERVADO QUE O CHILLER TAMBEM FOI DANIFICADO NO MESMO DIA
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS POR SOLICITAÇÃO DA REGAP
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS POR SOLICITAÇÃO DA REGAP
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
REALIZAÇÃO DE LIMPEZA DE FILTROS E VERIFICAÇÃO DE CALIBRAÇÃO DAS BBAS DOSADORAS ANALISES DE MANGANÊS
GERADOR DE DIÓXIDO DE CLORO PARADO PARA TESTE COM CLORO GÁS
GERADOR DE DIÓXIDO DE CLORO PARADO PARA TESTE COM CLORO GÁS - RECEBIMENTO DE ÁCIDO SULFURICO 98% -I 8,83
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - LIMPEZA DA PLANTA DE DIÓXID
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
GERADOR DE DIÓXIDO DE CLORO PARADO DEVIDO BAIXA DEMANDA DE ÁGUA TRATADA - TESTES DE ÁGUA PARA ACOMP
Vazão PRÉ
Produção de ClO2 Demanda Concetração Eficiencia MOTIV Barragem CLOROÇÃO 1-BRUTA 2- TQ01F
20 0 0 20 0 20 ia 20 20 20 0 20
N- -2 -2 R- -2 N- ed -2
EV AR AI 20 20 20 AN 20
JA F M AB M JU M 3/ 1/ 1/ J 7/
1/ 1/
2
1/
3 2/ 2
Demanda X Dosagem ClO2 Contrato 4600545279 Demanda X Dosagem (ppm) JAN 2020 D
6.00 5.00 5.00
5.50 4.50 4.50
5.00
4.00 4.00
4.50
4.00 3.50 3.50
3.50 3.00 3.00
3.00
2.50 2.50
2.50
2.00 2.00 2.00
1.50 1.50 1.50
1.00
1.00 1.00
0.50
0.00 0.50 0.50
a
-2
0 20 20 -2
0
-2
0
-2
0
ed
i
N V- AR
-
BR AI N 0.00 0.00
JA FE M A M JU M
1/3/2020 1/21/2020 1/31/2020 JAN-20 2/7/2020 2
Dosagem de Cloro Gás Contrato 4600545279 (Lbs/dia) Dosagem de Cloro Gás (Lbs/dia)
JAN 2020
3000
2750 3000 3000
2500 2750 2750
2250
2500 2500
2000
1750 2250 2250
1500 2000 2000
1250
1000 1750 1750
750 1500 1500
500
1250 1250
250
0 1000 1000
0 0 0 20 0 20 ia
-2 -2 -2 R- -2 N- ed 750
N EV AR AI 750
JA F M AB M JU M
500 500
250 250
0 0
1/3/2020 1/21/2020 1/31/2020 JAN-20 2/7/2020 2
Demanda X Dosagem (ppm) FEV 2020 Demanda X Dosagem (ppm) MAR 2020
5.00 5.00
4.50 4.50
4.00 4.00
3.50 3.50
3.00 3.00
2.50 2.50
2.00 2.00
1.50 1.50
1.00 1.00
0.50 0.50
0.00 0.00
2/7/2020 2/14/2020 2/21/2020 2/28/2020 FEV-20 3/6/2020 3/13/2020 MAR-20
20
20
0 0
2/
2/7/2020 2/14/2020 2/21/2020 2/28/2020 FEV-20 3/6/2020 3/13/2020 MAR-20 4/
4
OXIDAÇÃO DE MANGANÊS (ppm) OXIDAÇÃO DE MANGANÊS (ppm) OXID
FEV 2020 MAR 2020 ABR
0.70 0.70 0.70
0.65 0.65 0.65
0.60 0.60 0.60
0.55 0.55 0.55
0.50 0.50 0.50
0.45 0.45 0.45
0.40 0.40 0.40
0.35 0.35 0.35
0.30 0.30 0.30
0.25 0.25 0.25
0.20 0.20 0.20
0.15 0.15 0.15
0.10 0.10 0.10
0.05 0.05 0.05
0.00 0.00 0.00
750
750 750
700
700 700
650
ORP (mV) ORP (mV)
FEV 2020 MAR 2020
800 800 800
750
750 750
700
700 700
650
650 650 600
500
550 550
450
500 500
400
450 450
350
ORP TQ01F ORP Filtrada ORP ETA ORP TQ01F ORP Filtrada ORP ETA
Preparo da solução de Dióxido de Cloro para decobrir o volume de ClO2 para agua bruta Calculo de Eficiencia:
Eficiencia= Real/Teorica
Vazão da Barragem (M3/H) 1400 eT 327
Produção de ClO2 ( Kg/H) 1.83 eR 330
Concentração Real ClO2 (ppm) 330 e% 101%
Vazão de Motivante ( M3/H) 5.60
DEMANDA 2.99
Preparo da solução de Dióxido de Cloro para decobrir o volume de ClO2 para agua bruta Calculo de Eficiencia:
Eficiencia= Real/Teorica
Vazão da Barragem (M3/H) 1400 eT 231
Produção de ClO2 ( Kg/H) 1.50 eR 232
Concentração Real ClO2 (ppm) 232 e% 101%
Vazão de Motivante ( M3/H) 6.50
DEMANDA 2.99
Preparo da solução de Dióxido de Cloro para decobrir o volume de ClO2 para agua bruta Calculo de Eficiencia:
Eficiencia= Real/Teorica
Vazão da Barragem (M3/H) 1000 eT 259
Produção de ClO2 ( Kg/H) 1.50 eR 261
Concentração Real ClO2 (ppm) 261 e% 101%
Vazão de Motivante ( M3/H) 5.80
DEMANDA 4.09
Preparo da solução de Dióxido de Cloro para decobrir o volume de ClO2 para agua bruta Calculo de Eficiencia:
Eficiencia= Real/Teorica
Vazão da Barragem (M3/H) 1000 eT 154
Produção de ClO2 ( Kg/H) 1.00 eR 154
Concentração Real ClO2 (ppm) 154 e% 100%
Vazão de Motivante ( M3/H) 6.50
DEMANDA 3.56
Preparo da solução de Dióxido de Cloro para decobrir o volume de ClO2 para agua bruta Calculo de Eficiencia:
Eficiencia= Real/Teorica
Vazão da Barragem (M3/H) 1000 eT 172
Produção de ClO2 ( Kg/H) 1.00 eR 173
Concentração Real ClO2 (ppm) 173 e% 100%
Vazão de Motivante ( M3/H) 5.80
DEMANDA 6.38
Data: 3/6/2020
ficiencia:
eal/Teorica
9:00 eficiencia %= 101%
13:00 eficiencia %=
Média eficiencia %= 101%
Data: 3/13/2020
ficiencia:
eal/Teorica
9:00 eficiencia %= 101%
13:00 eficiencia %=
Média eficiencia %= 101%
Data: 4/2/2020
ficiencia:
eal/Teorica
9:00 eficiencia %= 101%
13:00 eficiencia %=
Média eficiencia %= 101%
Data: 4/9/2020
ficiencia:
eal/Teorica
9:00 eficiencia %= 100%
13:00 eficiencia %=
Média eficiencia %= 100%
Data: 4/16/2020
ficiencia:
eal/Teorica
9:00 eficiencia %= 100%
13:00 eficiencia %=
Média eficiencia %= 100%
ENDEREÇO
CLIENTE CLIENTE INTERNO
APLICAÇÃO
RESPONSAVEL
N° SE DERIE MODELO
ANO FABRICAÇÃO DATA DE INSTALAÇÃO
PRESSÃO DE ENTRADA MOTIVANTE EFICIENCIA REAL
VAZÃO DE AGUA MOTIVANTE EFICIENCIA TEORICA
PRODUÇÃO DE ClO2 (KG/h) TIRAR FOTOS DAS TELAS
VÁCUO MODELO DAS BOMBAS DE DOSAGEM
NIVEIS DE TANQUE PURATE
NIVEIS DE TANQUE ÁCIDO
LISTA DE FALHAS
1
2
3
4
5
LIMPEÇA E INSPEÇÃO DOS FILTROS DA OSMOSE REVERSA
OSMOSE 1 OSMOSE 2
REALIZADO REALIZADO
SIM NÃO SIM NÃO
OBS:
OBS:
OBSERVAÇÕES E RECOMENDAÇÕES
OBS.:
RELATÓRIO DE INSPEÇÃO E MANUTENÇÃO PLANTA DE DIÓXIDO DE CLORO - PETROBRAS REGAP
DATA
INSPEÇÃO DE CALIBRAÇÃO DAS BOMBAS DOSADORAS - PROVETAS
OBS:
OBS: