Escolar Documentos
Profissional Documentos
Cultura Documentos
QD1
4 9w
5 1
1
3
3g
3g Conduto ø1"
2#25(25)25 mm² DIAGRAMA UNIFILAR TRIPOLAR
3 4 16w 4 3 16w 5
QD1
16w 16w
1550w
3a 3a 3e 3f 50 A
3a 3e 5 5 25A 15A
5 6 25 A
6,0mm² 2,5mm²
QUADRO DE DISTRIBUIÇÃO
4 4 3f 6 2 6,0 CT1 CT6
3 16w
Chuveiro 2500 W 1
6 25 A 25A 15A
1 2 3 3h 6,0
CT2 6,0mm² CT7 2,5mm²
3 2 1550 W Central de ar
3h 6 15 A
3c 7 8 7 2,5
3 6 15A 15A
16w 16w 3 16w 8 Iluminação 265 W 3 CT3 2,5mm² CT8 2,5mm²
15 A 2#25,0mm²
3c 3c 3c
3b 3 2,5 M
3 4 300 W Tomadas 2#25,0mm² 2#25,0mm² 15A
3 15 A
CT4 2,5mm²
3 2,5
16w 16w 3i 16w Tomadas 700 W 5
3b 3b 3i 15 A 15A
3 2,5 CT5 2,5mm²
QD1 6 800 W Tomadas
7 15 A
16w 2,5
8
3d Tomadas 300 W 7
16w 7 15 A
2,5
3j 3j 7 8 800 W Tomadas
7
3 3
8 Potência Instalada (W)
A 3.290
B 3.925
8 8 Total 7.215
16w
VERMELHO
3k
QUADRO DE CARGAS - QD 02
Azul Claro
16w 3k
PRETO
3d 3d 8
A B N Verde
LUMINÁRIAS(W) TOMADAS (W) TOTAL SEÇÃO PROTEÇÃO FASE
8 CIRC. (W) (mm²) (A) ABC
06 09 16 100 1550 2500
3
CT- 01 01 1550 6,0 2x25A AB
QUADRO DE CARGAS - QD 01 CT- 02 01 2500 6,0 2x25A AC
CT- 03 01 1550 6,0 2x25A BC
16w LUMINÁRIAS(W) TOMADAS (W) TOTAL SEÇÃO PROTEÇÃO FASE CT- 04 01 1550 6,0 2x25A AB
3d CIRC.
09 16 25 100 1550 2500 (W) (mm²) (A) ABC CT- 05 01 1550 6,0 2x25A AC
CT- 01 01 2500 6,0 2x25A AB CT- 06 08 00 14 272 2,5 1x15A A
CT- 02 01 1550 6,0 2x25A AB CT- 07 10 1000 2,5 1x15A B
CT- 03 01 16 00 265 2,5 1x15A A CT- 08 08 800 2,5 1x15A C
7 CT- 04 03 300 2,5 1x15A B CT- 09 08 800 2,5 1x15A A
7
7 6 16w 6 16w 7 CT- 05 07 700 2,5 1x15A A CT- 10 12 1200 2,5 1x15A B
6b 6c 6 7
16w 16w CT- 06 08 800 2,5 1x15A B CT- 11 11 1100 2,5 1x15A C
7 6a 6d
7 CT- 07 03 300 2,5 1x15A A CT- 12 01 1550 6,0 2x25A BC
800 2,5 1x15A B CT- 13 01 1550 6,0 2x25A AB
6cd CT- 08 08
7 6ab
AB TOTAL 08 00 14 49 06 01 16.972 10,0 3x50A ABC
TOTAL 01 16 00 29 01 01 7.215 10,0 2x50A
6w 6 6w 6w
7 6o 6p 6q 7
1550w
7
8 11 6 1
DIAGRAMA MULTIFILAR TRIPOLAR
8
QD2
16w 8 16w 6mn
6 Conduto ø1"
6e 6f 6n 3#25(25)25 mm²
QUADRO DE DISTRIBUIÇÃO
1
8 6o
2 3 6 6m 2 6,0
25A 15A
Central de ar 1550 W 3
9 6 3 25 A 3#25,0mm² CT3 6,0mm² CT11 2,5mm²
6 4 13 11 6 6,0
5 11 12 Central de ar
M
16w 11 4 1550 W 3#25,0mm² 3#25,0mm² 25A 25A
6 8 6mn 25 A CT4 6,0mm² CT12 6,0mm²
6g 6,0
9 8 9 2500w Central de ar 1550 W 5
9 10 25A 25A
6 6 15 A
CT5 6,0mm² CT13 6,0mm²
2,5
9 6 6 5 9w
6w 5 6w 6w 2 6 272 W Iluminação
6p 6l 15 A 15A
5 6o 9 8 8 6q 6l 2,5mm²
9 2,5
1550w
6opq CT6
4 3 Tomadas 1000 W 7
6 15 A
6 12* 6 2,5 15A
10 2,5mm²
1550w
11 CT7
8 800 W Tomadas
15 A
9 6k 2,5 15A
6ij Tomadas 800 W 9 CT8 2,5mm²
11 15 A
2,5
10 1200 W Tomadas
15 A
10 6
10 16w 16w 11 16w 3 2,5 PROJETO:
16w 10 Tomadas 1100 W 11
6i 6j 10 11 6k
6h
10
10 11
11
6,0
25 A
RESIDÊNCIA UNIFAMILIAR
12 1550 W Tomada p/ academia
6gh 25 A
12 lustre 4 11 6,0
PROJETO: ASSUNTO: PRANCHA:
INSTALAÇÕES
11
6k Tomada p/ academia 1550 W 13 INSTALAÇÃO ELÉTRICA TÉRREO 01/05
1550w
Azul Claro
MARROM
Total 16.972
PRETO
PHALOMA CARVALHO
PROPRIETÁRIO
MARÇO/2023
ESCALA:
INDICADA
ÁREA TOTAL CONSTRUÍDA:
704,00m²
DESENHO:
GERALDO FILHO
ESCALA 1/50 END. DA OBRA:
25A 15A
CT1 6,0mm² CT12 2,5mm²
50 A
25 A 25A 15A
6,0 CT2 6,0mm² CT13 2,5mm²
Central de ar 1550 W 1
25 A
6,0 25A 15A
QUADRO DE DISTRIBUIÇÃO
2 2500 W Chuveiro CT3 6,0mm² CT14 2,5mm²
25 A
13 12 6,0
Chuveiro 2500 W 3 25A 15A
16w 16w 16w 25 A CT4 6,0mm² CT15 2,5mm²
6,0
12a 12abc 12b 12c 4 1550 W Central de ar
13 13 12 13 25 A 25A 15A
6,0 CT5 6,0mm² CT16 2,5mm²
Chuveiro 2500 W 5 3#25,0mm²
25 A M
6,0 25A 15A
1550w
16 3#25,0mm² 3#25,0mm²
1550w
VERMELHO
18 4
Azul Claro
MARROM
17
PRETO
12j 5 7 12p 21
Total 29.844
17 19 12 6 21
12 8 A B C N
6w 6w 6w 21
1550w
17 12k 12l 12m 20
5
17 17 6
7 21 FIAÇÃO QUE VEM PELO CHÃO
18 12 6w 19 6w QUADRO DE CARGAS - QD 03
18 12v 12v INTERRUPTOR SIMPLES
18 19 LUMINÁRIAS(W) TOMADAS (W) TOTAL SEÇÃO PROTEÇÃO FASE
12q 19 CIRC.
1550w
ESCALA 1/50
PHALOMA CARVALHO
PROPRIETÁRIO
CX. Nº 01
TV TV
TV TV
TV
TV
CX. Nº 02
CX. Nº 01
TV TV PROJETO:
RESIDÊNCIA UNIFAMILIAR
PROJETO: ASSUNTO: PRANCHA:
INST. TELEFÔNICA TÉRREO INST. TELEFÔNICA 1º PAVIMENTO ENGº CIVIL GERALDO FILHO - CREA/RR 092043745-1
AUTOR E RESP. TÉCNICO
PHALOMA CARVALHO
PROPRIETÁRIO
Ø25mm
RG-02 RG-01 RG-03
Ø3/4" Ø3/4" Ø3/4"
Ø25mm Ø25mm
PIA
Ø32mm
Ø1/2" LV VS DH CH
RG - REGISTRO DE GAVETA
Ø1/2" Ø1/2" Ø1/2" Ø1/2"
Ø32mm
Ø32mm
CX. D´ÁGUA Ø32mm
CAP. 500 L EXTRAVASOR
Ø32mm Ø32mm
LV - LAVATÓRIO
VS - VASO SANITÁRIO
Ø32mm
CH - CHUVEIRO
PC - PIA DE COZINHA
RG-04
Ø3/4"
DH - DUCHA HIGIÊNICA
Ø25mm
TQ
Ø1/2"
DESCE Ø32mm
ML
Ø1/2"
Ø32mm
Ø25mm Ø25mm
RG-02 RG-04
Ø3/4" Ø3/4"
LV VS DH CH CH DH VS LV
Ø1/2" Ø1/2" Ø1/2" Ø1/2" Ø1/2" Ø1/2" Ø1/2" Ø1/2"
Ø25mm Ø25mm
LV VS DH CH
Ø1/2" Ø1/2" Ø1/2" Ø1/2"
RG-03
Ø3/4"
RG-05
Ø3/4"
CH
Ø1/2"
DH VS LV
Ø1/2" Ø1/2" Ø1/2" TQ - TANQUE DE LAVAR ROUPA
Ø32mm
Ø32mm
VEM DO HIDROMETRO
Ø32mm
Ø32mm
RG-03
Ø3/4" PIA
Ø1/2"
Ø25mm
RECEBE PVº 1
DESCE
Ø32mm
Ø32mm
Ø32mm
REGISTRO
GERAL
RG-02 Ø3/4"
Ø3/4"
PIA CX. D´ÁGUA Ø32mm
Ø25mm
Ø1/2"
CAP. 1000 L EXTRAVASOR
Ø32mm
RECEBE PVº 1
Ø25mm SHAFT
SOBE
Ø25mm
Ø50mm
VEM DO HIDROMETRO
RG-01
Ø25mm
RG-01
Ø3/4"
Ø3/4"
Ø32mm
Ø25mm
LV VS DH CH
Ø1/2" Ø1/2" Ø1/2" Ø1/2" Ø32mm
CX. D´ÁGUA
Ø32mm
CAP. 1000 L
RECEBE PVº 1
SOBE
Ø25mm
VEM DO HIDROMETRO
PROJETO:
RESIDÊNCIA UNIFAMILIAR
PROJETO: ASSUNTO: PRANCHA:
RS - RALO SIFONADO
CS - CAIXA SIFONADA
Ø100 Ø100 Ø100 Ø100
CI CI CI CI
i=1% VAI PARA O ESGOTO i=1% i=1% i=1% CV - COLUNA DE VENTILAÇÃO
CG
0
10
Ø
Ø50
Ø40
Ø50
Ø4
0
Ø40
1,30
0,10 1,10 0,10
Vem da FOSSA
Ø 100mm
Ø100
i=1%
Ø100mm
Ø100
i=1%
1,60
Ø50 CI
SHAFT
DESCE
SHAFT
DESCE 1,40 0,10
Ø50
Ø1
00
Ø50 Ø50
00
0,10
Ø1
Ø100
Ø40 Ø40
i=1%
40
Ø
Vem da CI
Ø50
40
Ø
Ø100mm
Ø40
Ø40
Ø100
CI
i=1%
CI
0,80
1,00
0
Ø
10
10
Ø50
Ø50
Ø
0
CI
Ø40
Ø40
0,10
Ø
10
0
40
Ø
40
Ø40 Ø40 Ø
CG
Ø100
i=1%
SUMIDOURO - PLANTA BAIXA
Ø1
00
Ø100
i=1%
ESC.: 1/20
Ø
50
CG
N. Terreno
(Ø100) 2 TUBOS
CI (Ø100) 2 TUBOS
BOS
(Ø50) 1 TU SHAFT CI
(Ø50) 1 TUBO
Ø
50
Ø40
2,50
Alvenaria
Ø
40
rebocada
Ø100
i=1%
Ø100
SHAFT
i=1%
DESCE 00
Ø1
Ø40
Ø50
Ø50
FOSSA SÉPTICA- CORTE
ESC.: 1/20
Ø40
Ø100
N. Terreno
Ø
40
Ø40 CI
Ø50
SHAFT
Ø100
CI
Alvenaria
Ø50
chapiscada 3,00
SUMIDOURO- CORTE
ESC.: 1/20
PROJETO:
RESIDÊNCIA UNIFAMILIAR
PROJETO: ASSUNTO: PRANCHA: