CONTROLE ESTATSTICO DA QUALIDADE DO CONCRETO

DETERMINAO DA RESISTNCIA COMPRESSO AXIAL SIMPLES (MPa)


AVALIAO PELO MTODO DA ACI 214/2002
CLASSE:

C1

01

LOTE:

Fck DE PROJETO:

Nmero

Concreto Fresco

25.0 MPa

IDADE DE CONSIDERADA: 28 DIAS

Rev: 00

Resist. Compresso (MPa)


Amp.
Mdia
28 dias

Estrutura

39.7

0.2

FS

(CTS3-3104/10) Unidade 3 2 Estgio envol. Da Caixa Espiral

38.8

31.1

14.7

FS

(CTS3-3105/10) Uni. 3 2Estgio Envolvimento Cx Espiral

25.0

28.0

42.7

0.7

FS

(CTS3-3120/10) Unidade 3 2 Estgio env. da Caixa Expiral

16.7

22.8

30.9

40.1

0.4

FS

(CTS3-3121/10) Uni. 2 Vigas V1 Linha C

2,313

11.8

23.2

30.3

33.5

2.6

FS

(CTS3-3129/10) Uni. 3 Plataforma dos Transformadores

2.6

2,345

17.9

28.2

30.2

36.6

0.2

FS

(CTS3-3137/10) Uni. 1 Laje cobertura do Gerador

13.0

2.9

2,322

13.1

23.2

31.5

46.0

3.4

FS

(CTS3-3232/10) Unidade 3 Plataforma dos Transformadores

9/14/2010

14.5

2.8

2,321

12.8

26.2

29.6

40.8

3.0

FS

(CTS3-3241/10) Unidade 2 Linha Transformadores

19.C1.3-BS

10/5/2010

2.6

2,361

13.7

24.0

28.4

39.1

0.1

AS

(CTS3-3429/10) UNID 1 UNID 2 UNID 3 VIGAS PRE MOLDADAS

2269

19.C1.3-BS

10/7/2010

13.0

3.4

2,322

11.4

20.8

33.1

35.8

0.4

FS

(CTS3-3441/10) CF 3LAJE 164,04 NA LINHA B

2281

19.C1.3-BS

10/8/2010

13.0

2.5

2,361

8.3

16.3

28.6

28.2

1.8

BD

(CTS3-3459-10) ENVELOPES 4 E 5

2293

19.C1.3-BS

10/16/2010

13.0

2.6

2,368

10.3

16.4

22.8

39.7

0.9

FS

(CTS3-3480/10) UM.3 VIGAS V5 EIXO7 E PILARES

2301

19.C1.3-BS

10/16/2010

11.0

2.5

2,374

17.5

27.2

38.8

5.0

FS

(CTS3-3991/10) UNID 2 PILARES E VIGAS

2319

19.C1.3-BS

10/22/2010

15.0

4.0

2,276

10.9

19.2

27.2

39.0

0.8

FS

(CTS3-4036/10) UNIDADE 3 VIGAS LINHA C

2349

19.C1.3-BS

10/28/2010

16.0

3.8

2,237

9.1

12.4

33.3

37.6

2.5

AS

(CTS3-4092/10) UNID.2 VIGAS PREMOLDADAS VP1 E VP2

2355

19.C1.3-BS

10/29/2010

19.0

3.6

2,315

14.8

20.8

32.5

39.2

3.3

FS

(CTS3-4101/10) UNID.3 VIGAS V1D EIXOS 6 E 7 LINHA C

2359

19.C1.3-BS

10/30/2010

13.5

2.5

2,349

12.7

20.9

36.4

42.6

3.4

FS

(CTS3-4108/10) UNID 3 VIGA ENTRE OS EIXOS 6 E 7 LINHA B

2363

19.C1.3-BS

11/1/2010

12.0

3.0

2,280

17.2

30.8

36.4

1.6

FS

(CTS3-4114/10) UNIDADE 3 LAJES DOS PREMOLDADOS

2389

19.C1.3-BS

11/9/2010

16.0

3.2

2,318

16.2

23.3

36.6

42.5

2.5

FS

(CTS3-4179/10) UNID.3 LINHA DE TRANSMIO PILARES E VIGAS

2403

19.C1.3-BS

11/12/2010

13.0

3.0

2,348

20.7

32.9

40.9

44.4

7.9

FS

(CTS3-4208/10) UNIDADE 2 ESCADA DE ACESSO DO GERADOR

2439

19.C1.3-BS

11/24/2010

12.5

3.3

2,349

20.6

32.0

33.6

40.5

2.8

BD

(CTS3-4283/10) ENVELOPES 5,6 E 7

13.7

3.1

2324

13.6

22.7

31.6

38.8

2.8

Dosagem

Data de
Moldagem

28

90

2109

19.C1.3-BS

8/26/2010

13.5

3.4

2,291

11.1

26.0

32.2

2111

19.C1.3-BS

8/26/2010

13.5

3.4

2,291

12.9

28.1

2115

19.C1.3-BS

8/27/2010

13.5

3.0

2,320

12.7

2117

19.C1.3-BS

8/28/2010

11.5

3.0

2,338

2121

19.C1.3-BS

8/28/2010

14.0

3.2

2147

19.C1.3-BS

9/2/2010

14.0

2177

19.C1.3-BS

9/12/2010

2179

19.C1.3-BS

2261

Srie

Consistncia
(cm)

Resultados Mdios

Ar
Massa
Incorp. Unit.
(%) (kg/m)

Idade (dia)

ESTATSTICA DO RESULTADO
Dentro do Lote (Resistncia)

Local de Aplicao

RESISTNCIA CARACTERSTICA ESTIMADA

Dentro do Ensaio (Amplitude)

Mdia (MPa)

31.6

Mdia (MPa)

2.78

Numero de Amostras

Desvio Padro (MPa)

4.2

0,8865 Mdia (MPa)

2.46

Coeficiente t

1.711

7.80

fck Estimado (MPa)

24.4

Coeficiente de Variao (%)

Coeficiente de Variao (%)


13.3
ACI 214 (PRTICA RECOMENDADA)

Dentro do Lote
Padro Controle

C.V. (%)

Excelente

< 7,0

21

CONCLUSO DO LOTE NA IDADE DE CONTROLE

Dentro do Ensaio

Conforme (fck est/fck proj > 1,0)

D. Padro (MPa)
< 2,80

Padro Controle

Coeficiente de Variao (%)

No Conforme (fck est/fck proj < 1,0)

Excelente

< 3,0

Lote Parcial

Muito Bom

7,0 a 9,0

3,0 a 4,0

9,0 a 11,0

2,8 a 3,4
3,4 a 4,1

Muito Bom

Bom

Bom

4,0 a 5,0

Conforme (fck est/fck proj > 1,0)

Razovel

11,0 a 14,0

4,1 a 4,8

Razovel

5,0 a 6,0

No Conforme (fck est/fck proj < 1,0)

Pobre

> 14,0

> 4,8

Pobre

> 6,0

Lote Parcial

CONCLUSO DO LOTE NA IDADE DE 90 DIAS

1.26

Tendncia de Crescimento do fck Estimado

Acompanhamento das Resistncias Simples


60

60

50

50

Resistncia (MPa)

Resistncia Simples
(MPa)

0.98

40
30
20
10

y = 7.1237ln(x) - 0.0569
R = 0.9979

40

30
20

10
0

11

13

15

17

19

21

23

25

27

29

14

21

28

N de Amostras
3 dias

Observao:

7 dias

28 dias

fcj Requerido (33,2 MPa)

90 dias

35

42 49 56
Idade (dia)

63

70

77

fck Requerido (25,0 MPa)

fck estimado

Idade de Controle

Curva de Tendncia

84

91

CONTROLE ESTATSTICO DA QUALIDADE DO CONCRETO


DETERMINAO DA RESISTNCIA COMPRESSO AXIAL SIMPLES (MPa)
AVALIAO PELO MTODO DA ACI 214/2002
CLASSE:

C1

02

LOTE:

Fck DE PROJETO:

Nmero

Concreto Fresco
Dosagem

Srie

Data de
Moldagem

Consistncia
(cm)

25.0 MPa

IDADE DE CONSIDERADA: 28 DIAS

Rev: 00

Resist. Compresso (MPa)

Ar
Massa
Incorp. Unit.
(%) (kg/m)

Idade (dia)
3

28

90

Amp.
Mdia
28 dias

Estrutura

Local de Aplicao

2471

19.C1.3-BS

12/11/2010

14.0

2.8

2,287

18.6

27.1

32.0

35.7

3.4

FS

(CTS3-4399/10) UNID. 03 SUP DAS LINHAS

2499

19.C1.3-BS

12/22/2010

13.0

2.7

2,346

23.0

27.5

41.8

46.7

2.1

FS

(CTS3-4461/10) Caixa d gua

2511

19.C1.3-BS

1/11/2011

14.0

1.9

2,386

22.6

30.5

46.9

45.9

2.8

FS

(CTS3-4504/11) UNIDADE 3 LAJE DO GERADOR

2521

19.C1.3-BS

1/15/2011

19.0

2.0

2,373

17.3

23.0

32.0

37.1

0.3

FS

(CTS3-4526/11) UNIDADE 3SUPORTE DAS LINHAS DE TRANSIO

2557

19.C1.3-BS

1/29/2011

12.0

1.3

2,342

24.4

30.9

42.5

49.1

1.7

AM

(CTS3-4602/11) CAIXA D'AGUA

2601

19.C1.3-BS

2/18/2011

15.0

3.2

2,346

20.8

26.8

37.4

43.6

0.8

FS

(CTS3-4696/11) Suporte das linhas de transmisso

2603

19.C1.3-BS

2/18/2011

13.0

2.7

2,366

22.6

25.1

26.6

43.6

4.3

AM

(CTS3-4670/11) RESERVATORIO DE AGUA POTAVEL

2611

19.C1.3-BS

2/24/2011

14.0

3.8

2,307

24.5

27.1

40.4

49.0

0.1

AS

(CTS3-4713/11) VIGAS COMPLEMENTARES DOS TRILHOS DO PRT

2617

19.C1.3-BS

3/2/2011

15.0

2.9

2,340

15.3

27.4

44.9

48.8

2.6

BD

(CTS3-4734/11) ENVELOPES E8,E8A,E9,E9A

2625

19.C1.3-BS

3/4/2011

14.0

2.9

2,347

12.9

25.3

39.0

44.7

1.2

FS

(CTS3-4750/11) LAJE SOBRE PREMOLDADOS MONTANTE LINHA A

2665

19.C1.3-BS

3/25/2011

14.0

2.2

2,354

17.1

24.4

31.8

41.9

0.4

FS

(CTS3-4886/11) SALA DO GRUPO GERADOR DIESEL

2689

19.C1.3-BS

4/2/2011

15.0

2.2

2,341

14.9

23.3

36.4

41.6

1.2

BD

(CTS3-4946/11) CAIXA DE PASSAGEM 7,7 A 8 E 8A

2707

19.C1.3-BS

4/8/2011

14.0

3.0

18.5

28.4

38.9

44.9

1.5

BD

(CTS3-4993/11) ENVELOPES E10 E 10A

2725

19.C1.3-BS

4/19/2011

14.0

2.2

2,350

20.0

25.1

43.8

50.1

2.0

BD

(CTS3-5058/11) ENVELOPES E11 E E11A

2743

19.C1.3-BS

4/29/2011

13.0

2.1

2,363

15.8

26.6

41.3

48.0

2.3

FS

(CTS3-5903/11) SALA DO GRUPO GERADOR DIESEL

2747

19.C1.3-BS

4/30/2011

14.0

2.9

2,343

17.4

27.0

39.1

48.8

0.8

BD

(CTS3-5111/11) ENVELOPES E12 E E12A

2751

19.C1.3-BS

4/30/2011

13.0

2.2

2,343

17.2

27.4

42.6

50.5

0.8

BD

(CTS3-5113/11) ENVELOPES E13 E E131

2753

19.C1.3-BS

5/3/2011

14.0

2,340

20.9

26.9

52.0

57.5

1.2

BD

(CTS3.5423.11) ENVELOPE E28

2769

19.C1.3-BS

5/6/2011

14.0

2.5

2,346

18.9

31.7

43.9

51.0

1.0

BD

(CTS3.5149.11) ENVELOPES E 29

2771

19.C1.3-BS

5/6/2011

14.0

2.1

2,375

16.9

27.8

46.6

52.4

1.3

AM

(CTS3.5150.11) RESERVATORIO INFERIOR DE AGUA POTAVEL

2773

19.C1.3-BS

5/7/2011

14.0

2.2

2,350

16.3

30.5

41.3

48.3

1.0

BD

(CTS3-5160/11) ENVELOPES - E30

2775

19.C1.3-BS

5/9/2011

14.5

3.4

2,330

16.4

30.8

44.2

50.6

1.8

BD

(CTS3.5567.11) ENVELOPES - E3 E E3A

2779

19.C1.3-BS

5/10/2011

14.0

2.8

2,357

17.7

30.8

44.9

50.1

0.1

BD

(CTS3.5571.11) ENVELOPES E3 E E3A

2785

19.C1.3-BS

5/13/2011

12.0

2.8

2,330

17.7

30.3

44.6

54.8

0.9

BD

(CTS3.5592.11) ENVELOPES E14 E E14A

2787

19.C1.3-BS

5/14/2011

13.0

3.0

2,311

16.8

24.7

39.2

44.0

0.0

BD

(CTS3.5596.11) ENVELOPES E31

2799

19.C1.3-BS

5/19/2011

15.0

3.8

2,305

18.6

25.9

39.3

44.0

1.5

BD

(CTS3.5620.11) ENVELOPES E50,E51,E52 E E53

2807

19.C1.3-BS

5/24/2011

13.0

3.8

2,337

15.3

26.4

37.5

47.9

2.2

BD

(CTS3.5712.11) ENVELOPES E55

2809

19.C1.3-BS

5/25/2011

14.0

3.0

2,323

14.3

25.8

38.1

42.4

4.0

BD

(CTS3.5719.11) ENVELOPES E54

2811

19.C1.3-BS

5/25/2011

14.0

3.2

2,317

14.7

27.9

41.3

45.9

0.8

BD

(CTS3.5720.11) ENVELOPES E56

2823

19.C1.3-BS

5/27/2011

14.0

2.9

2,317

15.3

25.7

41.0

47.2

2.1

BD

(CTS3.5746.11) ENVELOPES E61

14.0

2.7

2340

18.1

27.3

40.4

46.9

1.5

Resultados Mdios

ESTATSTICA DO RESULTADO
Dentro do Lote (Resistncia)

RESISTNCIA CARACTERSTICA ESTIMADA

Dentro do Ensaio (Amplitude)

Mdia (MPa)

40.4

Mdia (MPa)

1.54

Numero de Amostras

Desvio Padro (MPa)

5.2

0,8865 Mdia (MPa)

1.36

Coeficiente t

1.645

3.38

fck Estimado (MPa)

31.8

Coeficiente de Variao (%)

Coeficiente de Variao (%)


12.8
ACI 214 (PRTICA RECOMENDADA)

Dentro do Lote

30

CONCLUSO DO LOTE

Dentro do Ensaio

Padro Controle

C.V. (%)

D. Padro (MPa)

Padro Controle

Coeficiente de Variao (%)

Conforme (fck est/fck proj > 1,0)

Excelente

< 7,0

< 2,80

Excelente

< 3,0

No Conforme (fck est/fck proj < 1,0)

Muito Bom

7,0 a 9,0

2,8 a 3,4

Muito Bom

3,0 a 4,0

Lote Parcial

Bom

9,0 a 11,0

3,4 a 4,1

Bom

4,0 a 5,0

Razovel

11,0 a 14,0

4,1 a 4,8

Razovel

5,0 a 6,0

Pobre

> 14,0

> 4,8

Pobre

> 6,0

Tendncia de Crescimento do fck Estimado

Acompanhamento das Resistncias Simples


60

60

50

50

Resistncia (MPa)

Resistncia Simples
(MPa)

1.27

40

30
20

10

y = 7.4494ln(x) + 6.4579
R = 0.9823

40
30

20
10

0
1

11

13

15

17

19

21

23

25

27

29

14

21

28

N de Amostras
3 dias

Observao:

7 dias

28 dias

fcj Requerido (33,2 MPa)

90 dias

35

42 49 56
Idade (dia)

63

70

77

fck Requerido (25,0 MPa)

fck estimado

Idade de Controle

Curva de Tendncia

84

91

CONTROLE ESTATSTICO DA QUALIDADE DO CONCRETO


DETERMINAO DA RESISTNCIA COMPRESSO AXIAL SIMPLES (MPa)
AVALIAO PELO MTODO DA ACI 214/2002
CLASSE:

C1

03

LOTE:

Fck DE PROJETO:

Nmero

Concreto Fresco

25.0 MPa

IDADE DE CONSIDERADA: 28 DIAS

Rev: 00

Resist. Compresso (MPa)


Amp.
Mdia
28 dias

Estrutura

46.1

0.7

BD

(CTS3.5750.11)

40.1

40.5

2.5

BD

(CTS3.5754.11) ENVELOPES E59

25.3

42.7

49.4

4.1

BD

(CTS3.5755.11) ENVELOPES E58

16.8

25.2

35.4

43.5

1.4

BD

(CTS3.5775.11) CAIXA DE PASSAGEM 10-11-12-13-14

2,330

20.2

26.0

41.6

43.0

0.5

BD

(CTS3.5786.11) ENVELOPES E1 E E1A

2.6

2,357

18.3

25.1

41.5

46.3

0.2

BD

(CTS3.5790.11) ENVELOPES E15 E E 15A

14.0

3.0

2,343

16.0

28.1

42.1

49.5

0.9

BD

(CTS3.5808.11) CAIXAS DE PASSAGEM 7,10,11,12,13 E 14.

6/10/2011

13.0

2.8

2,330

15.6

26.2

40.8

45.2

1.6

BD

(CTS3.5827.11) CAIXAS DE PASSAGEM CP 18,18 A 20 A

19.C1.3-BS

6/16/2011

15.0

4.0

2,298

19.3

26.0

41.2

40.8

0.4

BD

(CTS3.5860.11) ENVELOPES E2 E2A

2867

19.C1.3-BS

6/17/2011

12.0

3.6

2,323

16.6

30.1

45.3

44.0

2.9

FS

(CTS3.5870.11) UNIDADE 3

2871

19.C1.3-BS

6/18/2011

14.0

3.4

2,311

12.1

27.5

39.4

34.5

0.0

BD

(CTS3.5883.11) CAIXA DE PASSAGEM 21 E 21A

2891

19.C1.3-BS

6/25/2011

14.0

2.4

2,330

14.7

25.1

39.5

44.5

0.8

BD

(CTS3.5930.11) CAIXA DE PASSAGEM CP4 E CP4A

2905

19.C1.3-BS

7/2/2011

14.0

3.4

2,317

17.8

33.2

49.4

50.7

0.2

FS

(CTS3.5973.11) UNID. 3 LAJE FUNDO DO POO

2953

19.C1.3-BS

7/23/2011

14.0

2.5

2,323

20.6

31.6

43.4

45.8

0.9

FS

(CTS3.6084.11) PAREDE DA CAIXA DO POO SEPARADOR AGUA E

2983

19.C1.3-BS

8/9/2011

14.0

2.0

2,339

17.8

34.0

44.7

51.5

2.1

FS

(CTS3.6172.11) TAMPA DO POO SEPARADOR AGUA /OLEO

2989

19.C1.3-BS

8/10/2011

15.0

1.8

2,339

14.6

22.5

46.3

AM

(CTS3.6183.11) ACABAMENTO DA LAJE EIXO 2/3-LINHA A/B

3035

19.C1.3-BS

9/2/2011

12.0

2.4

2,332

17.2

33.2

45.7

48.1

4.0

FS

(CTS3.6297.11) LAJE JUSANTE LINHA D

3045

19.C1.3-BS

9/7/2011

14.0

2.3

2,326

23.2

33.9

45.0

48.2

0.7

FS

(CTS3.6327.11) LAJE JUSANTE LINHA D

3051

19.C1.3-BS

9/9/2011

14.0

2.2

2,345

18.2

31.1

47.1

47.7

1.7

FS

(CTS3.6342.11) LAJE JUSATE LINHA D

3081

19.C1.3-BS

9/22/2011

14.0

3.6

2,306

21.3

33.4

45.2

48.8

2.9

FS

(CTS3.6415.11) BL./CAMADA UNID3-ESCADA DE ACESSO AO GERAD

13.8

2.8

2,328

16.9

28.4

42.7

45.7

1.5

Dosagem

Data de
Moldagem

28

90

2825

19.C1.3-BS

5/28/2011

14.0

3.4

2,323

15.3

27.1

40.9

2827

19.C1.3-BS

5/28/2011

15.0

3.2

2,313

13.1

23.0

2829

19.C1.3-BS

5/28/2011

11.0

2.8

2,325

8.4

2833

19.C1.3-BS

6/2/2011

14.0

2.4

2,344

2837

19.C1.3-BS

6/4/2011

14.0

2.8

2839

19.C1.3-BS

6/4/2011

14.0

2845

19.C1.3-BS

6/8/2011

2851

19.C1.3-BS

2861

Srie

Consistncia
(cm)

Resultados Mdios

Ar
Massa
Incorp. Unit.
(%) (kg/m)

Idade (dia)

ESTATSTICA DO RESULTADO
Dentro do Lote (Resistncia)

Local de Aplicao

RESISTNCIA CARACTERSTICA ESTIMADA

Dentro do Ensaio (Amplitude)

Mdia (MPa)

42.7

Mdia (MPa)

1.50

Numero de Amostras

Desvio Padro (MPa)

3.2

0,8865 Mdia (MPa)

1.33

Coeficiente t

3.11

fck Estimado (MPa)

Coeficiente de Variao (%)

Coeficiente de Variao (%)


7.6
ACI 214 (PRTICA RECOMENDADA)

Dentro do Lote

19
1.726
35.3

CONCLUSO DO LOTE

Dentro do Ensaio

Padro Controle

C.V. (%)

D. Padro (MPa)

Padro Controle

Coeficiente de Variao (%)

Conforme (fck est/fck proj > 1,0)

Excelente

< 7,0

< 2,80

Excelente

< 3,0

No Conforme (fck est/fck proj < 1,0)

Muito Bom

7,0 a 9,0

2,8 a 3,4

Muito Bom

3,0 a 4,0

Lote Parcial

Bom

9,0 a 11,0

3,4 a 4,1

Bom

4,0 a 5,0

Razovel

11,0 a 14,0

4,1 a 4,8

Razovel

5,0 a 6,0

Pobre

> 14,0

> 4,8

Pobre

> 6,0

Tendncia de Crescimento do fck Estimado

Acompanhamento das Resistncias Simples


60

60

50

50

Resistncia (MPa)

Resistncia Simples
(MPa)

1.41

40
30
20
10

y = 8.0321ln(x) + 4.6444
R = 0.931

40

30
20

10
0

11

13

15

17

19

21

23

25

27

29

14

21

28

N de Amostras
3 dias

Observao:

7 dias

28 dias

fcj Requerido (33,7 MPa)

90 dias

35

42 49 56
Idade (dia)

63

70

77

fck Requerido (25,0 MPa)

fck estimado

Idade de Controle

Curva de Tendncia

84

91

CONTROLE ESTATSTICO DA QUALIDADE DO CONCRETO


DETERMINAO DA RESISTNCIA COMPRESSO AXIAL SIMPLES (MPa)
AVALIAO PELO MTODO DA ACI 214/2002
CLASSE:

C1

LOTE:

Nmero

04

Fck DE PROJETO:
Concreto Fresco

Dosagem
Srie

Data de
Moldagem

Consistncia
(cm)

25.0 MPa

IDADE DE CONSIDERADA: 28 DIAS

Rev: 00

Resist. Compresso (MPa)

Ar
Massa
Incorp. Unit.
(%) (kg/m)

Idade (dia)
3

28

90

Amp.
Mdia
28 dias

Estrutura

Local de Aplicao

3133

19.C1.3-BS

10/19/2011

14.0

3.6

2,306

16.0

25.8

36.4

2.0

FS

(CTS3-6548/11) PAREDE FECHAMENTO DO TUNEL FORADO

3159

19.C1.3-BS

11/2/2011

15.0

4.0

2,309

15.4

27.3

37.3

0.3

FS

(CTS3-6594/11) Envelopamento de cabos - Envelope E 6 e CP-6

3183

19.C1.3-BS

11/22/2011

16.0

2.0

2,385

16.7

19.9

35.3

1.5

AS

(CTS3-6645/11) COMPLEMENTO MURO LATERAL SUPERIOR

3193

19.C1.3-BS

12/1/2011

13.0

2,441

21.8

24.4

AS

(CTS3-6663-11)Muro lateral superior

14.5

3.2

2,360

17.5

24.3

36.3

1.3

Resultados Mdios