Você está na página 1de 2

SL Description Qty

Intelligent Fire Alarm Panel


Supply,Installation, Testing and commissioning of Microprocessor Based Intelligent
analogue addressable Single Loop Fire Alarm Panel UL listed 9th edition , 160
Characters LCD display, Maximum 4 number of loop cards Expandable , with Class A
Style 5,6 or 7 / Class B style 4 wiring, with min 254 devices per loop, Day / Night Mode
Facility, USB 2.0/RS 232 Interface for PC connectivity, On Board RS 485
Communication facility for peer to peer Network / Repeater, The loop card shall be
configuration free replacable. The panel shall have a provision for Ethernet module ,
graphics software and also MODBUS connectivity for BMS/SCADA system
Integration.Also the panel shall have provision for seemless inegration with digital
evacuation system has to be considered for future expansion,The Battery Backup has
to be calculated for 24 hours in Normal Condition and 30 Minutes in Alarm Condition,
The system has to be complete in all respect complying to the specification in
BOQ.Shall be UL Listed.
1 1
Supply,installation,Testing and commissioning of Conventional Optical smoke Detector,
Dual LED’s for 360 visibility, Regular 100mm base, Shall be UL Listed along with the
2 reuqired Junction Boxes and Accessories. 90.00
Supply,installation,Testing and commissioning of Conventional Heat Detector, Dual
LED’s for 360 visibility, Regular 100mm base, Shall be UL Listed along with the
2 reuqired Junction Boxes and Accessories. RO
Supply,installation,Testing and commissioning of Manual Call point Indoor Use, shall
have a break Glass Rod,Shall be integrated with addressabel panel thru required
3 Module, with required Junction Boxes and accessories.
20.00
Supply,Installation, Testing and commissioning of 4 in 4 out Input output Module for
connecting Conventional devices and Flow Swithes he field NO/NC devices. Binary
4 Coding Setting - . 9.00
Supply,Installation, Testing and commissioning of Conventional type Horn wall mounted
5 type rated at 95 dBA @ 1m for Audible annunciation 18.00
Supply of Fault isolator Module capable of monitoring shorted loop circuit and
6 automatically restore communications when shorted conditions are corrected . 2.00
Supply,Installation, Testing and commissioning of Response indicator with dual LED for
7 all detectors located above false ceiling 45.00
Supply, Installation, Testing and commissioning of SMPS based 5A 24V power supply
8 with Necessary back up 1.00
Supplying, and Laying of 2 core 1.5 sqmm FRLS twisted Shielded copper multi strand
9 armoured Cable along with the required accessories. 500.00

Total
Tax and duties extra as applicable.
Syetem installer margin should be consider.
Unit Unit Price Total

Nos 70000 70000

Nos 1000.00 90000.00

Nos 950.00

Nos 800.00 16000.00

Nos 10500.00 94500.00

Nos 800.00 14400.00

Nos 1800.00 3600.00

Nos 120.00 5400.00

Nos 15000.00 15000.00

Nos 250.00 125000.00

Nos 433900.00

Você também pode gostar