Você está na página 1de 11

Pressão

Inicial 0
(MCA) Dados de Entrada Referente as Colunas de Água Fria
Trecho Fator Conexões (Quantidades) Tamanho
▲H Comprimento Válvula Regsitr Registr Virtual
de Pesos Joelho Joelho Curva Curva Tê Tê Tê Entrada Saída Válvula
Montante Jusante (m) Real (m) Uso Retençã o o Conexões
90º 45º 90º 45º Direto Lateral Centro Normal Afogada PC
A B -5 18 0.42 603.2 4 0 2 0 0 1 0 0 0 0 o
0 Gaveta
0 Globo
0 23.8
B C -3 3.1 0.42 580.0 0 0 0 0 3 0 0 0 0 0 0 0 0 6.9
C D -3 3.1 0.42 556.8 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
D E -3 3.1 0.42 533.6 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
E F -3 3.1 0.42 510.4 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
F G -3 3.1 0.42 487.2 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
G H -3 3.1 0.42 464.0 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
H I -3 3.1 0.42 440.8 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
I J -3 3.1 0.42 417.6 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
J K -3 3.1 0.42 394.4 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
K L -3 3.1 0.42 371.2 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
L M -3 3.1 0.42 348.0 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
M N -3 3.1 0.42 324.8 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
N O -3 3.1 0.42 301.6 0 0 0 0 3 0 0 0 0 0 0 0 0 6.6
O P -3 3.1 0.42 278.4 0 0 0 0 3 0 0 0 0 0 0 0 0 4.5
P Q -3 3.1 0.42 255.2 0 0 0 0 3 0 0 0 0 0 0 0 0 4.5
Q R -3 3.1 0.42 232.0 0 0 0 0 3 0 0 0 0 0 0 1 0 4.9
R S -3 3.1 0.42 208.8 0 0 0 0 3 0 0 0 0 0 0 0 0 4.5
S T -3 3.1 0.42 185.6 0 0 0 0 3 0 0 0 0 0 0 0 0 4.5
T U -3 3.1 0.42 162.4 0 0 0 0 3 0 0 0 0 0 0 0 0 4.5
U V -3 3.1 0.42 139.2 0 0 0 0 3 0 0 0 0 0 0 0 0 2.7
V W -3 3.1 0.42 116.0 0 0 0 0 3 0 0 0 0 0 0 0 0 2.7
W X -3 3.1 0.42 92.8 0 0 0 0 3 0 0 0 0 0 0 0 0 2.7
X Y -3 3.1 0.42 69.6 0 0 0 0 3 0 0 0 0 0 0 0 0 2.7
Y Z -3 3.1 0.42 46.4 0 0 0 0 3 0 0 0 0 0 0 0 0 2.7
Z / -3 3.1 0.42 23.2 0 0 0 0 3 0 0 0 0 0 0 0 0 2.7

Pressão
Inicial 3.500
(MCA) Dados de Entrada Referente aos Ramais e Sub-Ramais de Água Fria
Trecho Fator Conexões (Quantidades) Tamanho
▲H Comprimento Válvula Regsitr Registr Virtual
de Pesos Joelho Joelho Curva Curva Tê Tê Tê Entrada Saída Válvula
Montante Jusante (m) Real (m) Retençã o o
Uso 90º 45º 90º 45º Direto Lateral Centro Normal Afogada PC Conexões
B-1 B-2 1.3 8.33 0.50 5.1 4 0 0 0 0 1 0 0 0 0 o
0 Gaveta
1 Globo
0 7.4
B-2 B-3 0 0.8 1.00 0.7 1 0 1 0 0 0 0 0 0 0 0 0 0 1.7
B-3 B-3-1 -2 3.4 1.00 0.7 2 0 0 0 0 0 0 0 0 0 0 1 0 2.6
B-2 B-4 0 2.4 0.50 4.4 0 0 0 0 1 0 0 0 0 0 0 0 0 0.8
B-4 B-5 0 0.4 1.00 1.7 0 0 0 0 0 1 0 0 0 0 0 0 0 2.4
B-5 B-5-1 -1.2 1.15 1.00 1.7 0 0 1 0 0 0 0 0 0 0 0 1 0 0.7
B-5-1 B-5-2 -0.4 1 1.00 1.0 1 0 0 0 1 0 0 0 0 0 0 0 0 2
B-5-1 B-5-3 -0.9 0.9 1.00 0.7 2 0 0 0 0 1 0 0 0 0 0 0 0 4.8
B-4 B-6 0 0.65 0.53 2.7 0 0 0 0 1 0 0 0 0 0 0 0 0 0.8
B-6 B-7 0 0.25 0.80 1.0 0 0 0 0 1 0 0 0 0 0 0 0 0 0.8
B-7 B-7-1 -2.1 2.7 0.80 1.0 1 0 1 0 0 0 0 0 0 0 0 1 0 1.9
B-7-1 B-7-2 0.5 0.6 1.00 0.4 2 0 0 0 0 2 0 0 0 0 0 0 0 7.2
B-7-1 B-7-3 0 1 1.00 0.7 0 0 0 0 1 0 0 0 0 0 0 0 0 0.8
B-7-3 B-7-4 -0.3 0.3 1.00 0.4 1 0 0 0 1 0 0 0 0 0 0 0 0 2
B-7-3 B-7-5 0 0.85 1.00 0.3 1 0 0 0 0 1 0 0 0 0 0 0 0 3.6
B-6 B-8 0 1.25 0.62 1.7 0 0 0 0 0 1 0 0 0 0 0 0 0 2.4
B-8 B-9 0 0.25 1.00 0.7 0 0 0 0 0 1 0 0 0 0 0 0 0 2.4
B-9 B-9-1 -2.1 2.3 1.00 0.7 1 0 1 0 0 1 0 0 0 0 0 1 0 4.3
B-9-1 B-9-2 -0.3 0.6 1.00 0.3 2 0 0 0 1 0 0 0 0 0 0 0 0 3.2
B-8 B-10 0 11.1 1.00 1.0 3 0 0 0 1 0 0 0 0 0 0 0 0 4.4
B-10 B-10-1 -1.9 1.85 0.80 1.0 1 0 1 0 0 0 0 0 0 0 0 1 0 1.9
B-10-1 B-10-2 0.3 0.5 1.00 0.4 2 0 0 0 0 2 0 0 0 0 0 0 0 7.2
B-10-1 B-10-3 0 1.25 1.00 0.7 0 0 0 0 1 0 0 0 0 0 0 0 0 0.8
B-10-3 B-10-4 -0.5 0.5 1.00 0.3 1 0 0 0 0 1 0 0 0 0 0 0 0 3.6
B-10-3 B-10-5 0 0.85 1.00 0.4 1 0 0 0 1 0 0 0 0 0 0 0 0 2

Pressão
Inicial 3
(MCA) Dados de Entrada Referente aos Ramais e Sub-Ramais de Água Quente
Trecho Fator Conexões (Quantidades) Tamanho
▲H Comprimento Válvula Regsitr Registr Virtual
de Pesos Joelho Joelho Curva Curva Tê Tê Tê Entrada Saída Válvula
Montante Jusante (m) Real (m) Retençã o o
Uso 90º 45º 90º 45º Direto Lateral Centro Normal Afogada PC Conexões
Q-1 Q-2 1.15 1.25 0.80 1.5 1 0 0 0 0 0 0 0 0 0 o
0 Gaveta
1 Globo
0 1.7
Q-2 Q-3 -2 4.95 1.00 0.7 3 0 1 0 0 1 0 0 0 0 0 1 0 8.2
Q-2 Q-4 0 1.4 1.00 0.8 1 0 0 0 1 0 0 0 0 0 0 0 0 2.3
Q-4 Q-5 -0.6 2.9 1.00 0.4 2 0 0 0 1 1 0 0 0 0 0 1 0 7.2
Q-4 Q-6 -0.6 14.77 1.00 0.4 2 0 1 0 0 2 0 0 0 0 0 1 0 10.1
Dimensionamento da Bomba de Recalque OBS: Bomba selecionada a
partir do catalago online da
Volume do Reservatório Superior 75780.000 imbil de acordo com a Vazao
Estimada e Altura
Tempo p/ Abastecer Reservatorio 6.000 manometrica.
Vazão Estimada (m³/s) 0.004
Vazão Estimada (m³/h) 12.630
Altura Manometrica (m) 124.219

Perda de Carga Sucção Diametro 40mm


Comprimento da Tubulação (m) 103.700
Comprimento Equivalente (m) 34.400
Comprimento Real (m) 138.100
Perda de Carga Unitaria (m/m) 0.211
Perda de Carga Total (m) 29.081
Perda de Carga Recalque Diametro 32mm
Comprimento da Tubulação (m) 4.65
Comprimento Equivalente (m) 20.400
Comprimento Real (m) 25.050
Perda de Carga Unitaria (m/m) 0.624
Perda de Carga Total (m) 15.638
Cálculo de Pressão nos Ramais e Sub-Ramais De Água Fria
Trecho Vazão DiametroVelocidadeComprimento Equivalento (m) PressãoPerda de Carga(mca/m) Pressão Fator
Tubulação ▲H C Reynolds
Montante Jusante (l/s) (mm) (m/s) Tubulação Conexões Total Montante Unitária Total Jusante Darcy
B-1 B-2 0.479 PVC 25 0.976 8.33 7.4 15.73 1.3 3.50 0.039 0.609 140 1.59 30498 0.0199
B-2 B-3 0.251 PVC 25 0.511 0.8 1.7 2.5 0 1.59 0.012 0.030 140 1.56 15979 0.0229
B-3 B-3-1 0.251 PVC 25 0.511 3.4 2.6 6 -2 1.56 0.012 0.073 140 3.49 15979 0.0229
B-2 B-4 0.445 PVC 25 0.906 2.4 0.8 3.2 0 1.59 0.034 0.108 140 1.48 28328 0.0202
B-4 B-5 0.391 PVC 25 0.797 0.4 2.4 2.8 0 1.48 0.027 0.075 140 1.41 24902 0.0208
B-5 B-5-1 0.391 PVC 25 0.797 1.15 0.7 1.85 -1.15 1.41 0.027 0.050 140 2.51 24902 0.0208
B-5-1 B-5-2 0.300 PVC 25 0.611 1 2 3 -0.4 2.51 0.017 0.050 140 2.86 19099 0.0220
B-5-1 B-5-3 0.251 PVC 25 0.511 0.9 4.8 5.7 -0.9 2.51 0.012 0.069 140 3.34 15979 0.0229
B-4 B-6 0.359 PVC 25 0.731 0.65 0.8 1.45 0 1.48 0.023 0.033 140 1.45 22847 0.0211
B-6 B-7 0.268 PVC 25 0.547 0.25 0.8 1.05 0 1.45 0.014 0.014 140 1.43 17082 0.0225
B-7 B-7-1 0.268 PVC 25 0.547 2.7 1.9 4.6 -2.05 1.43 0.014 0.063 140 3.42 17082 0.0225
B-7-1 B-7-2 0.190 PVC 25 0.387 0.6 7.2 7.8 1.6 3.42 0.007 0.058 140 1.76 12079 0.0244
B-7-1 B-7-3 0.251 PVC 25 0.511 1 0.8 1.8 0 3.42 0.012 0.022 140 3.40 15979 0.0229
B-7-3 B-7-4 0.190 PVC 25 0.387 0.3 2 2.3 -0.3 3.40 0.007 0.017 140 3.68 12079 0.0244
B-7-3 B-7-5 0.164 PVC 25 0.335 0.85 3.6 4.45 0 3.40 0.006 0.026 140 3.37 10461 0.0253
B-6 B-8 0.308 PVC 25 0.627 1.25 2.4 3.65 0 1.45 0.018 0.064 140 1.38 19607 0.0218
B-8 B-9 0.251 PVC 25 0.511 0.25 2.4 2.65 0 1.38 0.012 0.032 140 1.35 15979 0.0229
B-9 B-9-1 0.251 PVC 25 0.511 2.3 4.3 6.6 -2.05 1.35 0.012 0.080 140 3.32 15979 0.0229
B-9-1 B-9-2 0.164 PVC 25 0.335 0.6 3.2 3.8 -0.3 3.32 0.006 0.022 140 3.60 10461 0.0253
B-8 B-10 0.300 PVC 25 0.611 11.1 4.4 15.5 0 1.38 0.017 0.259 140 1.13 19099 0.0220
B-10 B-10-1 0.268 PVC 25 0.547 1.85 1.9 3.75 -1.85 1.13 0.014 0.051 140 2.92 17082 0.0225
B-10-1 B-10-2 0.190 PVC 25 0.387 0.5 7.2 7.7 0.3 2.92 0.007 0.057 140 2.57 12079 0.0244
B-10-1 B-10-3 0.251 PVC 25 0.511 1.25 0.8 2.05 0 2.92 0.012 0.025 140 2.90 15979 0.0229
B-10-3 B-10-4 0.164 PVC 25 0.335 0.5 3.6 4.1 -0.5 2.90 0.006 0.024 140 3.38 10461 0.0253
B-10-3 B-10-5 0.190 PVC 25 0.387 0.85 2 2.85 0 2.90 0.007 0.021 140 2.88 12079 0.0244
Cálculo de Pressão nas Colunas AF
Trecho Vazão Diâmetro Velocidade Comprimento Equivalente (m) ▲H Pressão Perda de Carga Pressão Fator
Tubulação C Reynolds
Montante Jusante (l/s) (mm) (m/s) Tubulação Conexões Total (m) Montante Unitária Total Jusante Darcy
A B 4.78 PVC 60 1.69 18 23.8 41.8 -5 0.000 0.036 1.500 140 3.500 126662 0.0148
B C 4.68 PVC 60 1.66 3.1 6.9 10 -3 3.500 0.035 0.346 140 6.154 124202 0.0149
C D 4.59 PVC 50 2.34 3.1 6.6 9.7 -3 6.154 0.082 0.795 140 8.358 146031 0.0147
D E 4.49 PVC 50 2.29 3.1 6.6 9.7 -3 8.358 0.079 0.764 140 10.594 142957 0.0148
E F 4.39 PVC 50 2.24 3.1 6.6 9.7 -3 10.594 0.076 0.733 140 12.861 139814 0.0148
F G 4.29 PVC 50 2.19 3.1 6.6 9.7 -3 12.861 0.072 0.702 140 15.158 136600 0.0149
G H 4.19 PVC 50 2.13 3.1 6.6 9.7 -3 15.158 0.069 0.671 140 17.487 133308 0.0149
H I 4.08 PVC 50 2.08 3.1 6.6 9.7 -3 17.487 0.066 0.640 140 19.848 129932 0.0150
I J 3.97 PVC 50 2.02 3.1 6.6 9.7 -3 19.848 0.063 0.608 140 22.240 126467 0.0150
J K 3.86 PVC 50 1.97 3.1 6.6 9.7 -3 22.240 0.059 0.577 140 24.663 122904 0.0151
K L 3.75 PVC 50 1.91 3.1 6.6 9.7 -3 24.663 0.056 0.545 140 27.118 119234 0.0151
L M 3.63 PVC 50 1.85 3.1 6.6 9.7 -3 27.118 0.053 0.513 140 29.604 115448 0.0152
M N 3.50 PVC 50 1.78 3.1 6.6 9.7 -3 29.604 0.050 0.482 140 32.123 111533 0.0153
N O 3.38 PVC 50 1.72 3.1 6.6 9.7 -3 8.000 0.046 0.450 140 10.550 107476 0.0154
O P 3.24 PVC 40 2.58 3.1 4.5 7.6 -3 10.550 0.130 0.986 140 12.564 129075 0.0153
P Q 3.11 PVC 40 2.47 3.1 4.5 7.6 -3 12.564 0.120 0.909 140 14.655 123579 0.0154
Q R 2.96 PVC 40 2.36 3.1 4.9 8 -3 14.655 0.109 0.876 140 16.779 117828 0.0155
R S 2.81 PVC 40 2.24 3.1 4.5 7.6 -3 16.779 0.099 0.754 140 19.025 111782 0.0156
S T 2.65 PVC 40 2.11 3.1 4.5 7.6 -3 19.025 0.089 0.676 140 21.349 105389 0.0157
T U 2.48 PVC 40 1.97 3.1 4.5 7.6 -3 21.349 0.079 0.597 140 23.753 98582 0.0159
U V 2.29 PVC 32 2.85 3.1 2.7 5.8 -3 23.753 0.206 1.193 140 25.559 114087 0.0159
V W 2.09 PVC 32 2.60 3.1 2.7 5.8 -3 25.559 0.173 1.006 140 27.553 104147 0.0161
W X 1.87 PVC 32 2.33 3.1 2.7 5.8 -3 27.553 0.141 0.817 140 29.737 93152 0.0163
X Y 1.62 PVC 32 2.02 3.1 2.7 5.8 -3 29.737 0.108 0.625 140 32.112 80672 0.0166
Y Z 1.32 PVC 32 1.65 3.1 2.7 5.8 -3 32.112 0.074 0.430 140 34.682 65868 0.0171
Z / 0.94 PVC 32 1.16 3.1 2.7 5.8 -3 34.682 0.039 0.228 140 37.455 46576 0.0182
Cálculo de Pressão nos Ramais e Sub-Ramais De Água Quente
Trecho Vazão DiâmetroVelocidadeComprimento Equivalente (m) Pressão Perda de Carga (mca/m) Pressão Fator
Tubulação ▲H C Reynolds
Montante Jusante (l/s) (mm) (m/s) Tubulação Conexões Total Montante Unitária Total Jusante Darcy
Q-1 Q-2 0.367 AQUATHERM 22 0.967 1.25 1.7 2.95 1.15 3 0.045 0.132 140 1.718 26581 0.0206
Q-2 Q-3 0.251 AQUATHERM 22 0.660 4.95 8.2 13.15 -2 1.718 0.023 0.297 140 3.421 18158 0.0223
Q-2 Q-4 0.268 AQUATHERM 22 0.706 1.4 2.3 3.7 0 1.718 0.025 0.094 140 1.624 19412 0.0220
Q-4 Q-5 0.190 AQUATHERM 22 0.499 2.9 7.2 10.1 -0.55 1.624 0.014 0.139 140 2.035 13726 0.0238
Q-4 Q-6 0.190 AQUATHERM 22 0.499 14.77 10.1 24.87 -0.55 1.624 0.014 0.342 140 1.832 13726 0.0238
Conexõ
Diâmetro
Joelho 90º Joelho 45º Curva 90º Curva 45º Tê Direto
(mm)
25 1.2 0.5 0.5 0.3 0.8
32 1.5 0.7 0.6 0.4 0.9
40 2 1 0.7 0.5 1.5
50 3.2 1.3 1.2 0.6 2.2
60 3.4 1.5 1.3 0.7 2.3
75 3.7 1.7 1.4 0.8 2.4
85 3.9 3.9 1.5 0.9 2.5

Conexõ
Diâmetro
Joelho 90º Joelho 45º Curva 90º Curva 45º Tê Direto
(mm)
15 0.9 0.5 0.5 0.3 0.8
22 1.3 0.8 0.7 0.5 1
28 1.6 1.1 0.8 0.6 1.3
35 2.1 1.4 1.3 0.8 2.3
42 3.3 1.6 1.4 0.9 2.4
54 3.5 1.8 1.5 1 2.5
66 3.6 4 1.7 1.1 2.6
Tê Conexões
de AF
Tê de Entrada Saída Válvula de Válvula de Regsitro
saída
Centro Normal Afogada PC Retenção de Gaveta
lateral
2.4 2.4 0.4 0.9 9.5 2.7 0.2
3.1 3.1 0.5 1.3 13.3 3.8 0.3
4.6 4.6 0.6 1.5 15.5 4.9 0.4
7.3 7.3 1 3.2 18.3 6.8 0.7
7.6 7.6 1.5 3.3 23.7 7.1 0.8
7.8 7.8 1.6 3.5 25 8.2 0.9
8 8 2 3.7 26.8 9.3 0.9

Tê Conexões
de AQ
Tê de Entrada Saída Válvula de Válvula de Regsitro
saída
Centro Normal Afogada PC Retenção de Gaveta
lateral
2.5 2.3 0.4 0.9 9.5 2.7 0.2
3.2 2.5 0.6 1.4 13.6 3.9 0.4
4.7 3.2 0.7 1.6 15.6 5 0.5
7.4 4.8 1.1 3.3 18.5 6.9 0.8
7.8 7.4 1.6 3.4 23.9 7.3 0.9
8 7.8 1.7 3.6 25.3 8.3 1.1
8.2 8.2 2.1 3.9 27 9.5 1.2
Registro
de Globo
11.4
15
22
35.8
37.9
38
40

Registro
de Globo
11.4
16
23
35.9
38.2
39
41
DIÂMETROS TUBULAÇÃO
100 PVC
75 CPVC
60 TIGRE
50 AQUATHERM
40
32
25
20

15
22
28
35
42
54
66
79

Você também pode gostar