Você está na página 1de 2

FORMULAS PARA CUCULOS ELTRICOS E MECNICOS

DADOS DESEJADOS MONOFSICO POTNCIA ATIVA (KW) KW = I x Uf x cs 1000

CORENTE ALTERNADA (CA) TRIFSICO KW = x I x Ul x cs 1000

CORRENTE CONTNUA (DC)

KW = I x U 1000

POTNCIA APARENTE (KVA)

KVA = I x Uf 1000

KVA =

x I x Ul 1000

KVA = I x U 1000

POTNCIA ATIVA (CV)

CV = I x Uf x n x cs 736

x I x Ul x n x cs 736

CV = I x U x n 736

CORRENTE (A)

A = KW x 1000 Uf x cs

A = KW x 1000 x Ul x cs

A = KW x 1000 U

CORRENTE (A)

A = KVA x 1000 Uf

A = KVA x 1000 x Ul

A = KVA x 1000 U

QUEDA DE TENSO (U) PARA CABOS

U = 2 x I x L x cs 56 x S

U =

x I x L x cs 56 x S

U = Rh x I x L

BITOLA DO CABO EM RELAO A QUEDA DE TENSO CORRENTE DO MOTOR (A)

S = 2 x I x L x cs 56 x Ul x 0.05

S=

x I x L x cs 56 x Ul x 0.05

I = 736 x cv____ Uf x n x cs

I = 736 x cv_________ x Ul x n x cs

TORQUE DO MOTOR NYLTON

T = 9.55 x P N

VELOCIDADE DA POLIA RPM

VF = dm x N DM

RENDIMENTO DO MOTOR

Rm = 736 x cv x Ul x cs

FATOR DE POTNCIA

FP = KVA KW

RPM DO MOTOR

RPM = 120 x F NP

ONDE I = Corrente em Amperes U = Queda de Tenso

Uf = Tenso entre fase e neutro Ul = Tenso entre duas fases U = Tenso entre positivo e negativo L = Comprimento do fio em metros P = Potncia nominal em Watts VF = Velocidade Final em RPM DM = Dimetro Maior KVA = Kilovoltamper (Fator de Demanda Carga Instalada) FP = Fator de Potncia cs Rh = Resistividade hmica do material

Cs f = Fator de Potncia da carga n = Rendimento do motor S = Bitola do condutor em mm T = Torque nominal em Nylton N = Velocidade nominal em RPM dm = Dimetro menor Rm = Rendimento do Motor ou (Eficincia do Motor) KW = Kilowatts (Energia Consumida) NP = Nmeros de Plos F = Frequncia em hertz