Você está na página 1de 1

CLCULO DE CORREO DO FATOR DE POTNCIA

CLIENTE: WF ENGENHARIA
ANTES
POTNCIA ATIVA (kW):
POTNCIA APARENTE (kVA):
POTNCIA REATIVA:
F.P. TOTAL:
DEPOIS
F.P. DESEJADO:
POTNCIA ATIVA:
POTNCIA APARENTE:
POTNCIA REATIVA:
POTNCIA REATIVA
ACRECENTAR
PORCENTAGEM A MAIS
PREVISTO PARA FUTURA
EXPANSO:

TOTAL DE POTNCIA REATIVA


ACRESCENTAR:

ESTGIOS ACONSELHVEIS:
1
2
3
4
5
6

DATA:03/07/2009
527.26
610.90
308.538008
0.863087248

0.92
527.26
573.1086957
224.6118194
83.92618859

115%

96.51511688

30 kVAr
25 kVAr
20 kVAr
10 kVAr
10 kVAr
5 kVAr

ITEM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

DADOS DAS CARGAS


POTNCIA ATIVA
POTNCIA
(kW)
APARENTE (kVA)
4.50
5.36
4.50
5.36
15.00
16.85
3.00
3.66
2.25
2.81
15.00
16.85
15.00
16.85
3.00
3.66
3.00
3.66
15.00
16.85
15.00
16.85
15.00
16.85
56.25
61.81
3.75
4.57
30.00
33.33

16

37.50

45.18

17
18
19

5.63
15.00
56.25

7.03
18.99
61.81

20

30.00

33.33

21
22
23
24
25
26
27
28
TOTAL

15.00
30.00
37.50
4.50
5.63
37.50
15.00
37.50
527.26

18.99
33.33
45.18
5.36
7.03
45.18
18.99
45.18
610.90

Você também pode gostar