Escolar Documentos
Profissional Documentos
Cultura Documentos
POTENCIA EM (VA)
POTENCIA DE ILUMINAÇÃO 1540
POTENCIA DE TUG'S 2600
POTENCIA DE TUE'S 20600
0
600 1800
600 1200
1800 1800
600 600
5500 5500
5500 5500
600 600
1800 1800
1800 1800
0
0
PREVISÃO DE DEMANDA INSTALADA
PD=(0,59 . 3,62)+20,6
PD= 22,7358 KW
I=22735/220
I= 103,34 A
DEMANDA ILUM+TUG'S
2.1358
MANDA TUE'S
20.6
127
127
3 TUG'S 1
127
TUG'S 127
127
4 TUGS'2 127
127
5 TUE 1 220
6 TUE 2 220
7 TUE 3 220
8 TUE 4 220
9 TUE 5 220
10 TUE 6 220
TUE'S
11 TUE 7 220
12 TUE 8 220
13 TUE 9 220
14 TUE 10 220
15 TUE 11 220
16 TUE 12 220
FASE 1
CIRCUITO POTENCIA TOTAL (VA) CORRENTE TOTAL
1 460.00 5.67
4 300 8.82
5 300 1.36
6 300 1.36
7 300 1.36
8 300 1.36
9 300 1.36
10 900 4.09
11 900 4.09
12 900 4.09
13 2750 12.50
14 300 1.36
15 2750 12.50
16 300 1.36
POTENCIA TOTAL 11060.00
CORRENTE TOTAL 61.31
POTENCIA TOTAL (VA) 22420.00
CORRENTE TOTAL ( A ) 122.1403006442
CIRCUITOS
POTENCIA
LOCAL
QUANTIDADE FATOR DE POTENCIA POTENCIA (VA) TOTAL (W)
SALA 2 1 160.00 320
COZINHA 1 1 100 100
ÁREA DE SERVIÇO 1 1 100 100
CIRCULAÇÃO 2 1 100 200
VARANDA 2 1 160 320
SUÍTE 1 1 100 100
BANHEIRO SUÍTE 1 1 1 100 100
BANHEIRO SOCIAL 1 1 100 100
QUARTO 1 1 1 100 100
QUARTO 2 1 1 100 100
FASE 2
CIRCUITO POTENCIA TOTAL (VA) CORRENTE TOTAL
2 660 6.46
3 400 7.56
5 300 1.36
6 300 1.36
7 300 1.36
8 300 1.36
9 300 1.36
10 900 4.09
11 900 4.09
12 900 4.09
13 2750 12.50
14 300 1.36
15 2750 12.50
16 300 1.36
POTENCIA TOTAL (VA) 11360
CORRENTE TOTAL (A) 60.83
CORRENTE DE
CORRENTE (A)
PROJETO
2.52 2.52
0.79 0.79
0.79 0.79
1.57 1.57
2.52 2.52
0.79 0.79
0.79 0.79
0.79 0.79
0.79 0.79
0.79 0.79
3.15 3.94
3.15 3.94
0.63 0.79
0.63 0.79
4.41 5.51
0.63 0.79
3.78 4.72
2.73 2.73
2.73 2.73
2.73 2.73
2.73 2.73
2.73 2.73
8.18 8.18
8.18 8.18
8.18 8.18
25.00 25.00
2.73 2.73
25.00 25.00
2.73 2.73
DISJUNTOR GERAL 105A
1 1.5 10
2 1.5 10
3 2.5 10
4 2.5 15
5 2.5 15
6 2.5 15
7 2.5 15
8 2.5 15
9 2.5 15
10 2.5 15
11 2.5 15
12 2.5 15
13 4 25
14 2.5 15
15 6 35
16 2.5 15
TABELA FATOR DE DEMANDA FÓRMULA CORRENTE CORRIGIDA