CLIENTE SANTA LOLLA

OBRA: SHOPPING CONTAGEM RESUMOS DOS GANHOS DE CALOR


CIDADE: CONTAGEM ITEM SENSÍVEL LATENTE
SALA: LOJA LUC-2099 CONV COND.RAD. 1,101
ÁREA (m²) 49.5 PESSOAS 1,125 775
P.D. (m) 2.6 EQUIPAMENTOS 6,966
TBS EXT: (C°) 32 OUTROS
UR EXT: (%) 55 TOTAL SENS. 9,192
TOTAL LAT. 775
ÁREA DT C Q TOTAL 9,967
PAREDE 1 0 0 2.5 0
PAREDE 2 0 0 2.5 0
PAREDE 3 0 0 2.5 0 AR EXTERIOR
PAREDE 3 0 0 2.5 0 PESSOAS M3/H TOTAL
TETO 49.5 8 2 792 15 23 250
PISO/DIVISÃO 49.5 2.5 2.5 309 ÁREA TAXA rph TOTAL
49.5 0
ÁREA C FS Q
PAREDE 1 0 34 VOLUME Q TOTAL
PAREDE 2 0 23 SENSÍVEL 2.183 546
TETO 0 0 99.4 0 LATENTE 5.68 1,420
TOTAL 1,101
PESSOAS PESSOAS Q QS QL
SENSÍVEL 15 75 1,125 **********
LATENTE PARADA 5 45 ******* 225 TOTAL GERAL
LATENTE EM MOV. 10 55 ******* 550 KCAL TR V(INSUFL) (m³/h)
TOTAL 1,125 775 11,933 3.9777083333 2,720
V(ÁGUA GELADA)
EQUIPAMENTOS EQUIP.(W) K SENS. LAT. Vazão de ar externo pela NBR 16401-1 1,0 m³/h
FLUORESCENTE 4,400 0.86 3,784 Vef= pz*Fp+Az*Fa Vazão ar ext. média por pessoa corrigida (ρ)
INCANDESCENTE 0 0 0 Vef=(15*3,8)+(49,5*0,6) 95,37/15=6,358L/s
EQUIPAMENTOS 3,700 0.86 3,182 Vef=86,7 6,358L/s*3600/1000
TOTAL 6,966 Vefc=86,7*1,1=95,37 23 m³/h