Você está na página 1de 2

DISJUNTOR

COMANDO EMERGÊNCIA
Q1 S1
TR1
380 220 1 2 12 11
L1 / 2

0 0 3 4
L2 / 2
170VA

X1 1 2 3 4
W6
1x2,5mm²
PT

W1 W3 PT W7 W9 W11 W14
1 3 5
1x16mm² PT PT PT 1x6,0mm² PT PT PT 1x6,0mm² PT PT PT 1x2,5mm² PT PT 1x2,5mm² PT PT 1x1,0mm² PT PT PT

PT
Q2
NÃO
FORNECIDO
1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3 1L1 5L3 1L1 5L3
2 4 6 K1 K4 K3 K2 K5 K6
2 2T1 4T2 6T3 2 2T1 4T2 6T3 2 2T1 4T2 6T3 2 2T1 4T2 6T3 2 2T1 6T3 2 2T1 6T3
CWM25.00 CWM25.00 CWM12.00 CWM25.00 CW07.01 CW07.01

R S T
1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3 1L1 3L2 5L3 RSF ~
2
FE1 FE2 FE3 FE4
RELE
2 2T1 4T2 6T3 2.P 2T1 4T2 6T3 2 2T1 4T2 6T3 2 2T1 4T2 6T3 SEQUÊNCIA
R S T N PE RW27.D 15...23A RW27.D 15...23A RW17.1D 1,8...2,8A RW17.1D 5,6...8A
FASES
REG: 21 A REG: 21 A REG: 2,0 A REG: 6,5 A
380V/3~/60HZ

É OBRIGATÓRIO A X1 21
INSTALAÇÃO DE
DISJUNTOR INDICADO 1
NO MANUAL DE
P1 P
INSTALAÇÃO ELÉTRICA PRESSOSTATO 4
CONDENSAÇÃO

X1 22

X1 23 24

W10 W12 W13


1 1 1
W2 W4 W8 PP PP PP
1x6,0mm² PT PT PT 1x6,0mm² PT PT PT 1x6,0mm² PT PT PT 3x1,5mm² PT BR 3x2,5mm² PT BR 3x1,5mm PT BR

CAIXA
LIGAÇÃO
DO COMPRESSOR
RL1 L C1 x1
RELE
AMPEROMETRICO C1
x2
S R C2

3
U2 V2 W2
PT1
U1 W3
PROTETOR
TERMICO 1
V1
M V3

W1 3~ U3

C S R PE
1 2 1 2
M1
MOTOR U4 W4 V4 PE
M M M
PRINCIPAL M2 M3 M4
VENTILADOR 1~ COMPRESSOR 1~ VENTILADOR 1~
FRIGORÍFICO SECADOR
PE PE
W10 W12 W13
1.F 1.H 1.J
W5 PP PP PP
2x6,0mm² VD 3x1,5mm² AZ 3x2,5mm² AZ 3x1,5mm² AZ

PE /

PARA TOLERÂNCIAS NÃO INDICADAS, VER "TABELA DE TOLERÂNCIA METALPLAN"


ESCALA: S/E DATA
ELABORADO POR: Rafael 8/12/2011
energy solutions VERIFICADO POR: Edson 8/12/2011
APROVADO POR: Fábio 8/12/2011
CLIENTE: PESO
03 RETORNO DO CONTROLE DO SECADOR PARA O CLP PRINCIPAL RB 19/01/15 ER 19/01/15 FB 19/01/15 BRUTO: --- kg
TÍTULO: LÍQ.: --- kg
02 REVISÃO GERAL PARA NOVO PACK - G5 RB 18/03/14 ER 18/03/14 FB 18/03/14 ESQUEMA ELÉTRICO COMPRESSOR
01 ACRESCENTOU BORNES PARA PRESSOSTATO DE CONDENSAÇÃO RB 12/07/13 ER 12/07/13 FB 12/07/13
FOLHA
EQUIPAMENTO:
TOTALPACK 25 HP 380V CÓDIGO: 01800128 1 2
FORMATO A3 REV DESCRIÇÃO ELAB DATA VERI DATA APR DATA
1/ L1

1/ L2

X1 7 8 9 10 11

SINAL DE FALHA
REMOTO 220V
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2
RC1 K1 RC2 K2 RC3 K3 RC4 K4 RC5 K5 RC6 K6 RC7 VS1 RC8 VS2 RC9 VS3 H1
1.A A1 1.E A1 1.D A1 1.B A1 1.F A1 1.H A1 CARGA A1 PURGA A1 PURGA A1 BUZZER A1
2.P 2.O 2.P ALÍVIO SECADOR SECADOR

X1 12 13 14 15 16

11 11
K3 K4
2 12 2 12

11
K2
2 12

CLP
RX-TX- RX+TX+ GND Vout R-T- R+T+ GND C1 NO1 NO2 NO3 C2 NO4 NO5 NO6 N07 C3 NC7

J7 J8 J9 J10 J11 J12 J13 J14

CLP CAREL

J1 J2 J3 J4 J5
G G0 +Vdc GND +5VR B1 B2 B3 B4 B5 B6 B7 GND +Vdc DI1 DI2 DI3 DI4 DI5 DI6 DI7 DIC1 GND Y1 Y2 Y3

Θ
ST1
ÓLEO

X1 19
Θ
20

ST2
ON/OFF REMOTO
ALÍVIO REMOTO

P.O

X1 17 18

95
FE2
1.E 96

12 14 95 95 95
GND BR
SENSOR RSF FE1 FE3 FE4
SP1 DE 1.J 11 1.A 96 1.F 96 1.H 96
PRESSÃO
PT

PARA TOLERÂNCIAS NÃO INDICADAS, VER "TABELA DE TOLERÂNCIA METALPLAN"


ESCALA: S/E DATA
ELABORADO POR: Rafael 8/12/2011
energy solutions VERIFICADO POR: Edson 8/12/2011
APROVADO POR: Fábio 8/12/2011
CLIENTE: PESO
03 RETORNO DO CONTROLE DO SECADOR PARA O CLP PRINCIPAL RB 19/01/15 ER 19/01/15 FB 19/01/15 BRUTO: --- kg
TÍTULO: LÍQ.: --- kg
02 REVISÃO GERAL PARA NOVO PACK - G5 RB 18/03/14 ER 18/03/14 FB 18/03/14 ESQUEMA ELÉTRICO COMPRESSOR
01 ACRESCENTOU BORNES PARA PRESSOSTATO DE CONDENSAÇÃO RB 12/07/13 ER 12/07/13 FB 12/07/13
FOLHA
EQUIPAMENTO:
TOTALPACK 25 HP 380V CÓDIGO: 01800128 2 2
FORMATO A3 REV DESCRIÇÃO ELAB DATA VERI DATA APR DATA

Você também pode gostar