Você está na página 1de 1

NOTAS

1 - ESTA OBRA FOI CALCULADA E DEVERÁ SER EXECUTADA COM ADEQUADO CONTROLE DE
QUALIDADE E RÍGIDOS LIMITES DE TOLERÂNCIA DA VARIABILIDADE DAS MEDIDAS, CONFORME
NBR 6118. CONFERIR TODAS AS MEDIDAS EM OBRA.
2 - UNIDADES EM CENTÍMETROS, EXCETO QUANDO INDICADO.
3 - CLASSE DE AGRESSIVIDADE II (NBR 6118:2014).
4 - ESTRUTURA DE CONCRETO:
- CONCRETO ESTRUTURAL C35 - fck ≥ 35 MPa e E ≥ 33,1 GPa;
- CONSUMO DE CIMENTO ≥ 280 kg/m³;
- SLUMP TEST: 10 ± 2 cm;
- FATOR ÁGUA CIMENTO A/C ≤ 0,60;
- AÇO CA-50A E CA-60B;
CORTE AA 5 - COBRIMENTOS:
ESCALA 1:100 - BLOCOS: 3,0 cm;
- ESTACAS: 4,0 cm;
- PILARES: 2,5 cm;
1 2 3 4 5 6 7 8 9 10 - VIGAS: 2,5 cm;
6733.2 - LAJES: 2,0 cm;
- UTILIZAR ESPAÇADORES EM TODAS AS PEÇAS DE CONCRETO ARMADO.
870.0 717.5 717.5 717.5 717.5 740.0 740.0 740.0 773.2 6 - ESTRUTURA METÁLICA:
- PERFIS:
CHAPAS AÇO: ASTM A-36 OU SIMILAR (fy ≥ 250 MPa e fu ≥ 400 MPa);
PERFIS DOBRADOS: CF-26 OU SIMILAR (fy ≥ 260 MPa e fu ≥ 400 MPa);
PERFIS LAMINADOS: ASTM A-36 OU SIMILAR (fy ≥ 250 MPa e fu ≥ 400 MPa);
12,30m - CHUMBADORES: SAE 1010/1020 OU SIMILAR (fy ≥ 180 MPa e fu ≥ 330 MPa);
NÍVEL 1300 - PARAFUSOS (PINOS) E PORCAS: ASTM-A325;
V309 V307 V308 V305 V306 V301 V302 V303 V304
- SOLDAS: ELETRODOS AWS E70XX - COMPATÍVEL COM O METAL BASE (RESISTENTE À
V330 V341
CORROSÃO);
- O DETALHAMENTO, FABRICAÇÃO E MONTAGEM DEVERÁ SEGUIR OS CRITÉRIOS DA NORMA
ABNT NBR8800 E COMPLETADA PELA AISC;

375
- OS MATERIAIS EMPREGADOS NA FABRICAÇÃO DEVERÃO SER NOVOS E SEM EMENDAS, A
P10 P8 P9 P7 P4 P5 P6 P1 P2 P3
NÃO SER AS ESPECIFICADAS EM PROJETO.
8,55m
L207 L208 L209 L210 L211 L201 L212 L202 L203 L204 L205 L206 NÍVEL 1200
V209 V251 V205 V255 V206 V259 V207 V262 V211 V263 V211 V266 V204 V267 V204 V201 V202 V203

176.2
P10 P8 P9 P7 P4 P12 P13 P11 P6 P1 P2 P3 6,788m
NÍVEL 1150

1260

193.8
P10 P8 P9 P7 P4 P12 P13 P11 P6 P1 P2 P3
4,85m
L103 L104 L105 L106 L101 L102 L107 NÍVEL 1100
V144 V109 V148 V106 V152 V107 V156 V108 V160 V111 V161 V111 V164 V102 V165 V102 V103 V104 V105 V171

242.5
P10 P8 P9 P7 P4 P12 P13 P11 P6 P1 P2 P3
2,425m
NÍVEL 1050

242.5
272.5
P10 P8 P9 P7 P4 P12 P13 P11 P6 P1 P2 P3 0,00m
TOPO DO PISO DO TÉRREO -0,30m
NÍVEL 1000

30
V8
V9 V9 V9 V10 V10 V10 V11 V11 V12 V12 V12 V12 V12 V88
V70 V13 V71 V73
V1

CORTE BB
ESCALA 1:100

1 2 3 4 5 6 7 8 9 10
6733.2

870.0 717.5 717.5 717.5 717.5 740.0 740.0 740.0 773.2

12,30m
NÍVEL 1300

V314 V315 V316 V317


V328 V331 V333 V335 V337 V339

375
P31 P32 P33 P34 P35 P36 P37 P38 P39 P40

8,55m
L222
L223
L220 L221 L225 L226 L227
NÍVEL 1200

V223 V224 V249 V225 V253 V226 V257 V227 V260 V228 V264 V271

176.2
P31 P32 P33 P34 P35 P36 P37 P38 P39 P40 6,788m
NÍVEL 1150

1260

193.8
P31 P32 P33 P34 P35 P36 P37 P38 P39 P40 4,85m
L118 L119 L120 L121
NÍVEL 1100

V142 V146 V124 V150 V125 V154 V126 V158 V127 V162 V169

242.5
P31 P32 P33 P34 P35 P36 P37 P38 P39 P40
2,425m
NÍVEL 1050

242.5
272.5
P31 P32 P33 P34 P35 P36 P37 P38 P39 P40 0,00m
TOPO DO PISO DO TÉRREO -0,30m
NÍVEL 1000

30
V50 V55 V59 V85
V29 V31
B54
V30 V30 R5
R4
R3
R2
R1
R0 EMISSÃO ORIGINAL DO PROJETO 20/09/22 FERNANDO
REVISÃO MODIFICAÇÃO DATA VISTO

CLIENTE:
DE'LÁZARI ENGENHARIA
PROJETO E CONSULTORIA ESTRUTURAL
ALAMEDA SANTOS, 1165 - JARDIM PAULISTA
CEP: 01419-002, SÃO PAULO/SP
TELEFONE: (11) 4081.1003
engenharia@delarazi-engenharia.com.br
www.delazari-engenharia.com.br

OBRA: S.I.N. - SISTEMA DE IMPLANTE ID: est_sin_galpao_pb


SÃO PAULO - SP ESCALA: INDICADA

TÍTULO: PROJETO ESTRUTURAL ETAPA: PROJETO BÁSICO


GALPÃO PARA FÁBRICA REVISÃO: R0
CORTES A E B FOLHA: 08/09