Você está na página 1de 1

PRODUZIDO POR UMA VERSÃO DO AUTODESK PARA ESTUDANTES

DETALHE DO QGBT S/ ESCALA DIAGRAMA UNIFILAR DO QGBT S/ ESCALA


0,80m

QGBT #6mm²

25A DISJ. DE DPS #6mm²

3X#240mm² FA FB FC TERRA NEUTRO QGBT 25A DISJ. DE DPS #6mm²

220V/380V 25A DISJ. DE DPS #6mm²


1X#185mm² 63A
VEM DO MEDIDOR DE 100mm 400A NOBREACK #2x16mm² ( 10 )
NEMA
KILO-WATT-HORA GERAL 63A QNBE TRAFO NOBREACK #3x16mm² ( 10 )
DO SHOPPING ON
1X#50mm² 63A RESERVA
3X240mm² (185) + ( 50 )
( 220V/380V ) 63A QDLT MEZANINO #3x16mm² ( 10 )

NEUTRO 80A QDL TÉRREO #3x25mm² ( 10 )


OFF

400A
T N 200A AR CONDICIONADO #3x95mm² ( 25 )
1X50mm² 63A ALIMENTA TRAFO DO QDTC #3x16mm² ( 10 )
T #6mm²

PLACA DE IDENTIFICAÇÃO S #6mm²

PRODUZIDO POR UMA VERSÃO DO AUTODESK PARA ESTUDANTES


PRODUZIDO POR UMA VERSÃO DO AUTODESK PARA ESTUDANTES

TERRA
PERIGO R #6mm² #10mm² PLACA DE IDENTIFICAÇÃO
FABRICANTE #6mm²
CHOQUE

20KA
DPS
ELÉTRICO
PERIGO
MODELO QGBT #6mm²

20KA
DPS
NÍVEL DE TENSÃO: CORRENTE FABRICANTE
NOMINAL 500A FA FB FC CHOQUE #10mm²
220V/380V ( BARRAMENTO )

20KA
DPS
FABRICADO MÊS/ANO
ELÉTRICO #6mm²

20KA
DPS
TERRA NEUTRO
MODELO QGBT
NÍVEL DE TENSÃO: #6mm²
CORRENTE

OFF

25A
ON

C-01 DISJ. DE DPS NOMINAL


DIN 500A
C-02 220V/380V ( BARRAMENTO )
OFF

25A
ON

DISJ. DE DPS
DIN
FABRICADO MÊS/ANO
C-03
OFF

25A
ON

DISJ. DE DPS
DIN
C-04 #16mm²
OFF

63A

NOBREACK
ON

DIN
C-05 #16mm² NOTAS SOBRE ATERRAMENTO:
63A
OFF

QNBE TRAFO NOBREACK


ON

C-05 #16mm² 1- ELETRODUTOS UTILIZADOS DEVERÃO SER DE PVC-RIGIDO ROSQUEÁVEL OU SOLDÁVEL.


DIN
2- ELETRODUTOS DEVERÃO SER SONDADOS COM ARAME GALVANIZADOS #1.65mm.
OFF

63A

RESERVA
ON

DIN NOTAS IMPORTANTE:


C-06 #16mm² 3- ELETRODUTOS PROVIDOS DE BUCHAS E ARRUELAS NAS SUAS EXTREMIDADES,EXCETO
AQUELES QUE TERMINEM EM CAIXAS DE SAIDAS. OBS: PINTAR AS FASES DO BARRAMENTO
1,20m

1,20m
C-06 #16mm²
DO QGBT DE ACORDO COM A NORMA NBR-5410:
63A
OFF
ON

QDLF MEZANINO 4- MÁXIMO DE DUAS CURVAS, NÃO REVERSAS, EM LANCE DE TUBULAÇÃO, ENTRE CAIXAS.
C-06 #16mm² FASE A OU FASE R ( VERMELHO )
DIN
5- UTILIZAR CURVAS DE RAIO LONGO, PADRÃO COMERCIAL E NUNCA JOELHOS. FASE B OU FASE S ( BRANCO )
C-07 #25mm² 6- COTAS EM CENTÍMETROS E DIÂMETROS INTERNOS EM MILIMETROS. FASE C OU FASE T ( PRETO )
NEUTRO ( AZUL CLARO )
C-07 #25mm² 7- RESISTÊNCIA DE ATERRAMENTO MENOR OU IGUAL A 15 OHMS.
TERRA OU PROTEÇÃO( VERDE )
80A
OFF
ON

QDL TÉRREO
C-07 #25mm²
OBS: INSTALAR A PLACA DE IDENTIFICAÇÃO
DIN

C-08 #95mm²
QUADRO DE CARGAS 220V / 380V DO NÍVEL DE TENSÃO 220V/380V NA PORTA DO
QGBT CONFORME O DESENHO ACIMA.
C-08 #95mm²
COND. DISJUNTORES CARGA
200A
OFF

AR CONDICIONADO TENSÃO
ON

ALIMENTAÇÃO DO C-08 #95mm²


QDTC-127V/220V NEMA CIRC ALIMENTAÇÃO
FA
FB
FC
N
4X#16mm²
FA FB FC
NOTA: 01 DPS ( D. P. SURTO )
( mm² )

1x6,0
(A)

25A ( MONOPOLAR )
( KVA )

16,435KVA
(V)

220V
PHAEND
fire solutions ltda
OBS: INSTALAR TOMADAS UNIVERSAL PADRÃO
2P+T DE ACORDO COM NORMAS DA ABNT E
N 02 DPS ( D. P. SURTO ) 1x6,0 25A ( MONOPOLAR ) 16,435KVA 220V
ON ON
ULTILIZAR A FIAÇÃO COM AS CORES CORRETAS: CONTEÚDO DA PRANCHA 1/5
NEUTRO: AZUL TERRA: VERDE.
03 DPS ( D. P. SURTO ) 1x6,0 25A ( MONOPOLAR ) 16,435KVA 220V

Design AutoCAD & corelDRAW


DDR DIN

rojetos
- DIAGRAMA UNIFILAR
OFF OFF
NOTAS: - NOTAS E OBSERVAÇÕES
- DETALHE DO QGBT
N 63A 63A

04 NOBREACK 2x16 (10) 63A ( MONOPOLAR ) 23,978KVA 220V - QUADRO DE CARGAS


OBS: ATERRAR TODOS OS QUADROS E AS CAIXAS DE
4X#16mm²
PASSAGEM DE METAL DE ACORDO COM A NORMA NBR-5410.
05 QNBE TRAFO NOB. 2x16 (10) 63A ( BIPOLAR ) 41,416KVA 380V

paulo.lemos@phaend.com.br
N Prancha Número / Controle Desenho em CAD:

FA OBS: ATERRAR TODOS OS ARMÁRIOS E EQUIPOTENCIALIZAR


FB OS ATERRAMENTOS DE ACORDO COM A NORMA NBR-5410. 1/5 405/2019 ALESSANDRO

FC
OBS: MEDIR A RESISTÊNCIA DE ATERRAMENTO DE COM 06 QDLT MEZANINO 3x16 (10) 63A ( TRIPOLAR ) 41,416KVA 380V Título
SAÍDA DO SECUNDÁRIO
DO TRAFO DO QDTC-127V/220V TERRÔMETRO DE ACORDO COM A NORMA NBR-5410, PROJETO PARA NORMALIZAÇÃO DA INFRA ESTRUTURA
RT < 15 OHM'S. 07 QDL TÉRREO 3x25 (10) 80A ( TRIPOLAR ) 52,592KVA 380V DAS INSTALAÇÕES ELÉTRICAS COM DIMENSIONAMENTO
DE INSTALAÇÃO E MONTAGEM DO QGBT
FA
3X#16mm² C-09 OBS: POR MOTIVO DE FALTA DE LUGAR VAGO NO QUADRO
FB
C-09 QDTC O DISJUNTOR DDR DE 63A TRIPOLAR FOI INSTALADO
FC
C-09 NO QUADRO QGBT, PORTANTO ESTE DISJUNTOR ALIMENTA 08 AR CONDICIONADO 3x95 (25) 200A ( TRIPOLAR ) 131,480KVA 380V
Endereço

CACHOEIRO DE ITAPEMIRIM ESPÍRITO SANTO-ES.


ALIMENTAÇÃO DO PRIMÁRIO DO COM 127V/220V O QUADRO QDTC.
TRAFO DE 20KVA DO QDTC-380V PROP.
09 TRAFO QDTC 3x16 (10) 63A ( TRIPOLAR ) 41,416KVA 380V
CASA E VÍDEO
CNPJ: _____________________________
R.T.
DEMANDA(KVA) 3x240 (185) (50) 400A( TRIPOLAR ) 262,960KVA 380V
LUIZ LEANDRO DA SILVA NETO CFT / CRT - RJ : 2009234278

0,80m Conteúdo
TÉC. EM ELETROTÉCNICA
Data
PROJETO ELÉTRICO QGBT 04 / 04 / 2019

PRODUZIDO POR UMA VERSÃO DO AUTODESK PARA ESTUDANTES

Você também pode gostar