Você está na página 1de 7

Cálculos justificativos

Cálculos plano N. º1
SECCION ALIMENTADOR GENERAL:

S = (2 x L x Rho x I) / VP

S= (2 x17.65 x 0.018 x (195.7+28.1)) / 11.4 = 12.37 (mm ˄ 2)

P= 𝑉 × 𝐼 × cos 𝜑 × √3 × 𝑛

𝑃 × 746
𝐼𝑛𝑚 =
𝑉 × cos 𝜑 × √3 × 𝑛

Línea trifásica:

Motor 45 HP:

45𝐻𝑃 × 746
𝐼𝑛𝑚 = = 71.43 𝐴
380 × 0.85 × √3 × 0.84

𝐼𝐴 = 71.43 × 1.25 = 89.28 𝐴 3 × 100 𝐴

Motor 15 HP:

15𝐻𝑃 × 746
𝐼𝑛𝑚 = = 23.81 𝐴
380 × 0.85 × √3 × 0.84

𝐼𝐴 = 23.81 × 1.25 = 29.76 𝐴 3 × 32𝐴


Motor 20 HP:

20𝐻𝑃 × 746
𝐼𝑛𝑚 = = 31.74 𝐴
380 × 0.85 × √3 × 0.84

𝐼𝐴 = 31.74 × 1.25 = 39.67 𝐴 3 × 50𝐴

Línea monofásica:

2 motores 10 HP:

10𝐻𝑃 × 746
𝐼𝑛𝑚 = = 27.49 𝐴
220 × 0.85 × 0.84

𝐼𝐴 = 27.49 × 1.25 = 34.36 𝐴 3 × 40𝐴

𝐼𝑐 = 0.25 × 40 = 10 + 40 = 50𝐴 1 × 40𝐴

8.37 --------3 cables -----3/4”

Motor 5 HP:

5𝐻𝑃 × 746
𝐼𝑛𝑚 = = 13.74 𝐴
220 × 0.85 × 0.84

𝐼𝐴 = 13.74 × 1.25 = 17.17 𝐴 1 × 20𝐴

𝐼𝑐 = 0.25 × 20 = 5 𝑈𝑛𝑖𝑑𝑎𝑑𝑒𝑠

5 x 20 ------ 3 cables ------- ½

P= 𝑉 × 𝐼 × cos 𝜑 × √3 × 𝑛
KW Motores:
Motor 1) 380 × 71.43 × 0.85 × √3 × 0.87 = 34.76 𝐾𝑊
Motor 2) 380 × 27.44 × 0.85 × √3 × 0.87 = 72.72 𝐾𝑊
Motor 3) 380 × 23.81 × 0.85 × √3 × 0.87 = 11.58 𝐾𝑊
Motor 4) 380 × 13.74 × 0.85 × √3 × 0.87 = 3.86 𝐾𝑊
Motor 5) 380 × 31.74 × 0.85 × √3 × 0.87 = 15.44 𝐾𝑊
Motor 6) 380 × 27.49 × 0.85 × √3 × 0.87 = +7.72 𝐾𝑊
81.08 KW
Sección motores:

Motor 1) 100 × 0.25 = 25 + 100 = 125 ------ 42.4 𝑚𝑚2 ------- 2”


Motor 2) 40 × 0.25 = 10 + 40 = 50 ----- 13.3 𝑚𝑚2 ---- 3/4
Motor 3) 32 × 0.25 = 8 + 32 = 40------ 8.37 𝑚𝑚2 ---- 1”
Motor 4) 20 × 0.25 = 5 + 20 = 25------ 3.31 𝑚𝑚2 ------ 16mm
Motor 5) 50 × 0.25 = 12.5 + 50 = 62.5------ 13.3 𝑚𝑚2 ----- 3/4”
Motor 6) 40 × 0.25 = 10 + 40 = 50------ 13.3 𝑚𝑚2 ---- 3/4”

Cálculos piso 1 alumbrado


5100𝑊
𝑐𝑡𝑜 1 = = 23,18 × 0.9 = 20.86 𝐴
220𝑉

20.86 × 1,1
= 1 × 25 𝐴
220 × 0.9

820 𝑊
𝑐𝑡𝑜 2 = = 3.72𝐴 × 0.9 = 3,35 𝐴 1 × 16 𝐴
220𝑉

160 𝑊
𝑐𝑡𝑜 3 = = 0,72 𝐴 × 0.9 = 0,65 𝐴 1×6𝐴
220𝑉

1840 𝑊
𝑐𝑡𝑜 1 𝑒𝑚𝑒𝑟𝑔𝑒𝑛𝑐𝑖𝑎 = = 8,36 𝐴 × 0.9 = 7,52 𝐴 1 × 10 𝐴
220𝑉
(7940 × 0,8) × 1,1
𝐴𝑈𝑇. 𝐺𝑒𝑛𝑒𝑟𝑎𝑙 𝑡𝑟𝑖𝑓𝑎𝑠𝑖𝑐𝑜 = = 11,41 𝐴 3 × 16 𝐴
380 × 0,93 × √3

Cálculos piso 2 alumbrado


580 𝑊
𝑐𝑡𝑜1 = = 2,63 𝐴 × 0.9 = 2,37 𝐴 1×6𝐴
220𝑉

620 𝑊
𝑐𝑡𝑜2 = = 2,18 𝐴 × 0.9 = 1,96 𝐴 1×6𝐴
220 𝑉

820 𝑊
𝑐𝑡𝑜3 = = 3,72 𝐴 × 0.9 = 3,34 𝐴 1×6𝐴
220𝑉

760 𝑊
𝑐𝑡𝑜4 = = 3,45 𝐴 × 0.9 = 3,1 𝐴 1×6𝐴
220𝑉

860 𝑊
𝑐𝑡𝑜5 = = 3,90 𝐴 × 0.9 = 3,51 𝐴 1×6𝐴
220𝑉
620 𝑊
𝑐𝑡𝑜 6 = = 2,81 𝐴 × 0.9 = 2,52 𝐴 1×6𝐴
220𝑉

500 𝑊
𝑐𝑡𝑜 7 = = 2,27 𝐴 × 0.9 = 2,04 𝐴 1×6𝐴
220𝑉

640 𝑊
𝑐𝑡𝑜 8 = = 2,90 𝐴 × 0.9 = 2,61 𝐴 1×6𝐴
220𝑉

600 𝑊
𝑐𝑡𝑜 9 = = 2,72 𝐴 × 0.9 = 2,44 𝐴 1×6𝐴
220𝑉

380 𝑊
𝑐𝑡𝑜 10 = = 1,72 𝐴 × 0.9 = 1,55 𝐴 1×6𝐴
220𝑉
560 𝑊
𝑐𝑡𝑜 11 = = 2,54 𝐴 × 0.9 = 2,28 𝐴 1×6𝐴
220𝑉

360 𝑊
𝑐𝑡𝑜 12 = = 1,63 𝐴 × 0.9 = 1,46 𝐴 1×6𝐴
220𝑉

440 𝑊
𝑐𝑡𝑜 13 = = 2 𝐴 × 0.9 = 1,8 𝐴 1×6𝐴
220𝑉

6400 𝑊
𝑐𝑡𝑜 14 = = 2,9 𝐴 × 0.9 = 1,8 𝐴 1×6𝐴
220𝑉

460 𝑊
𝑐𝑡𝑜 15 = = 2,90 𝐴 × 0.9 = 2,61 𝐴 1×6𝐴
220𝑉

960 𝑊
𝑐𝑡𝑜 16 = = 4,33 𝐴 × 0.9 = 3,89 𝐴 1×6𝐴
220𝑉

AUT. General trifásico


(9800 × 0,8) × 1,1
= 14,08 𝐴 3 × 20 𝐴
380 × 0,93 × √3

Cálculos piso Nº2 Enchufes:


4000 𝑊
𝑐𝑡𝑜 1 = = 18,18 𝐴 × 0.9 = 16,36 𝐴 1 × 25 𝐴
220𝑉

11500 𝑊
𝑐𝑡𝑜 2 = = 52,27 𝐴 × 0.9 = 47,04 𝐴 1 × 50 𝐴
220𝑉

11500 𝑊
𝑐𝑡𝑜 3 = = 52,27 𝐴 × 0.9 = 47,04 𝐴 1 × 50 𝐴
220𝑉
10500 𝑊
𝑐𝑡𝑜 4 = = 47,72 𝐴 × 0.9 = 42,94 𝐴 1 × 50 𝐴
220𝑉

11000 𝑊
𝑐𝑡𝑜 5 = = 50 𝐴 × 0.9 = 45 𝐴 1 × 50 𝐴
220𝑉

13500 𝑊
𝑐𝑡𝑜 6 = = 61,36 𝐴 × 0.9 = 55,22 𝐴 1 × 63 𝐴
220𝑉

13500 𝑊
𝑐𝑡𝑜 7 = = 61,36 𝐴 × 0.9 = 55,22 𝐴 1 × 63 𝐴
220𝑉

13500 𝑊
𝑐𝑡𝑜 8 = = 61,36 𝐴 × 0.9 = 55,22 𝐴 1 × 63 𝐴
220𝑉

11500 𝑊
𝑐𝑡𝑜 9 = = 52,27 𝐴 × 0.9 = 47,04 𝐴 1 × 63 𝐴
220𝑉

8500 𝑊
𝑐𝑡𝑜 10 = = 52,27 𝐴 × 0.9 = 47,04 𝐴 1 × 50 𝐴
220𝑉

14000 𝑊
𝑐𝑡𝑜 11 = = 59,09 𝐴 × 0.9 = 53,18 𝐴 1 × 50 𝐴
220𝑉

8000 𝑊
𝑐𝑡𝑜 12 = = 45,45 𝐴 × 0.9 = 40,95 𝐴 1 × 50 𝐴
220𝑉

8000 𝑊
𝑐𝑡𝑜 13 = = 45,45 𝐴 × 0.9 = 40,95 𝐴 1 × 50 𝐴
220𝑉

9000 𝑊
𝑐𝑡𝑜 14 = = 47,72 𝐴 × 0.9 = 42,94 𝐴 1 × 50 𝐴
220𝑉
7000 𝑊
𝑐𝑡𝑜 15 = = 43,18 𝐴 × 0.9 = 38,86 𝐴 1 × 50 𝐴
220𝑉

6000 𝑊
𝑐𝑡𝑜 16 = = 27,27 𝐴 × 0.9 = 24,54 𝐴 1 × 32 𝐴
220𝑉

(156 × 0,8) × 11
𝑑𝑖𝑠. 𝑔𝑒𝑛 𝑡𝑟𝑖𝑓 = = 1,12𝐴 3 × 10 𝐴
380 × 0,93 × √3