SOLUCION:

Para la red de media tensión:

c∗U MT
I CCMT =
√3∗Z CC
c∗U MT 1.1∗24900
ZCC = =
√ 3∗I CCMT √ 3∗14400
ZCC =1.09816 Ω=Z MT

X MT =0.995∗Z MT =0.995∗1.09816=1.09268 Ω

R MT =0.1∗Z MT =0.1∗X MT =0.1∗1.09268=0.109268 Ω

Z MT =0.109268+ j 1.09268 Ω

ACOMETIDA:

Z A =0.36+ j∗0.335 Ω

Impedancia total en media tensión:

Z MTtotal=0.109268+ j 1.09268+0.36+ j∗0.335

Z MTtotal=0.4693+ j 1.4277 Ω

Relación de transformación:

24900
tr= =62.25
400

Impedancia referida al lado de baja:


0.4693+ j1.4277
Z MBT =
62.252

Z MBT =0.1211+ j 0.3684 m Ω

TRANSFORMADOR:

u cc % 4
∗Un2 ∗400 2
100 100
ZT = =
S 400∗103

ZT =0.016 Ω

Pcu % 3
∗Un2 ∗4002
100 100
RT = =
S 400∗103

RT =0.012 Ω

X T =√ ZT 2−RT 2=√ 0.0162−0.0122

X T =10.5830 m Ω

ZT =12+ j10.5830 m Ω

Factor de corrección:

0.95∗C max 0.95∗1.05


k T= =
X T ∗Sn 10.5830∗10−3∗400∗10 3
1+0.6∗
( Un2 ) 1+0.6∗
( 400 2 )
k T =0.98191

La impedancia corregida será:

ZTc =k T ∗Z T =0.98191∗(12+ j10.5830)

ZTc =11.7829+ j10.3916 m Ω

Alimentador tablero – transformador

Z A =0.388+ j 0.395 mΩ

Impedancia hasta el punto de falla:

Z f =Z MBT + Z Tc + Z A =0.1211+ j 0.3684+11.7829+ j 10.3916+ 0.388+ j 0.395

Z f =12.292+ j11.155 m Ω
El modulo será:

Z f = √12.2922 +11.1552=16.599m Ω

La corriente de cortocircuito permanente será:

I } rsub {K} = {c*U} over {sqrt {3} * {Z} rsub {f}} = {400} over {sqrt {3} *16.599} =13.9129 k ¿

Corriente de pico:

I p=√ 2∗k∗I } rsub {K ¿


−3∗R −3∗12.292
X 11.155
k =1.02+0.98∗e =1.02+0.98∗e

k =1.0559

I p=√ 2∗1.0559∗13.9129

I p=20.774 kA

DETERMINAR LA CORRIENTE DE CORTOCIRCUITO MONOFASICO Y TRIFASICO EN LAS BARRAS


DEL TABLERO:
SOLUCION:

RED DE MEDIA TENSION:

c∗U MT
I CCMT =
√3∗Z CC
c∗U MT 1.1∗6900
ZCC = =
√ 3∗I CCMT √3∗7400
ZCC =0.59217 Ω=Z MT

X MT =0.995∗Z MT =0.995∗0.59217=589.213 mΩ

R MT =0.1∗Z MT =0.1∗X MT =0.1∗598.213=59.8213 m Ω


Z MT =59.8213+ j 589.213 mΩ

Relación de transformación:

6900
tr= =17.25
400

Impedancia referida al lado de baja:

59.8213+ j589.213 m Ω
Z MBT =
17.252

Z MBT =0.201+ j 1.98 mΩ

TRANSFORMADOR:

u cc % 4
∗Un2 ∗400 2
100 100
ZT = =
S 630∗103

ZT =10.1587 m Ω

Un 2 2
400
RT =Pcu∗ ( )
Sn
=7600∗
630∗103 ( )
RT =3.0637 m Ω

X T =√ ZT 2−RT 2=√ 10.15872−3.06372

X T =9.6857 mΩ

ZT =3.0637+ j 9.6857 mΩ

Factor de corrección:

0.95∗C max 0.95∗1.05


k T= = 3
X T ∗Sn −3
9.6857∗10 ∗630∗10
1+0.6∗
( Un2 ) 1+0.6∗
( 400 2 )
k T =0.97518

La impedancia corregida será:

ZTc =k T ∗Z T =0.97518∗(3.0637+ j 9.6857)

ZTc =2.9877+ j9.44338 m Ω

Para el alimentador transformador – tablero general


Para las fases:

Resistencia a 20 °C:

ρ∗l 0.01724∗30
R F= = =2.155 mΩ
s 240

Como son dos conductores en paralelo:

2.155
Rf= =1.0775 mΩ=RN
2

Reactancia:

X =0.09∗30=2.7 m Ω

Z f =1.0775+ j 2.7 mΩ

Z N =1.0775+ j 2.7 m Ω

Alimentador tablero general – tablero de distribución

Resistencia a 20 °C:

ρ∗l 0.01724∗60
R F= = =41.376 m Ω=R N
s 25

Reactancia:

X =0. 112∗6 0=6.72 m Ω

Z f a=41.376+ j6.72 m Ω

Z N a =41.376+ j 6.72 m Ω

Corriente de cortocircuito trifásico:

Z F =0.201+ j 1.98+2.9877+ j9.44338+1.0775+ j2.7 +41.376+ j 6.72

Z F =45.6402+ j19.4955 m Ω

|Z F|=49.6296 mΩ
La corriente de cortocircuito permanente será:

I } rsub {K} = {c*U} over {sqrt {3} * {Z} rsub {f}} = {400} over {sqrt {3} * 49.6296} = 4.6532 k ¿

Corriente de pico:

I p=√ 2∗k∗I } rsub {K ¿


−3∗R −3∗45.6402
X 19.4955
k =1.02+0.98∗e =1.02+0.98∗e

k =1.02087

I p=√ 2∗1.02087∗4.6532

I p 3 ϕ=6.7181kA

Corriente de cortocircuito monofásico:

Z N =1.0775+ j 2.7+ 41.376+ j 6.72

Z N =42.4535+ j8.07 m Ω

Z F + Z N =45.6402+ j19.4955+ 42.4535+ j 8.07=88.0937+ j27.5655

|Z F + Z N |=92.3058 mΩ
La corriente de cortocircuito permanente será:

I } rsub {K} = {c*U} over {sqrt {3} * left lline {Z} rsub {F} + {Z} rsub {N} right rline} = {400} over {sq

Corriente de pico:

I p=√ 2∗k∗I } rsub {K ¿


−3∗R −3∗88.0937
X 27.5655
k =1.02+0.98∗e =1.02+0.98∗e

k =1.0200672

I p=√ 2∗1.0200672∗2.5019

I p 1ϕ =3.609 kA

.- Determinar la corriente de cortocircuito trifásico en la barra del tablero general de


una instalación industrial, con la siguiente información.

a) Características de la red primaria


Corriente de cortocircuito trifásico; 11.5 (kA).
Tensión; 24.9 (kV)

b) Transformador.
Potencia 630 (kVA)
Tension nominal secundario: 420 (V).
Ucc(%); 4 (%)
Pérdidas de potencia Pcu (W); 4170 con carga.

c) Dos conductores de 240 (mm2) por fase, que conecta el transformador con el tablero
general.
Longitud 20 (m)

d) Conexión a la barra del tablero; 2 motores:


Cada motor con potencia: 55 (kW), fp 0.89, rendimiento 93.9 (%), reactancia
subtransitoria.
X” del 25 (%).
Cable de 35 (mm2)
Longitud del motor 1; 20 (m)
Longitud del motor 2; 35 (m)