Você está na página 1de 9

COBRE ALUMINIO

S r DMG RMG R20°C R40°C XL K S mm² 35


mm² mm mm mm Ohmio/KmOhmio/KmOhmio/KmOhmio/Km
25 3.20 1008 2.323 0.741 0.798 0.458 1.589 R20°C Ohmio/Km 0.978
1008 0.000 0.000 #DIV/0! #DIV/0! R40°C Ohmio/Km 1.053
50 4.45 1008 3.231 0.395 0.425 0.433 0.990 r mm 3.78
DMG mm 1008
RMG mm 2.744
XL Ohmio/Km 0.445
K Ohmio/Km 1.977
CALCULOS ELECTRICOS EN REDES DE MEDIA TENSION

PROYECTO REMODELACION DE REDES DE DISTRIBUCION PRIMARIA, SECUNDARIA Y CONEXIONES DOMICILIARIAS DEL


CENTRO CIVICO Y ALAMEDA GRAU - BARRIO LA SOLEDAD PERDIDA
DISTRITO : HUARAZ SISTEMA TRIFASICO POTENCIA
PROVINCIA : HUARAZ TENSION : 13.8 kV #NAME?
DEPARTAMENTO : ANCASH

P
U CONDUCTOR POTENCIA SUMA I L K CAIDA DE SUMA CAIDA DE PERDIDA
N COBRE DE POTENCIA TENSION CAIDA DE TENSION POTENCIA
T TRANSF. TRANSF. TENSION (kW)
O (mm²) (KVA) (KVA) (AMP.) (Km) (W/Km) (V) (V) (%)
0.00% 0
PA 50 0.0 3087.5 129.17 0.000 0.990 345.00 345.000 2.50% 55.575 0.00
P1 50 50.0 1817.5 76.04 0.138 0.990 10.39 355.386 2.58% #NAME? 0.14
P2 50 50.0 1767.5 73.95 0.140 0.990 10.25 365.633 2.65% #NAME? 0.28
P3 50 75.0 1717.5 71.86 0.279 0.990 19.84 385.476 2.79% #NAME? 0.56
P4 50 0.0 1642.5 68.72 0.120 0.990 8.16 393.638 2.85% #NAME? 0.68
P5 50 0.0 1542.5 64.53 0.089 0.990 5.68 399.323 2.89% #NAME? 0.77
P6 50 160.0 1442.5 60.35 0.107 0.990 6.39 405.714 2.94% #NAME? 0.87
P7 50 37.5 1132.5 47.38 0.256 0.990 12.01 417.720 3.03% #NAME? 1.13
P8 50 0.0 1095.0 45.81 0.054 0.990 2.45 420.168 3.04% #NAME? 1.18
P9 50 100.0 400.0 16.73 0.060 0.990 0.99 421.162 3.05% #NAME? 1.24
P10 50 0.0 300.0 12.55 0.139 0.990 1.73 422.889 3.06% #NAME? 1.38
P11 50 0.0 200.0 8.37 0.117 0.990 0.97 423.858 3.07% #NAME? 1.50
P12 50 100.0 100.0 4.18 0.138 0.990 0.57 424.429 3.08% #NAME? 1.64

P4.1 25 100.0 100.0 4.18 0.350 1.589 2.33 395.965 2.87% #NAME?

P5.1 25 100.0 100.0 4.18 0.185 1.589 1.23 400.553 2.90% #NAME?

P6.1 25 100.0 150.0 6.28 0.145 1.589 1.45 407.160 2.95% #NAME?
P6.2 25 50.0 50.0 2.09 0.087 1.589 0.29 407.450 2.95% #NAME?

P8.a 25 160.0 360.0 15.06 0.124 1.589 2.97 423.136 3.07% #NAME?
P8.b 25 0.0 200.0 8.37 0.198 1.589 2.63 425.769 3.09% #NAME?
P8.c 25 100.0 100.0 4.18 0.100 1.589 0.66 426.434 3.09% #NAME?

P8.b1 25 100.0 100.0 4.18 0.056 1.589 0.37 426.141 3.09% #NAME?

P8.1 50 0.0 335.0 14.02 0.453 0.990 6.28 426.453 3.09% #NAME?
P8.2 25 75.0 175.0 7.32 0.147 1.589 1.71 428.163 3.10% #NAME?
P8.3 25 100.0 100.0 4.18 0.135 1.589 0.90 429.060 3.11% #NAME?

P8.1.1 25 160.0 160.0 6.69 0.277 1.589 2.95 429.399 3.11% #NAME?

P10.1 25 100.0 100.0 4.18 0.046 1.589 0.31 423.195 3.07% #NAME?

P11.1 25 100.0 100.0 4.18 0.168 1.589 1.12 424.975 3.08% #NAME?
1 50 75.0 1270.0 53.13 0.032 0.990 1.68 346.683 2.51% #NAME?
2 50 50.0 1095.0 45.81 0.230 0.990 10.43 357.112 2.59% #NAME?
3 50 100.0 1045.0 43.72 0.194 0.990 8.40 365.507 2.65% #NAME?
4 50 0.0 945.0 39.54 0.097 0.990 3.80 369.303 2.68% #NAME?
5 50 100.0 895.0 37.44 0.085 0.990 3.15 372.453 2.70% #NAME?
6 50 0.0 595.0 24.89 0.181 0.990 4.46 376.913 2.73% #NAME?
7 50 0.0 495.0 20.71 0.075 0.990 1.54 378.450 2.74% #NAME?
8 50 0.0 395.0 16.53 0.069 0.990 1.13 379.579 2.75% #NAME?
9 50 75.0 235.0 9.83 0.096 0.990 0.93 380.513 2.76% #NAME?
10 25 160.0 160.0 6.69 0.069 1.589 0.73 381.247 2.76% #NAME?

1.1 25 100.0 100.0 4.18 0.140 1.589 0.93 347.614 2.52% #NAME?

4.1 25 50.0 50.0 2.09 0.185 1.589 0.61 369.918 2.68% #NAME?

5.1 50 100.0 200.0 8.37 0.228 0.990 1.89 374.341 2.71% #NAME?
5.2 50 100.0 100.0 4.18 0.172 0.990 0.71 375.054 2.72% #NAME?

5.1.1 25 10.0 10.0 0.42 0.102 1.589 0.07 374.409 2.71% #NAME?

6.1 25 10.0 100.0 4.18 0.069 1.589 0.46 377.371 2.73% #NAME?

7.1 25 10.0 100.0 4.18 0.115 1.589 0.76 379.215 2.75% #NAME?

8.1 25 10.0 160.0 6.69 0.108 1.589 1.15 380.728 2.76% #NAME?

DV1 = 345.00 V (2.5%) - CAIDA DE TENSION ASUMIDO EN EL PUNTO 1


PJ = 55.58 kW (2%) - PERDIDA DE POTENCIA ASUMIDO EN EL PUNTO 1

CAIDA DE TE N S I O N

0.03
0.03
CAIDA TENSION (% )

0.03
0.03
0.02
0.00 0.14 0.28 0.56 0.68 0.77 0.87 1.13 1.18 1.24 1.38 1.50 1.64

LONGITUD (km )
SAB. N° VI0119 - CAIDA DE TENSION - SERV. PARTICULAR
CIRCUITO: C2-SP

PROYECTO : SIST. DE DISTRIB. SECUNDARIA DE S.P. y A.P. EN 380-220V. PARA LA HABILITACION URBANA SAN AGUSTIN II ETAPA
CIRCUITO N° 2 (S.P)
DISTRITO : VIRÚ SISTEMA TRIFASICO
PROVINCIA : VIRÚ TENSION (V):
DEPARTAMENTO : LA LIBERTAD 380
UBICACIÓN : PREDIO STA. ELENA Y ANEXOS - LOTE "D" U.C. 05346

P
U CONDUCTOR NUMERO SUMA POTENCIA I L K CAIDA DE SUMA CAIDA DE
N CAAI-S DE DE SP TENSION CAIDA DE TENSION
T LOTES LOTES TENSION CABLE NYY 16mm2, 80 C°
O (mm²) (KW) (AMP.) (mt) (W/Km) (V) (V) (%)

0 35 0.0 81.0 28.35 47.92 0.00 2.210 0.00 0.000 0.00


P1 35 27.0 81.0 28.35 47.92 11.00 2.210 2.02 2.015 0.53
P2 35 0.0 54.0 18.90 31.94 47.00 2.210 5.74 7.755 2.04 4.31
P3 35 30.0 54.0 18.90 31.94 45.00 2.210 5.50 13.251 3.49
P4 35 24.0 24.0 8.40 14.20 60.00 2.210 3.26 16.508 4.34

418.00

P1 2.015 0.53
P1.1 25 12.0 27.0 9.45 15.97 43.00 2.210 2.63 4.641 1.22
P1.2 25 15.0 15.0 5.25 8.87 60.00 2.210 2.04 6.676 1.76
SAB. N° VI0119 - CAIDA DE TENSION - SERV. PARTICULAR
CIRCUITO: C1-SP

PROYECTO : SIST. DE DISTRIB. SECUNDARIA DE S.P. y A.P. EN 380-220V. PARA LA HABILITACION URBANA SAN AGUSTIN II ETAPA
CIRCUITO N° 1 (S.P)
DISTRITO : VIRÚ SISTEMA TRIFASICO
PROVINCIA : VIRU TENSION (V):
DEPARTAMENTO : LA LIBERTAD 380
UBICACIÓN : PREDIO STA. ELENA Y ANEXOS - LOTE "D" U.C. 05346

P
U CONDUCTOR NUMERO SUMA POTENCIA I L K CAIDA DE SUMA CAIDA DE
N CAAI-S DE DE SP TENSION CAIDA DE TENSION
T LOTES LOTES TENSION
O (mm²) (KW) (AMP.) (mt) (W/Km) (V) (V) (%)

0 35 0.0 81.0 28.35 47.92 0.00 1.620 0.00 0.000 0.00


P1 35 27.0 81.0 28.35 47.92 11.00 1.620 1.48 1.477 0.39
P2 35 0.0 54.0 18.90 31.94 38.00 1.620 3.40 4.879 1.28
P3 25 24.0 54.0 18.90 31.94 38.00 2.210 4.64 9.520 2.51
P4 25 30.0 30.0 10.50 17.75 60.00 2.210 4.07 13.591 3.58

P1 1.477 0.39
P1.1 25 15.0 27.0 9.45 14.37 30.00 2.210 1.65 3.126 0.82
P1.2 25 12.0 12.0 4.20 6.39 60.00 2.210 1.47 4.591 1.21

SAB. N° VI0119 - CAIDA DE TENSION - SERV. PARTICULAR


CIRCUITO: C3-SP
PROYECTO : SIST. DE DISTRIB. SECUNDARIA DE S.P. y A.P. EN 380-220V. PARA LA HABILITACION URBANA SAN AGUSTIN II ETAPA
CIRCUITO N° 3 (S.P)
DISTRITO : VIRU SISTEMA TRIFASICO
PROVINCIA : VIRU TENSION (V):
DEPARTAMENTO : LA LIBERTAD 380
UBICACIÓN : PREDIO STA. ELENA Y ANEXOS - LOTE "D" U.C. 05346

P
U CONDUCTOR NUMERO SUMA POTENCIA I L K CAIDA DE SUMA CAIDA DE
N CAAI-S DE DE SP TENSION CAIDA DE TENSION
T LOTES LOTES TENSION
O (mm²) (KW) (AMP.) (mt) (W/Km) (V) (V) (%)

0 35 0.0 27.0 9.45 14.37 0.00 1.620 0.00 0.000 0.00


P1 35 0.0 27.0 9.45 14.37 11.00 1.620 0.44 0.443 0.12
P2 35 0.0 27.0 9.45 14.37 47.00 1.620 1.89 2.337 0.61
P3 35 0.0 27.0 9.45 14.37 32.00 1.620 1.29 3.626 0.95
P4 25 12.0 27.0 9.45 14.37 45.00 2.210 2.47 6.099 1.60
P5 25 15.0 15.0 5.25 7.99 60.00 2.210 1.83 7.931 2.09
SAB. N° VI0119 - CAIDA DE TENSION - ALUMBRADO PUBLICO
CIRCUITO: C1 - A.P.

SECCIÓN : SIST. DE DISTRIB. SECUNDARIA DE S.P. y A.P. EN 380-220V. PARA LA HABILITACION URBANA SAN AGUSTIN II ETAPA
CIRCUITO N° 1 (A.P)
DISTRITO : VIRU SISTEMA MONOFASICO
PROVINCIA : VIRU TENSION :
DEPARTAMENTO : LA LIBERTAD 220
UBICACION : PREDIO STA. ELENA Y ANEXOS - LOTE "D" U.C. 05346

P
U CONDUCTOR NUMERO SUMA POTENCIA I L K CAIDA DE SUMA CAIDA DE
N CAAI-S DE DE AP TENSION CAIDA DE TENSION
T LAMP LAMP TENSION
O (mm²) (KW) (AMP.) (Km) (W/Km) (V) (V) (%)

0 16 0.0 14.0 1.078 5.44 0.00 3.960 0.000 0.000 0.00 CABLE NYY 10mm2, 80 C°
P1 16 6.0 14.0 1.078 5.44 11.00 3.960 0.474 0.474 0.22
P2 16 1.0 8.0 0.616 3.11 7.00 3.960 0.172 0.647 0.29
P3 16 1.0 7.0 0.539 2.72 38.00 3.960 0.819 1.466 0.67
P4 16 3.0 6.0 0.462 2.33 38.00 3.960 0.702 2.168 0.99
P5 16 1.0 3.0 0.231 1.17 60.00 3.960 0.554 2.723 1.24
P6 16 1.0 2.0 0.154 0.78 30.00 3.960 0.185 2.908 1.32
P7 16 1.0 1.0 0.077 0.39 16.00 3.960 0.049 2.957 1.34

P1 0.474 0.474 0.22


P1.1 16 3.0 5.0 0.385 1.94 60.00 3.960 0.924 1.398 0.64
P1.2 16 1.0 2.0 0.154 0.78 60.00 3.960 0.370 1.768 0.80
P1.3 16 1.0 1.0 0.077 0.39 17.00 3.960 0.052 1.820 0.83
SED. N° 1 - CAIDA DE TENSION - ALUMBRADO PUBLICO

CIRCUITO: C2- A.P.

SECCIÓN : SIST. DE DISTRIB. SECUNDARIA DE S.P. y A.P. EN 380-220V. PARA LA HABILITACION URBANA SAN AGUSTIN II ETAPA
CIRCUITO N° 2 (A.P)
DISTRITO : VIRU SISTEMA MONOFASICO
PROVINCIA : VIRU TENSION :
DEPARTAMENTO : LA LIBERTAD 220
UBICACION : PREDIO STA. ELENA Y ANEXOS - LOTE "D" U.C. 05346

P
U CONDUCTOR NUMERO SUMA POTENCIA I L K CAIDA DE SUMA CAIDA DE
N NYY DE DE AP TENSION CAIDA DE TENSION
T LAMP LAMP TENSION
O (mm²) (KW) (AMP.) (Km) (W/Km) (V) (V) (%)

0 16 0.0 0.0 0.000 0.00 0.00 3.960 0.000 0.000 0.00


P1 16 1.0 8.0 0.616 3.11 11.00 3.960 0.271 0.271 0.12
P2 16 1.0 7.0 0.539 2.72 30.00 3.960 0.647 0.918 0.42
P3 16 3.0 6.0 0.462 2.33 60.00 3.960 1.109 2.027 0.92
P4 16 1.0 3.0 0.231 1.17 73.00 3.960 0.675 2.701 1.23
P5 16 1.0 2.0 0.154 0.78 30.00 3.960 0.185 2.886 1.31
P6 16 1.0 1.0 0.077 0.39 30.00 3.960 0.092 2.978 1.35

SAB. N° VI0119 - CAIDA DE TENSION - ALUMBRADO PUBLICO


CIRCUITO: C3- A.P.

SECCIÓN : SIST. DE DISTRIB. SECUNDARIA DE S.P. y A.P. EN 380-220V. PARA LA HABILITACION URBANA SAN AGUSTIN II ETAPA
CIRCUITO N° 3 (A.P)
DISTRITO : VIRU SISTEMA MONOFASICO
PROVINCIA : VIRU TENSION :
DEPARTAMENTO : LA LIBERTAD 220
UBICACION : PREDIO STA. ELENA Y ANEXOS - LOTE "D" U.C. 05346

P
U CONDUCTOR NUMERO SUMA POTENCIA I L K CAIDA DE SUMA CAIDA DE
N NYY DE DE AP TENSION CAIDA DE TENSION
T LAMP LAMP TENSION
O (mm²) (KW) (AMP.) (Km) (W/Km) (V) (V) (%)

0 16 0.0 0.0 0.000 0.00 0.00 3.960 0.000 0.000 0.00


P1 16 0.0 10.0 0.770 3.89 11.00 3.960 0.339 0.339 0.15
P2 16 5.0 10.0 0.770 3.89 47.00 3.960 1.448 1.786 0.81
P3 16 3.0 5.0 0.385 1.94 47.00 3.960 0.724 2.510 1.14
P4 16 2.0 2.0 0.154 0.78 75.00 3.960 0.462 2.972 1.35

P2 4.312 1.96
P2.1 16 3.0 5.0 0.385 1.94 45.00 3.960 0.693 5.005 2.28
P2.2 16 2.0 2.0 0.154 0.78 75.00 3.960 0.462 5.467 2.49